Friedrich Mini Split Error Codes: 22, 23, 36 and 56

Friedrich Mini Split Error Codes: 22, 23, 36 and 56
Short answer

Friedrich's Floating Air Pro and Select single zone mini splits use number codes, read on a number display by pressing SLEEP on the remote 10 times in ten seconds. Friedrich lists 36 as an indoor to outdoor communication failure and 19 as a compressor drive failure. 22 is the compressor pre heating, which Friedrich calls normal in cold weather. 23 and 56 mean a leak of a flammable refrigerant.

Friedrich mini split error codes on the Floating Air Pro and Select single zone systems are numbers, plus EA, and Friedrich’s service manuals say you can call them up by pressing the SLEEP button on the remote 10 times within ten seconds. On a display with a number readout, the code then shows, such as 36, a communication failure between the indoor and outdoor units.

One code is not a fault. Friedrich lists 22 as the compressor pre heating process and calls it normal in cold weather. Everything below comes from Friedrich’s two 2025 single zone service manuals, the Pro for R-454B and the Select for R-32.

Before you start

What to carry: a torch, the remote, and a pen. Nothing needs opening.

Gas or electric? Electric. These are Friedrich’s ductless single zone systems. The Pro manual covers the FAHFW wall mounted indoor units with FPHSR outdoor units, and the Select manual covers its own FAHFW and FAHSW wall units with FSHSR outdoor units.

Renting? Send the code and the model on the indoor unit’s label to whoever arranges repairs.

A leak code means a flammable refrigerant is escaping.
Codes 23 and 56. Friedrich lists both as a leak in the product. Its manuals mark the appliance as using a flammable refrigerant: if it leaks and meets an external ignition source, there is a risk of fire. Friedrich adds that refrigerants may not have an odor, so do not rely on your nose.

Keep flames away from a leak. Friedrich warns not to pierce or burn the refrigerant system, and says only certified refrigeration technicians should service this equipment. Its R-454B warning also says the appliance shall be stored in a room without continuously operating ignition sources, such as open flames, an operating gas appliance or an operating electric heater, so keep those out of that room while 23 or 56 shows.

No home made defrosting. Friedrich says not to use any means to speed up defrosting or to clean, other than those it recommends. Deep cleaning of the indoor unit is for a professional.

Call up the code

Check 1Free, nothing to open

Press SLEEP 10 times in ten seconds

Friedrich’s service manuals say that when the compressor stops with a fault, pressing the sleep button on the remote 10 times in ten seconds makes the display show the error code. If two faults happened at the same time, press it 10 times again to see the other one.

Friedrich adds that this only works on a display with a number readout. Otherwise, only the display board’s light shows the fault.

The outdoor unit has its own three lights, LED1, LED2 and LED3, that show faults as patterns of on, off and blinking. They sit on the outdoor control board, which is technician work.

CALL UP A FRIEDRICH CODE

A Press SLEEP SLEEP 10 times within ten seconds

B The code shows 36 on a number display; 36: communication failure between the two units

C Two faults? press SLEEP 10 more times to see the second code

How Friedrich's service manuals say to call up a Floating Air code: press SLEEP on the remote 10 times within ten seconds, and press 10 more times if two faults happened together.

The indoor codes

These are selected rows from the indoor unit diagnostic code table in Friedrich’s Pro manual. The Select manual lists the same meanings for 19, 22, 23, 36 and 56.

Code What Friedrich’s table says
EA Communication between the display board and control board is interrupted
0 Normal
1 / 2 Outdoor coil sensor / compressor exhaust temperature sensor fault
5 IPM module protection
6 AC voltage higher or lower protection
7 Communication failure between the indoor and outdoor unit
8 / 9 Current overload protection / maximum current protection
11 Outdoor EEPROM in trouble
12 Outdoor ambient temperature too low or too high protection
13 Compressor exhaust temperature too high protection
15 Compressor shell temperature too high protection
16 Anti-freeze protection in cooling, or overload protection in heating
18 / 19 DC compressor start failure / compressor drive failure
20 Outdoor fan motor locked rotor protection
22 Compressor pre heating process; normal in cold weather
23 There is a leak in the product
27 Protection against too high system pressure
33 / 34 Indoor room / indoor coil temperature sensor fault
36 Communication failure between the indoor and outdoor unit
38 / 39 Indoor EEPROM failure / indoor fan motor runs abnormally
56 There is a leak in the product (leak detection, both manuals)
Check 2Free; no repair

With 22 in cold weather, wait

Friedrich’s tables call 22 the compressor pre heating process and say it is normal mode in cold weather. The outdoor light table says the same about its own pre heating pattern.

