Bosch Furnace Error Codes: BGH96 E1 to E8 and FL

Bosch Furnace Error Codes: BGH96 E1 to E8 and FL
Short answer

On Bosch's BGH96 Rev C furnace, E1 to E4 concern the pressure switch circuits, E5 and E6 concern limits, E7 is ignition lockout, and E8 is lockout after flame dropouts. FL means low flame sensing current. H1 and H2 are heating stages, not faults.

Bosch furnace error codes E7 and E8 describe two different failures on the BGH96 Rev C: ignition that did not succeed, and a flame that kept dropping out. Bosch’s troubleshooting chart separates them even though both leave you with a furnace that will not heat.

This guide follows the BGH96 Rev C gas furnace manual dated June 2025. Match that revision before using the chart. A code on a Bosch outdoor unit belongs in the Bosch IDS heat pump guide; a Greenstar boiler has its own Bosch boiler code guide.

Before you start

What to carry: a torch, your model information and a phone or pen. Record the complete display, including letters. Note whether the furnace never lit, stopped after warming the house, or still runs.

Gas or electric? The BGH96 covered here is a gas furnace. This is the integrated furnace control’s chart, not a universal list for every board in a Bosch heating system.

Keep access safe. Read a display only if it is visible without opening the cabinet. Leave panels and internal buttons to the service person. Bosch requires all electrical power disconnected before servicing.

Renting? Send the model, display and heating symptoms to your property manager so they can arrange the right visit.

Deal with gas and overheating before the display.
Bosch says that if you smell gas, do not light an appliance, touch electrical switches or use a phone inside. Leave immediately. Call the gas supplier at once from a neighbor’s phone and follow its instructions. If the supplier cannot be reached, call the fire department.

If the gas supply fails to shut off or the furnace overheats, Bosch requires the gas valve shut before electrical power is turned off. Do not approach a dangerous furnace to reach it.

Bosch reserves installation and service for a qualified installer, service agency or gas supplier. Leave gas pressure, combustion, wiring and safety switch work to them. A limit or unexpected flame indication is not an invitation to force another heating cycle.

Normal displays and the BGH96 fault chart

BGH96 REV C: THESE ARE OPERATING DISPLAYSH1AFirst stage heatingA heating mode in Bosch's diagram.Record any separate no heat symptom.H2BSecond stage heatingThe second heating stage is active.It is not an error number.CFCContinuous fanThe fan operation code.Keep this distinct from fault codes.Source: Bosch BTC 772003301 C, figure 66.
Bosch's BGH96 Rev C wiring diagram separates operation codes from faults. H1, H2 and CF describe what the furnace is doing.
Check 1Reading the display, with no parts needed

Check whether it is an operating display

Bosch’s figure 66 labels H1 first stage heating, H2 second stage heating and CF continuous fan. C1 and C2 are the cooling stages, while dF is defrost. These are operation codes in that diagram.

An operating label does not tell you whether the house has reached the thermostat setting. The broader furnace not working guide covers the no heat complaint.

Bosch’s troubleshooting tables 37 and 38 give these fault descriptions for the Rev C integrated control. The grouped limit entry is kept together here because the table lists several open durations against E5 and E6.

Display Meaning in Bosch’s troubleshooting chart
No display or FO Power, fuse, circuit breaker or internal control fault
FE Flame sensed with the gas valve off
E1 Pressure switch closed with the inducer off
E2 Low fire pressure switch open with the inducer on
E3 High fire pressure switch open with high inducer operation
E4 Pressure switch cycle lockout
E5 / E6 Open limit or rollout circuit and related lockout
E7 Lockout after failed ignition
E8 Lockout after too many flame dropouts
PR Incorrect line voltage polarity
BE Control failure
nL Abnormal thermostat signals
FL Low flame sensing current

Pressure and limit faults need different checks

Check 2Vent, pressure circuit and wiring diagnosis

Keep the pressure code with the service report

For E1, Bosch lists stuck pressure switch contacts or a short in that circuit. For E2, E3 and E4, its checks include the hose, flue, inducer, switch and wiring. The number matters because it identifies a different operating condition.

