On Carrier's 40MAHB high wall heat pump, EL 01 is an indoor and outdoor unit communication error, PC 03 is low pressure protection and EL 0C is refrigerant leakage detection. The older 40MAQ shows the same communication error as E1. dF on the display is not a fault: Carrier's owner's manual shows it while the unit is defrosting.
Carrier mini split error codes change with the model: on the 40MAHB high wall heat pump, EL 01 is an indoor and outdoor unit communication error, while Carrier’s older 40MAQ shows the same fault as E1. Both service manuals say to check the codes on the indoor unit first.
Some of what the display shows is not a fault at all. Carrier’s 40MAHB owner’s manual says dF appears when defrosting, which Carrier’s service manual describes under HEATING mode. Everything below comes from Carrier’s manuals for those named models.
Before you start
What to carry: a torch, the remote, and your phone to film the indoor unit’s lights. Nothing needs opening.
Gas or electric? Electric. Carrier calls the 40MAHB a family of heat pumps, and its owner’s manual covers sizes 06 to 36. The 40MAQ manual covers sizes 09 to 30.
Renting? Send the code, the model and a short video of the lights to whoever arranges repairs.
Cleaning or a filter. Carrier’s 40MAHB owner’s manual says always turn off power to the system before any cleaning or maintenance: the outdoor disconnect switch near the outdoor unit, and the indoor unit too if it is on a separate switch. Switch it back on when you finish: for outdoor units with a basepan or crankcase heater, Carrier strongly recommends keeping power on the unit when it is below 32°F (0°C).
Sharp parts. Carrier warns that the coil fins are very sharp, to always wear safety protection when cleaning, and not to touch metal parts when removing the filter. It also says never to use water to clean the inside of the indoor unit.
What stays with a technician. Carrier lists cleaning the outdoor coil from inside, the electrical connections, the fan wheel and the drain pans as maintenance for qualified service personnel. When the diagnostic lights come on, Carrier’s answer is to call your service representative.
Where the code shows
Read the indoor display and count the lamp flashes
On the 40MAHB, Carrier’s indoor table pairs each code with a count of operation lamp flashes and the state of the timer lamp. EL 01 is 2 flashes with the timer lamp off. PC 03 is 7 flashes with the timer lamp flashing, but PC 00 (IPM malfunction) shows the same 7 flashes, so read the code on the display to tell them apart. The timer lamp flashes only for the PC codes.
The outdoor unit has a light too. On the 40MAHB it flashes slowly, once per second, in standby and quickly, twice per second, when the unit has an issue. Carrier lists it as the outdoor unit error display in the service manual, so leave it to the technician.
40MAHB codes
These come from Table 5 in Carrier’s 40MAHB service manual.
| Display | What Carrier’s table says |
|---|---|
| EH 00 / EH 0A | Indoor unit EEPROM parameter error |
| EL 01 | Indoor/outdoor unit communication error |
| EH 02 | Zero-crossing signal detection error |
| EH 03 | Indoor fan operating outside of the normal range |
| EC 51 | Outdoor unit EEPROM parameter error |
| EC 52, EC 53, EC 54, EC 56 | Outdoor temperature sensor T3, T4, TP or T2B open or short circuited |
| EH 60 / EH 61 | Indoor sensor T1 / T2 open or short circuited |
| EC 07 | Outdoor fan operating outside of the normal range |
| EH 0b | Indoor PCB/Display board communication error |
| EL 0C | Refrigerant leakage detection |
| PC 00 | IPM malfunction or IGBT OSCP |
| PC 01 | Over voltage or over low voltage protection |
| PC 02 | Compressor or IPM high temp/pressure protection |
| PC 03 | Low pressure protection |
| PC 04 | Inverter compressor drive error |
| PC 08 | Current overload protection |
| PC 40 | Comm. error between outdoor chip and compressor chip |
| EH b1 | Indoor board and Multi-function communication error |
| FH 0d | Ionizer malfunction |
| — | Indoor units mode conflict |
Rule out the displays that are not faults
Carrier’s 40MAHB owner’s manual lists displays that are features, not faults: dF when defrosting, FP when the 46°F heating mode is on (some units), and CL when Active Clean is on.
Two dashes, —, are the mode conflict in Carrier’s table. The owner’s manual explains them on a multi zone system: AUTO changeover can set an indoor unit to standby, shown as two dashes, until all the indoor units are in the same mode. Heating is the priority, and Carrier says simultaneous heating and cooling is not allowed.
Carrier also lists heating behaviour that is not a malfunction. The unit can change from HEAT to FAN mode to prevent frost forming, and go back once the temperature rises. White mist can come from both units when it restarts in HEAT mode after defrosting.