Code 12 is different: Friedrich calls it protection when the outdoor ambient temperature is too low or too high, and its only listed cause is the temperature itself. Note how cold it is when 12 appears and pass that on if it keeps happening.

TWO COLD WEATHER CODES

A 22 Compressor pre heating Friedrich calls it normal mode in cold weather. Nothing to fix: let it finish.

B 12 Too cold or too hot outside Protection; the only cause listed is the temperature. Note it if 12 keeps coming.

Two of Friedrich's cold weather codes: 22 is the compressor pre heating, which Friedrich calls normal in cold weather, and 12 is protection when it is too cold or too hot outside.

Check 3Free to look; a service call for the fix

With 8 or 20, look at the outdoor unit from a distance

For 8, current overload protection, Friedrich’s causes include a dirty condenser and evaporator and an abnormal air inlet and outlet. For 20, outdoor fan motor locked rotor, they include something blocking the outdoor fan.

Friedrich warns to keep all air circulation and ventilation openings free from obstruction. From outside the unit, look for anything blocking the coil or the fan, and tell the technician what you saw. If you clear anything away from it, Friedrich says to disconnect all power to the unit before starting maintenance. The fan, the motor and the boards are theirs.

Check 4A technician; the leak must be repaired

With 56, the outdoor unit stops and the indoor fan runs at its highest speed

Friedrich’s Pro and Select manuals say that when a refrigerant leak is detected, code 56 shows, the indoor fan is forced to its highest speed and the outdoor unit stops. Other controls stop responding. Friedrich warns not to remove, disable or bypass the unit’s safety devices.

Even after the repair, Friedrich says the unit keeps alarming until a special remote control sequence clears it, and afterwards the indoor fan runs at maximum speed for 5 minutes before the set mode returns. That sequence belongs after the leak is fixed, so leave it to the technician.

What each one takes

What you see What the work involves
22 in cold weather Nothing; Friedrich calls it normal
12 A note of the outdoor temperature for the technician
8 or 20 A look for anything blocking the outdoor unit, then the technician’s checks
7 or 36 A technician tracing the communication wiring and boards
23 or 56 A certified refrigeration technician for the leak

Questions people ask

How do I see the error code on my Friedrich mini split?

Friedrich’s Floating Air Pro and Select service manuals say to press the sleep button on the remote 10 times within ten seconds. On a display with a number readout, the code appears; if two faults happened together, press it 10 more times for the second.

What does 36 mean on a Friedrich mini split?

Friedrich’s Floating Air Pro and Select manuals list 36 as a communication failure between the indoor unit and the outdoor unit. Code 7 has the same description, and the causes include the communication cable and its connections and the indoor control, PFC, power and outdoor control boards.

Is 22 a fault?

No. Friedrich’s Floating Air Pro and Select manuals call 22 the compressor pre heating process and says it is normal mode in cold weather.

Can I clear code 56 myself?

Friedrich gives a remote control sequence to clear 56, but only after the fault repair is completed. A leak of a flammable refrigerant needs a certified refrigeration technician first.

Do these codes apply to my older Friedrich?

They come from the 2025 Floating Air Pro and Select single zone service manuals. Other Friedrich models have their own manuals; check the model on your indoor unit’s label.

The other mini split guides: mini split error codes, mini split not heating, mini split freezing up and mini split won’t turn on.

Sources: Friedrich Floating Air Pro single zone service manual 96112000_00 (R-454B, FAHFW indoor units) and Floating Air Select single zone service manual 96122000_00 (R-32)