Carrier Mini Split Error Codes: EL 01, PC 03, E1 and dF

Carrier Mini Split Error Codes: EL 01, PC 03, E1 and dF
Short answer

On Carrier's 40MAHB high wall heat pump, EL 01 is an indoor and outdoor unit communication error, PC 03 is low pressure protection and EL 0C is refrigerant leakage detection. The older 40MAQ shows the same communication error as E1. dF on the display is not a fault: Carrier's owner's manual shows it while the unit is defrosting.

Carrier mini split error codes change with the model: on the 40MAHB high wall heat pump, EL 01 is an indoor and outdoor unit communication error, while Carrier’s older 40MAQ shows the same fault as E1. Both service manuals say to check the codes on the indoor unit first.

Some of what the display shows is not a fault at all. Carrier’s 40MAHB owner’s manual says dF appears when defrosting, which Carrier’s service manual describes under HEATING mode. Everything below comes from Carrier’s manuals for those named models.

Before you start

What to carry: a torch, the remote, and your phone to film the indoor unit’s lights. Nothing needs opening.

Gas or electric? Electric. Carrier calls the 40MAHB a family of heat pumps, and its owner’s manual covers sizes 06 to 36. The 40MAQ manual covers sizes 09 to 30.

Renting? Send the code, the model and a short video of the lights to whoever arranges repairs.

Power off before you touch anything.
Cleaning or a filter. Carrier’s 40MAHB owner’s manual says always turn off power to the system before any cleaning or maintenance: the outdoor disconnect switch near the outdoor unit, and the indoor unit too if it is on a separate switch. Switch it back on when you finish: for outdoor units with a basepan or crankcase heater, Carrier strongly recommends keeping power on the unit when it is below 32°F (0°C).

Sharp parts. Carrier warns that the coil fins are very sharp, to always wear safety protection when cleaning, and not to touch metal parts when removing the filter. It also says never to use water to clean the inside of the indoor unit.

What stays with a technician. Carrier lists cleaning the outdoor coil from inside, the electrical connections, the fan wheel and the drain pans as maintenance for qualified service personnel. When the diagnostic lights come on, Carrier’s answer is to call your service representative.

Where the code shows

Check 1Free, nothing to open

Read the indoor display and count the lamp flashes

On the 40MAHB, Carrier’s indoor table pairs each code with a count of operation lamp flashes and the state of the timer lamp. EL 01 is 2 flashes with the timer lamp off. PC 03 is 7 flashes with the timer lamp flashing, but PC 00 (IPM malfunction) shows the same 7 flashes, so read the code on the display to tell them apart. The timer lamp flashes only for the PC codes.

The outdoor unit has a light too. On the 40MAHB it flashes slowly, once per second, in standby and quickly, twice per second, when the unit has an issue. Carrier lists it as the outdoor unit error display in the service manual, so leave it to the technician.

WHERE A 40MAHB SHOWS A CODE

EL 01

A B C

A Indoor display the code itself, for example EL 01

B Operation and timer lamps count the operation lamp flashes, and note the timer lamp: off, on or flashing

C Outdoor unit light slow flash: standby; fast flash: an issue for the technician

Where Carrier's 40MAHB shows a code: the indoor display, the operation and timer lamps, and a light on the outdoor unit. Carrier's manuals say to check the indoor unit first.

40MAHB codes

These come from Table 5 in Carrier’s 40MAHB service manual.

Display What Carrier’s table says
EH 00 / EH 0A Indoor unit EEPROM parameter error
EL 01 Indoor/outdoor unit communication error
EH 02 Zero-crossing signal detection error
EH 03 Indoor fan operating outside of the normal range
EC 51 Outdoor unit EEPROM parameter error
EC 52, EC 53, EC 54, EC 56 Outdoor temperature sensor T3, T4, TP or T2B open or short circuited
EH 60 / EH 61 Indoor sensor T1 / T2 open or short circuited
EC 07 Outdoor fan operating outside of the normal range
EH 0b Indoor PCB/Display board communication error
EL 0C Refrigerant leakage detection
PC 00 IPM malfunction or IGBT OSCP
PC 01 Over voltage or over low voltage protection
PC 02 Compressor or IPM high temp/pressure protection
PC 03 Low pressure protection
PC 04 Inverter compressor drive error
PC 08 Current overload protection
PC 40 Comm. error between outdoor chip and compressor chip
EH b1 Indoor board and Multi-function communication error
FH 0d Ionizer malfunction
— Indoor units mode conflict
Check 2Free; no repair for a normal display

Rule out the displays that are not faults

Carrier’s 40MAHB owner’s manual lists displays that are features, not faults: dF when defrosting, FP when the 46°F heating mode is on (some units), and CL when Active Clean is on.

Two dashes, —, are the mode conflict in Carrier’s table. The owner’s manual explains them on a multi zone system: AUTO changeover can set an indoor unit to standby, shown as two dashes, until all the indoor units are in the same mode. Heating is the priority, and Carrier says simultaneous heating and cooling is not allowed.

