On the Luxaire TM9V*C control in manual 5750149-UIM-D-1219, four red flashes mean the main limit has opened. Four amber flashes instead report a Y thermostat signal without G. Seven red flashes mean ignition failed after three trials. Keep the model, colour and count together.
Luxaire furnace error codes need a colour as well as a number: on the TM9V*C, four red flashes and four amber flashes point to different circuits. Johnson Controls’ installation manual calls four red an open main limit, while four amber reports a missing thermostat signal.
The chart here follows the Johnson Controls manual for Luxaire’s TM9V, installation manual 5750149-UIM-D-1219 for TM9V*C models. Luxaire’s own product literature identifies this two stage furnace family. Our York code guide follows the TM9M, so its amber entries should not be substituted for these.
Before you start
What to carry: a torch, your furnace model information and something to record the light pattern. A video can preserve the colour, flashes and pause together.
Gas or electric? These are gas furnace diagnostics for the named TM9V*C series. They are not a fault chart for an electric air handler or a Luxaire outdoor heat pump.
Keep the cabinet closed. The installation manual prohibits operation with the blower door removed. Observe any visible indicator from outside; if access requires a panel to come off, leave that to the service technician.
Renting? Give the property manager the model and recorded pattern. Tell them whether the furnace stopped heating or is still warming the house.
Johnson Controls’ user manual says to leave immediately if you smell gas. Do not use switches, phones or ignition devices inside. Immediately call the gas supplier from outside and follow its instructions. If the supplier cannot be reached, call the fire department.
If gas fails to shut off or the furnace overheats, that manual requires gas off before electrical power. Approach the shutoff only when it is safe to do so.
The TM9V*C installation manual forbids bypassing a safety control or adjusting a pressure switch to make the furnace operate. Gas valve faults, rollout concerns and electrical tests need qualified service.
Read the colour and the pause
Distinguish normal blinking from a fault group
The TM9V*C manual defines slow blinking as two seconds on and two seconds off. Slow green is normal with no thermostat request; slow amber is normal with a heat request.
Its numbered codes use flashes of one third of a second on and one third off, followed by a two second pause between groups. Count the flashes inside a group rather than continuing across the pause.
The manual gives continuous amber its own meaning: a weak flame sensing current. Continuous flashing has no longer pause separating numbered groups. A steady light of any colour is also different; the manual identifies it as a control failure.
The TM9V*C fault chart
These definitions come from the installation manual’s diagnostics section. The service column shows what a technician checks before choosing a repair.
| Indication | Meaning on this control | Service area |
|---|---|---|
| 1 red | Flame sensed without a heat request | Gas valve closing and leakage checks |
| 2 red | Pressure switch closed when it should be open | Switch and wiring |
| 3 red | Pressure switch open when it should be closed | Inducer, vent, hose, wiring and switch |
| 4 red | Main limit contacts open | Airflow, firing rate and limit wiring |
| 5 red | Limit circuit open longer than fifteen minutes; the manual says this usually indicates rollout | Combustion air, inducer, heat exchanger and burners |
| 6 red | Pressure switch opened four times in one heat request | Inducer, vent and pressure switch |
| 7 red | No flame established in three ignition trials | Gas supply, ignition and flame detection |
| 8 red | Flame lost five times during the heating cycle | Gas pressure, flame sensor and gas valve |
| 9 red | Supply polarity, grounding or transformer wiring problem | Electrical checks |
| 10 red | Gas valve powered without a heat request | Valve and wiring |
| 11 red | Limit circuit open longer than five minutes but less than fifteen | Blower and limit investigation |
| 12 red | Model identification plug loose or missing | Correct plug and connection |
| 13 red | High fire pressure switch open when it should be closed | Vent restriction, wiring and vent pressure |
| 4 amber | Thermostat Y signal received without G | Thermostat wiring |
Four flashes: follow the right branch
Use red for the limit branch and amber for wiring
For four amber flashes, the TM9V*C manual says the furnace can heat and cool normally while reporting the wiring problem. Its check is the thermostat’s G connection. Leave terminal changes to the technician; replacing a filter does not repair that missing signal.
