On the Ducane 96G2UHV chart in manual 507961-02, three red flashes mean an open pressure switch with the inducer running. Four includes the primary limit, secondary limit or rollout switch. Seven is an ignition lockout. Green shows high heat status; amber shows airflow on models with a variable speed motor.
Ducane furnace codes can look confusing when more than one light is flashing. On the 96G2UHV, Allied Air’s installation manual assigns faults to a red LED and high heat status to a green LED. On models with a variable speed motor, an amber LED shows airflow. Counting the wrong light gives you the wrong answer.
This guide uses installation manual 507961-02, issue 2302. Its four flash entry includes rollout as well as the temperature limits. Keep that revision with the chart; a similar looking list from another furnace is not enough.
Before you start
What to carry: a torch, your phone and the furnace paperwork. Record the light through an existing viewing opening if you can see it safely.
Gas or electric? The 96G2UHV is a gas furnace. These are not the codes for an electric air handler or a Ducane heat pump.
Match the whole model. Look for 96G2UHV in the paperwork and compare the supplied diagnostic chart with the one below. Do not remove a running furnace’s door to identify the board. Ask the technician to confirm a replacement control if one has been fitted.
Renting? Report the light pattern and whether the home still has heat to your landlord or maintenance contact.
For overheating or a gas supply that fails to shut off, Allied Air says to shut off the gas before the electrical shutdown. If you cannot safely identify the gas shutoff, get urgent help rather than opening the cabinet.
If you smell gas, stop and leave the building. Allied Air instructs you to call the gas supplier from a neighbor’s phone and follow their directions. Do not attempt to light the burners by hand.
Allied Air says not to use this furnace if any part has been under water. Call a qualified technician immediately to inspect it and replace wet gas controls, control system parts and electrical parts, or the furnace if necessary.
For maintenance, Allied Air requires electrical power off at the disconnect. It also warns that the blower access panel must be secure during operation because combustion gases can enter the living space.
Start with the light’s colour
Record the red pattern separately
Count the repeated red flash group and include its colour in your description. If another lamp is blinking too, record it separately. Allied Air’s red fault chart is table 10, while the green high heat chart is table 11.
The furnace blinking light guide helps distinguish a repeating group from a continuous signal. Keep the cabinet closed while observing it.
The 96G2UHV red flash chart
These are Allied Air’s meanings in manual 507961-02, issue 2302. The word “open” describes a circuit state; it does not identify a failed switch on its own.
| Red light | Meaning in table 10 |
|---|---|
| Off | No power to the control, or a control hardware fault. |
| Steady on | Normal operation. |
| 1 flash | Flame present with the gas valve off. |
| 2 flashes | Pressure switch closed while the inducer is off. |
| 3 flashes | Pressure switch open while the inducer is energized. |
| 4 flashes | Primary limit, secondary limit or rollout switch open. |
| 5 flashes | Not used in this chart. |
| 6 flashes | Pressure switch cycle lockout. |
| 7 flashes | Lockout because ignition did not occur. |
| 8 flashes | Lockout after too many flame dropouts. |
| 9 flashes | Incorrect polarity and phasing of the electrical supply. |
For three flashes, look outside before discussing parts
Allied Air identifies three flashes as the pressure switch remaining open with the inducer energized. Its maintenance section calls for checking intake and exhaust pipes for blockage, especially following snow, ice or frozen fog.
From ground level, look for snow or ice obstructing the plastic pipe openings. Report a blockage you cannot safely reach. Do not detach vent pipes, reach into the furnace or bridge the pressure switch.
The pressure switch guide explains the distinction between a switch reporting a problem and a switch that needs replacement. Have the repairer investigate the full vent and inducer system.
For four flashes, do not assume it is only the filter
Allied Air groups three different safety switches under this code. A dirty filter check cannot tell you which one opened. Report four flashes as a limit or rollout circuit fault.
For ordinary filter maintenance, once the furnace is safely shut down, Allied Air says the filters are external to this unit and should be inspected monthly. Clean or replace yours as needed, using its specified type and size. The manual requires a filter in place whenever the furnace operates.
Separate no ignition from a flame that drops out
Allied Air calls seven flashes a no ignition lockout and eight a lockout after excessive flame dropouts. Tell the service company whether you observed any flame through the existing window before the stop.
One flash is a different report: Allied Air lists flame present with the gas valve off. Treat that as urgent service, following the gas shutdown warning above if gas is not shutting off. For nine flashes, have a qualified technician check the electrical supply.
Green high heat and amber airflow indications
Allied Air’s separate green LED table applies to this 96G2UHV control:
| Green light | Meaning in table 11 |
|---|---|
| Off | No demand for high heat. |
| On | High heat demand, operating normally. |
| Flashing | High heat demand, but the high pressure switch is not closed. |
For the amber LED on this model’s variable speed blower control, Allied Air assigns 100 cubic feet per minute to each flash. Its example is ten flashes for 1,000 CFM. That is an airflow indication, not red fault number ten, and it is not an instruction to change blower settings.
Keep the fault history for the repairer
Allied Air says this control stores the last five faults, newest first. Its board button can display that history, while holding the button longer than five seconds clears it. Let the technician retrieve it rather than opening a powered cabinet to press the button.
If the display changes before service arrives, keep your original recording. Describe any exterior obstruction or filter issue you found and whether heat returned. That is more useful than asking for a new board based on a light alone.
What each one takes
| Finding | Work involved |
|---|---|
| Model and lamp identification | Paperwork and a recording through the viewing opening. |
| External filter needs attention | The specified filter and a safe shutdown for maintenance. |
| Pressure circuit code | Exterior observation followed by vent, inducer and circuit diagnosis. |
| Limit, rollout or unexpected flame report | Safety circuit or gas control investigation before further operation. |
| Electrical polarity code | Qualified electrical testing and correction. |
Questions people ask
Why does another Ducane list give different meanings?
Compare the furnace, control and document revision. This page uses 96G2UHV manual 507961-02, issue 2302. Do not apply it automatically to 95G2UH, 80G1UH or a replacement board.
Does a steady red light mean the board has failed?
In this Allied Air chart, steady red means normal operation.
What if I counted five red flashes?
Five is unused in this revision’s table. Check the recording and have the model and installed control confirmed. Do not borrow a five flash meaning from another furnace.
Can the green light be off while the furnace still heats?
Allied Air defines green off as no demand for high heat. It does not label that state a whole furnace failure.
Where is the Ducane furnace code PDF?
The manufacturer’s 96G2UHV installation manual has both light tables on page 45. Confirm the document number on its cover.
The other furnace guides: reading a blinking light, pressure switch faults and rollout protection.
Sources: Allied Air Enterprises 96G2UHV installation instructions 507961-02, issue 2302, page 45 tables 10 and 11; pages 13, 52 and 55. https://s7d2.scene7.com/is/content/AlliedAirEnterprises/1%20-%20Document%20Updates/VALUE_GASFURNACES_96G2V-UPFLOW_INSTALLATIONMANUAL.pdf