Carrier also lists heating behaviour that is not a malfunction. The unit can change from HEAT to FAN mode to prevent frost forming, and go back once the temperature rises. White mist can come from both units when it restarts in HEAT mode after defrosting.

Check 3Free; a filter clean and clearing an obstruction

If it heats poorly, start with the filter and the outdoor unit

For heating that is not working properly, Carrier’s owner’s table gives four causes: the filter blocked with dust, the temperature set too low, a window or door open, and the outdoor unit obstructed. Its fix for the last one is to remove the obstruction.

Turn the unit off and disconnect its power before the filter comes out. Carrier’s maintenance table lists cleaning the air filter and cleaning the outdoor coil from outside among the jobs it does not mark for qualified personnel, and it says to clean the air filter more often in dusty zones.

Carrier also warns that running with dirty air filters may cause frost build up on the indoor coil, intermittent operation or blown fuses.

Check 4Free; a service call when the diagnostic lights are on

Power cycle for erratic running, call for diagnostic lights

For operation that is erratic, unpredictable or unresponsive, Carrier’s owner’s manual suggests disconnecting the power, reconnecting it, and pressing ON/OFF on the remote. Carrier says interference from cell phone towers and remote boosters may cause that kind of fault.

When the unit stops and the diagnostic lights come on, Carrier’s answer is to call your service representative. The same goes for a unit that does not work with the diagnostic lights on. A tripped breaker or blown fuse is the exception: Carrier says reset the breaker or replace the fuse with the specified one.

Carrier also notes a 3 minute protection feature: the unit cannot restart within three minutes of being turned off, so it may seem dead right after you switch it back on.

The older 40MAQ and 38MAQ

The 40MAQ service manual uses shorter codes for many of the same faults. Do not read a 40MAHB code from this table, or the other way round.

SAME FAULT, TWO NAMES 40MAHB 40MAQ What Carrier calls it EL 01 E1 Indoor and outdoor unit communication error EL 0C EC Refrigerant leakage detection EC 51 F4 Outdoor unit EEPROM parameter error PC 01 P1 Over voltage or over low voltage protection PC 04 P4 Inverter compressor drive error
The same fault under two names, from Carrier's 40MAHB and 40MAQ service manuals.
40MAQ display What Carrier’s table says
E0 Indoor unit EEPROM parameter error
E1 Indoor / outdoor units communication error
E2 Zero-crossing signal detection error
E3 Indoor fan speed has been out of control
E4 / E5 Room sensor T1 / coil sensor T2 open or short circuit
EC Refrigerant leakage detection
F1 to F3 An outdoor temperature sensor open or short circuit
F4 Outdoor unit EEPROM parameter error
F5 Outdoor fan speed has been out of control
P0 IPM malfunction or IGBT over-strong current protection
P1 Over voltage or over low voltage protection
P2 High temperature protection of compressor top (only for 9k, 12k models)
P4 Inverter compressor drive error

Carrier’s 40MAQ manual says its refrigerant leak check, EC, only works in cooling mode on one to one systems. When suspected leakage happens three times in a row, the indoor unit shows EC and turns off.

What each one takes

What you see What the work involves
dF, FP or CL on a 40MAHB Nothing; a defrost or a feature that is on
Two dashes on a multi zone Setting the indoor units to the same mode
Poor heating, no code A filter clean and a clear outdoor unit
EL 01 or E1 A technician tracing the indoor to outdoor communication
EL 0C, EC or PC 03 A technician; Carrier’s codes point at refrigerant leakage or low pressure

Questions people ask

Is it EL 0C or EL OC?

Carrier’s 40MAHB table prints EL 0C, with a zero, and calls it refrigerant leakage detection. On the older 40MAQ the same check shows as EC.

Does EC on a 40MAHB mean a refrigerant leak?

Carrier’s 40MAHB service manual uses both. Its Table 5 lists the refrigerant leak code as EL 0C, with EC 51 an outdoor EEPROM error and EC 52, EC 53, EC 54 and EC 56 outdoor sensor faults. Its description of the leak check says the display shows EC when the outdoor unit detects a refrigerant leak, and that the check only works in COOLING mode. On the 40MAQ, EC is refrigerant leakage detection.

Why does my mini split show dF and blow no heat for a while?

Carrier’s 40MAHB owner’s manual shows dF when defrosting. Its service manual says that during defrost the compressor keeps running, the indoor and outdoor motors stop and the defrost lamp lights, so the indoor unit stops blowing until it ends.

Can I clear a code by switching it off?

Carrier’s owner’s manual suggests switching the power off and back on for erratic operation. For diagnostic lights that come on, it says to call your service representative.

My Carrier ductless code is not on this page.

These are the 40MAHB and 40MAQ tables. Other Carrier ductless models have their own manuals; read the model on the indoor unit’s label and use that one.

The other mini split guides: mini split error codes, mini split not heating, mini split freezing up and how to reset a heat pump.

Sources: Carrier 40MAHB high wall ductless heat pump service manual (SG-40MAHB-02) and owner's manual (OM-40MAHB-01, 11/20); Carrier 40MAQ / 38MAQ high wall ductless split system service manual (38-40MAQ-01SM)