For four red flashes, Johnson Controls lists a dirty filter, unsuitable duct sizing, the blower speed, firing rate, loose limit wiring and a faulty blower motor. That is a broader investigation than replacing the limit switch.
For routine filter care, the user manual says to turn the thermostat off, let the blower stop automatically, then shut off gas and electrical supplies. Work only after the metal surfaces have cooled to room temperature, with the area well ventilated.
Replace a disposable filter with the same size, or use the manual’s cleaning instructions for a washable filter. The user manual requires a washed filter to dry completely before fitting. Secure the access panels before restoring supplies and the thermostat setting. If you cannot carry out that shutdown safely, leave the filter with the service visit.
The limit switch guide explains the protection the circuit provides. If the code remains or changes to 11 or 5 red, report that change rather than repeatedly restarting the furnace.
Seven red flashes and the pressure faults
For seven red, report what happened during ignition
Johnson Controls defines seven red flashes as failure to establish flame in three ignition trials. Its possible causes include low or absent gas pressure, the gas valve, the flame sensor, the igniter, loose wiring and a burner problem.
Describe whether the attempt stayed dark or whether flame appeared and disappeared. The manual distinguishes seven red from eight red, which follows five flame losses in a heating cycle. Both entries specify an hour of lockout before another attempt.
Do not use the retry as a way to check for a gas leak. The gas smell instructions above apply before any further troubleshooting.
Keep three, six and thirteen red distinct
In the TM9V*C manual, three red means the pressure switch has not closed when required. Six red means it opened four times during the same heat request. Thirteen red identifies the high fire pressure switch specifically.
Those distinctions tell the technician whether to investigate startup, a repeated interruption or the high fire circuit. The manual’s thirteen-flash entry names a partly blocked vent, a loose or disconnected wire, and vent pressure.
The pressure switch guide gives background on the air and vent path.
What each one takes
| Next step | What it involves |
|---|---|
| Identify the colour and flash group | An observation and the full model number |
| Maintain an accessible filter | Correct shutdown, a matching filter or permitted cleaning, then secure reassembly |
| Four amber | Thermostat signal and wiring checks |
| Continuing four red, eleven red or five red | Blower, limit and combustion investigation appropriate to the indication |
| Ignition, pressure or gas valve codes | Measurements by service personnel; parts depend on the findings |
Questions people ask
Where is the Luxaire TM9V code PDF?
Use Johnson Controls installation manual 5750149-UIM-D-1219, pages 37 and 38, for the TM9V*C series.
Does five red prove that a rollout switch tripped?
The manual defines the indication by a limit circuit that has stayed open longer than fifteen minutes and says this usually indicates a manual reset rollout switch. The service technician still needs to establish what opened and why.
Can a power cut erase the fault history?
Johnson Controls says the TM9V*C stores up to five codes and retains them through lost power. Its Last Error retrieval feature is reserved for a qualified service technician.
Does a dark light prove the board has failed?
No. The installation manual starts with power to the board and its fuse. It considers replacement only if the board is powered correctly and the fuse is intact.
Will every lockout restart by itself?
No. The TM9V*C manual distinguishes an automatic one hour soft lockout from hard lockout, which does not restart automatically. Its five-red and eleven-red instructions require the cause to be corrected before the control is reset.
The other furnace guides: reading furnace lights, rollout switch trips and a furnace that will not ignite.
Sources: Johnson Controls TM9V*C installation manual 5750149-UIM-D-1219, pages 2, 3 and 37 to 38; Residential Multi-Position Gas Furnace user's manual 1010352-UUM-N-0121, pages 1, 2, 4 and 5; Luxaire official TM9V product page and technical guide 5425618-LTG-C-1018. Installation PDF: https://pdf.lowes.com/installationguides/883982816193_install.pdf.