If it heats poorly, start with the filter and the outdoor unit
For heating that is not working properly, Carrier’s owner’s table gives four causes: the filter blocked with dust, the temperature set too low, a window or door open, and the outdoor unit obstructed. Its fix for the last one is to remove the obstruction.
Turn the unit off and disconnect its power before the filter comes out. Carrier’s maintenance table lists cleaning the air filter and cleaning the outdoor coil from outside among the jobs it does not mark for qualified personnel, and it says to clean the air filter more often in dusty zones.
Carrier also warns that running with dirty air filters may cause frost build up on the indoor coil, intermittent operation or blown fuses.
Power cycle for erratic running, call for diagnostic lights
For operation that is erratic, unpredictable or unresponsive, Carrier’s owner’s manual suggests disconnecting the power, reconnecting it, and pressing ON/OFF on the remote. Carrier says interference from cell phone towers and remote boosters may cause that kind of fault.
When the unit stops and the diagnostic lights come on, Carrier’s answer is to call your service representative. The same goes for a unit that does not work with the diagnostic lights on. A tripped breaker or blown fuse is the exception: Carrier says reset the breaker or replace the fuse with the specified one.
Carrier also notes a 3 minute protection feature: the unit cannot restart within three minutes of being turned off, so it may seem dead right after you switch it back on.
The older 40MAQ and 38MAQ
The 40MAQ service manual uses shorter codes for many of the same faults. Do not read a 40MAHB code from this table, or the other way round.
| 40MAQ display | What Carrier’s table says |
|---|---|
| E0 | Indoor unit EEPROM parameter error |
| E1 | Indoor / outdoor units communication error |
| E2 | Zero-crossing signal detection error |
| E3 | Indoor fan speed has been out of control |
| E4 / E5 | Room sensor T1 / coil sensor T2 open or short circuit |
| EC | Refrigerant leakage detection |
| F1 to F3 | An outdoor temperature sensor open or short circuit |
| F4 | Outdoor unit EEPROM parameter error |
| F5 | Outdoor fan speed has been out of control |
| P0 | IPM malfunction or IGBT over-strong current protection |
| P1 | Over voltage or over low voltage protection |
| P2 | High temperature protection of compressor top (only for 9k, 12k models) |
| P4 | Inverter compressor drive error |
Carrier’s 40MAQ manual says its refrigerant leak check, EC, only works in cooling mode on one to one systems. When suspected leakage happens three times in a row, the indoor unit shows EC and turns off.
What each one takes
| What you see | What the work involves |
|---|---|
| dF, FP or CL on a 40MAHB | Nothing; a defrost or a feature that is on |
| Two dashes on a multi zone | Setting the indoor units to the same mode |
| Poor heating, no code | A filter clean and a clear outdoor unit |
| EL 01 or E1 | A technician tracing the indoor to outdoor communication |
| EL 0C, EC or PC 03 | A technician; Carrier’s codes point at refrigerant leakage or low pressure |
Questions people ask
Is it EL 0C or EL OC?
Carrier’s 40MAHB table prints EL 0C, with a zero, and calls it refrigerant leakage detection. On the older 40MAQ the same check shows as EC.
Does EC on a 40MAHB mean a refrigerant leak?
Carrier’s 40MAHB service manual uses both. Its Table 5 lists the refrigerant leak code as EL 0C, with EC 51 an outdoor EEPROM error and EC 52, EC 53, EC 54 and EC 56 outdoor sensor faults. Its description of the leak check says the display shows EC when the outdoor unit detects a refrigerant leak, and that the check only works in COOLING mode. On the 40MAQ, EC is refrigerant leakage detection.
Why does my mini split show dF and blow no heat for a while?
Carrier’s 40MAHB owner’s manual shows dF when defrosting. Its service manual says that during defrost the compressor keeps running, the indoor and outdoor motors stop and the defrost lamp lights, so the indoor unit stops blowing until it ends.
Can I clear a code by switching it off?
Carrier’s owner’s manual suggests switching the power off and back on for erratic operation. For diagnostic lights that come on, it says to call your service representative.
My Carrier ductless code is not on this page.
These are the 40MAHB and 40MAQ tables. Other Carrier ductless models have their own manuals; read the model on the indoor unit’s label and use that one.
The other mini split guides: mini split error codes, mini split not heating, mini split freezing up and how to reset a heat pump.
Sources: Carrier 40MAHB high wall ductless heat pump service manual (SG-40MAHB-02) and owner's manual (OM-40MAHB-01, 11/20); Carrier 40MAQ / 38MAQ high wall ductless split system service manual (38-40MAQ-01SM)