Bryant's 926TB checks pressure switches and completes a purge before energizing its hot surface igniter. Once flame is proved, its blower timing differs between low and high heat. Identify which event is missing before assuming that no warm air means a failed igniter.
A Bryant furnace not igniting needs its starting sequence checked before an igniter is blamed. Bryant’s 926TB instructions put pressure proving and a purge ahead of igniter warmup. If that earlier work never finishes, the missing glow is only where you noticed the trouble.
The model here is Bryant’s two stage, noncommunicating 926TB, using II926TB-04 revision D from June 2023. For its numbered light patterns, see Bryant furnace error codes. This page follows the events behind the heating attempt rather than listing those codes again.
Before you start
What to carry: bring a torch for the equipment label and your phone for a startup record. Capture the full model, thermostat type, fault indication and the last startup event you observed. Mention a recently changed wall control or any work on the furnace.
Gas or electric? Bryant identifies the 926TB as a condensing gas furnace with a hot surface igniter. These burner checks do not apply to electric resistance heat in an air handler.
Renting? Let the property manager arrange the repair with that information. The checks below describe symptoms without opening the burner or control compartment.
For a persistent burning smell without a gas odor, Bryant says to turn off the furnace and have a qualified HVAC professional inspect it.
Bryant’s 926TB manual requires electrical disconnection before service, with the main disconnect off and a lockout tag for service work. Bryant warns that accessories and the cooling unit may have additional electrical supplies that must be shut off during furnace service. Bryant prohibits bypassing or closing the door switch with the blower door removed. Leave live measurements, gas work and the service test routines to trained personnel.
Start with the thermostat arrangement
Tell service which control is asking for heat
Bryant permits a single stage thermostat with the 926TB control choosing furnace stages, or a two stage thermostat controlling staging. Bryant’s installer instructions assign different setup switch positions to those arrangements.
In its adaptive operation with a single stage thermostat, Bryant says the 926TB can start in either low or high heat. Do not assume that every attempt must begin on low heat, and do not change a setup switch to force the behavior you expected.
If the furnace remains silent throughout the request, the general furnace troubleshooting guide covers power and thermostat checks. Use the stages below when the furnace begins a heating attempt.
The purge comes before the glow
Report whether the attempt got beyond the exhaust fan
Bryant first checks that the low and high heat pressure switches are open, then starts the 926TB inducer at high speed. In Bryant’s low heat startup description, closing the low heat pressure switch starts a 15 second purge.
If that low heat switch fails to stay closed, Bryant keeps the inducer running at high speed. Bryant begins a new 15 second purge after the switch closes again.
Only at the end of the purge does Bryant energize the hot surface igniter for its 17 second warmup. A small fan that runs without progressing to ignition therefore needs its proving sequence traced.
Describe what you heard and what was visible through the existing opening. Do not remove pressure tubing or fit a jumper to make the next step happen. The furnace pressure switch guide explains the surrounding vent and proving system.
When the igniter glows but flame does not stay
Separate gas admission from flame confirmation
After warmup, Bryant closes the main gas valve relay and energizes the valve to admit gas to the burners. Bryant starts a two second flame proving period five seconds after that relay closes.
Bryant keeps the igniter energized until flame is sensed or that proving period begins. An igniter going dark at that point is not, by itself, a reason to replace it.
If flame is not proved in the required period, Bryant closes the gas valve and permits up to three further ignition trials before lockout. Tell service whether the attempt produced no flame or a flame that disappeared.
The flame sensor guide explains the separate sensing part. Let the technician establish whether ignition, gas delivery or flame confirmation failed before deciding which part needs work.
When it lights before warm air arrives
Keep the firing stage with the blower observation
Once flame is proved, Bryant’s 926TB low heat sequence turns on the indoor blower 45 seconds after the main gas valve opens. Bryant’s high heat sequence instead starts it 25 seconds after that opening.
Bryant measures these delays from when the gas valve opens. Do not time from the thermostat button press and treat the result as a failed blower test.
Report whether you saw flame before the room airflow began, and whether useful heating followed. If flame was maintained but the room air stayed cool, the furnace blowing cold air guide is the next branch.
When there is low heat during a request for higher heat
Describe partial heating as well as a failed start
For a selected high heat startup, Bryant describes a 15 second purge beginning after the low heat pressure switch closes. If the high heat switch has not closed but the low heat switch has, Bryant permits low heat gas flow while waiting, for a maximum of two minutes after ignition.
That is a reason to tell service about heat that arrives but seems insufficient. It is a different observation from burners that never light.
During a later low to high transition, Bryant raises inducer speed, proves the high heat pressure switch and energizes the high heat gas valve solenoid. Bryant changes the indoor blower to high heat airflow five seconds after the control switches stages in adaptive operation.
Ask for the high heat proving and thermostat arrangement to be checked together. Leave switch settings, valve wiring and pressure measurements to the technician.
What each one takes
| What happened | Work involved |
|---|---|
| Failure followed a thermostat change | Verify control type, wiring and staging setup |
| Inducer runs without an igniter warmup | Trace pressure proving and purge completion |
| Ignition trial without sustained flame | Test gas delivery, ignition and flame sensing |
| Flame appears before room airflow | Compare blower response with the correct firing stage |
| Low heat during a higher heat request | Investigate high heat proving and staging |
Questions people ask
Which Bryant manual supplies the timings?
The 926TB installation and service instructions II926TB-04, revision D, June 2023. The sequence begins on printed page 70.
Does this furnace use a communicating wall control?
Bryant identifies the 926TB as noncommunicating. The manual describes single and two stage thermostat arrangements; do not apply a communicating furnace’s configuration procedure here.
Will adaptive operation drop from high to low heat during the same call?
Bryant says it will not switch from high to low while the R-to-W heat call remains closed with a single stage thermostat. The two stage thermostat sequence describes a different response when its high heat request ends.
Is the blower meant to continue after heating ends?
For the 926TB, Bryant lists selectable blower off periods of 90, 120, 150 or 180 seconds, with a 120 second factory setting. Bryant also gives the inducer a 15 second purge after the heat call ends.
Can I use the Carrier page for these setup details?
The Carrier furnace guide follows the 59MN7 modulating platform. Keep the 926TB’s staging and timing with the Bryant document used on this page.
The other furnace guides: furnace ignition types, furnace inducer motor, and furnace short cycling.