On a GE Zoneline AZ45 or AZ65, the fault codes are shown from OFF: hold the fan button and the red auxiliary set button together, and each stored code flashes for 3 seconds. Many clear themselves: F1 and F2, the fan faults, after 10 minutes, and F9, a frozen indoor coil, once it warms past 50°F. F26 stops cooling below 35°F outside and clears above 40°F.
A GE Zoneline is the through-the-wall heating and cooling unit found in many apartments, hotels and additions. It keeps its faults as F codes, and GE’s technical service guide lists every one with what it stops and how it clears.
This page covers the AZ45 series, which cools and heats with electric resistance heat, and the AZ65 series, a heat pump with electric heat as well. Many of its codes clear on their own once the condition passes.
Before you start
What to carry: a torch and a pen. Ten minutes.
Gas or electric? Electric. The Zoneline runs on 230/208 or 265 volts through a power cord kit, and GE says every new cord has an LCDI protector built in.
Know the model. GE’s model number tells you the series: AZ45 is cooling with electric heat, AZ65 a heat pump with electric heat. The model and serial label is on the unit.
A code that keeps coming back. The sensor, fan and board codes need a technician once they return after clearing.
How to show the codes
Read the stored codes
Enter the mode. GE says with the Zoneline in OFF, press and hold the fan button and the red auxiliary set button together. The red button sits behind the room cabinet, below the controls.
Read them. Each active code shows for 3 seconds on and off. If there are none, the display flashes two dashes.
It leaves by itself. GE says it shows every code three times, then returns to OFF after another 30 seconds. Any other button takes it out of the mode.
Clearing them. Pressing AUX clears the stored faults. Write them down first.
The codes that clear on their own
Give it time
F1 and F2, the fans. GE says a fan that misses its speed shuts down for 15 minutes and tries again every 15 minutes. F1 stops all heating and cooling. F2 leaves resistance heat and the fan. Both clear after 10 minutes.
F9, a frozen indoor coil. Below 34°F, the compressor stops until the coil warms. GE says it restarts at 50°F, and not before its 3 minute minimum off time: why a coil freezes.
F10 and F11, too hot. F10 is an AZ65 indoor coil over 131°F, clearing below 122°F. F11 is room air over 95°F at the inlet, which stops the compressor and heat until it drops below 85°F.
F25, a failed defrost. On heat pump models, five defrosts in a row that fail to warm the outdoor coil above 68°F lock out the heat pump. GE says it clears itself after 4.5 days.
F26, too cold to cool. On heat pump models, cooling is locked out when it is below 35°F outside, and it clears above 40°F.
The full list
| Code | What GE’s guide says |
|---|---|
| F1 | Indoor fan not at its speed: no heating or cooling. Clears after 10 minutes |
| F2 | Outdoor fan not at its speed: resistance heat and fan only. Clears after 10 minutes |
| F3 | External thermostat wiring signal not valid: internal control only |
| F4 | Indoor thermistor out of range: fan only |
| F5 | Outdoor thermistor out of range: resistance heat or fan only |
| F6 | Compressor: no temperature change after 1 minute. Clears after 3 minutes |
| F7 | Reversing valve not changing temperature as expected. Clears after 3 minutes |
| F8 | Software fault |
| F9 | Indoor coil below 34°F: compressor off until it warms past 50°F |
| F10 | Heat pump indoor coil over 131°F: outdoor fan off until below 122°F |
| F11 | Inlet air over 95°F: compressor and heat off until below 85°F |
| F12 | User interface board disconnected or failed |
| F13 | Heater airflow: indoor fan speed too low, no electric heat or heat pump |
| F16, F23, F24 | The make-up air module: communication, a fault, or its vent door |
| F17, F18, F19 | Outlet air sensor failed, or outlet air too hot: no resistance heat |
| F25 | Abnormal defrost on heat pump models: clears after 4.5 days |
| F26 | Cooling locked out below 35°F outside: clears above 40°F |
Things that look like faults
Know what it does on purpose
The fan pulses on its own. GE says that when it is set to cycle cooling and not on a wall thermostat, it waits 6 minutes after the compressor stops, then runs the fan on low for 30 seconds to check the room temperature.
It will not run at all in a hotel or apartment. GE says a Central Desk Control switch, when closed, stops the fan, cooling and heat from the unit’s own controls.
It heats with nobody asking. GE’s Freeze Sentinel, when set, keeps the room above 41°F with the electric heater. Its Heat Sentinel, when set, cools a room that reaches 85°F.
Water on the heat pump. On the AZ65, GE says the unit pumps condensate from its base pan onto the warm indoor coil, where it evaporates into the room.
When to call
Hand these over
Sensors and boards. F4, F5, F12 and F17 are sensors or a board, and F8 a software fault.
Codes that return. A fan, compressor or reversing valve code that clears and comes back points at the part named.
Filters first. GE sells replacement room front air filters for the AZ45 and AZ65. A clogged one starves the indoor coil of air: a room unit that is not cooling.
What each one costs
| The fix | Cost |
|---|---|
| Filter washed | Nothing |
| Unplug and reset | Nothing |
| Plug, outlet or breaker reset | Nothing |
| Sensor or board on a serviceable unit | A service call |
Questions people ask
How do I see the error codes on a GE Zoneline?
With it switched OFF, hold the fan button and the red auxiliary set button together. Each stored code shows for 3 seconds. Two flashing dashes means none.
How do I clear GE Zoneline error codes?
In the same code display mode, press AUX. GE says that clears the stored faults. Write them down first.
What does F9 mean on a GE Zoneline?
The indoor coil fell below 34°F. The compressor stops until the coil warms past 50°F, then restarts after its 3 minute minimum.
What does F26 mean on a GE Zoneline?
On heat pump models, cooling is locked out below 35°F outside. GE says it clears once it is above 40°F.
Why does my Zoneline fan turn on by itself?
GE says it pulses the fan on low for 30 seconds, 6 minutes after the compressor stops, to check the room temperature. Freeze Sentinel can also run the heater to keep the room above 41°F.
Why won’t my Zoneline turn on at all?
Check the power cord’s LCDI button and the circuit. In a hotel or apartment, GE’s Central Desk Control switch can stop the unit from the front desk.
Sources: GE Appliances 2019 Zoneline Air Conditioner Technical Service Guide 31-9301 Rev. 3 (January 2021), for the AZ45 and AZ65 230/208 volt models
By