Tell the technician if the small exhaust blower runs while ignition never follows. Bosch lists that symptom beside the E2, E4 and E3 group. The pressure switch guide explains the circuit’s purpose; leave hose removal and electrical tests for service.

Check 3Airflow and combustion checks before a parts decision

Treat E5 and E6 as a limit investigation

Bosch’s limit fault list includes blocked filters, restrictive ducts, blower speed or failure, burner alignment, a blocked flue and wiring. That range of causes is why a filter change alone cannot establish that the furnace is safe to restart.

For routine filter care, Bosch calls for the same type and size when replacing a disposable filter. Its external rack instructions depend on the installed rack kit. If maintenance is due, use those instructions with the electrical supply disconnected and secure the rack afterward. Bosch says the airflow arrow must point toward the blower.

Bosch distinguishes the automatic primary limit from the manually reset rollout limits in section 13. Leave a rollout reset to the service investigation; the rollout switch guide explains what that protection watches.

Ignition lockout and a weak flame signal

BGH96 REV C: THREE DIFFERENT FLAME REPORTSE7AFailed ignition lockoutThe control did not establish ignition.Service checks ignition and fuel supply.E8BFlame dropout lockoutToo many interruptions of the flame.Report whether heat started, then stopped.FLCLow flame sensing currentBosch lists sensor and flame checks.Sensor cleaning belongs to service.Source: Bosch BTC 772003301 C, table 38 and section 15.4.
Bosch separates failure to light, repeated flame loss and low sensing current. Keep the exact code with the symptom you observed.
Check 4Ignition, flame sensing and fuel supply diagnosis

Describe what happened before E7, E8 or FL

Bosch’s E7 and E8 checks include the gas valve setting, igniter, blocked orifices, flame sensor, grounding and gas pressure. FL has its own list: a coated or misplaced sensor, or a weak burner flame associated with gas pressure or combustion air.

Describe what you already noticed without opening the furnace to watch another attempt. Bosch places flame sensor cleaning in a section marked for qualified service technicians.

For failed ignition lockout, Bosch’s section 14.2 describes an automatic retry after one hour. It also describes power interruption or a thermostat cycle lasting 1 to 20 seconds. Those are reset methods, not repairs: Bosch says the control returns to lockout if the original condition remains.

Give a recurring fault to the service person rather than using repeated resets to keep the heat going. Keep the emergency and limit warnings above ahead of any restart decision.

What each one takes

Problem Work involved
E1 to E4 Testing the pressure circuit, venting and inducer
E5 or E6 Finding the open limit and checking airflow and combustion
E7, E8 or FL Ignition and flame signal measurements, with fuel checks as needed
PR, BE or nL Electrical, control or thermostat diagnosis
Filter maintenance A matching disposable filter or the installed filter’s cleaning procedure

Questions people ask

Where is the Bosch furnace error code PDF?

The BGH96 Rev C manual has the troubleshooting charts on pages 69 and 70. Match the revision as well as the furnace family.

Does a blank display prove the board is bad?

No. Bosch’s table also lists missing power, an open door switch, loose connections, a blown fuse or a circuit breaker problem. Its service procedure checks the supply and fuse before deciding on the control.

What should I report with nL?

In this Rev C chart, Bosch calls nL an abnormal thermostat signal and lists thermostat wiring or failure. Mention recent thermostat work and the full furnace model without moving any wires yourself.

Can the technician read older faults?

Yes. Bosch’s figure 66 describes an internal SW1 query that displays the last ten error codes, newest first. Leave that internal control access to the technician.

Does FE mean I should clean the flame sensor?

Bosch’s troubleshooting table defines FE as flame sensed with the gas valve off and directs service to a possible short at the sensor or its wiring. It is separate from the FL low current entry.

The other furnace guides: reading the light, failure to ignite and limit switch trips.

Sources: Bosch BGH96 Rev C Installation and Operating Instructions, BTC 772003301 C (06.2025), safety instructions, sections 13 to 15, tables 37 and 38, and figure 66. https://www.bosch-homecomfort.com/us/media/country_pool/documents/installation-manuals/bgh96_furnace_revc_iom_en_06.2025.pdf