On Payne's PG92ESA, short flashes give the first digit and long flashes give the second. Three short and three long is 33, an open limit or rollout circuit. One short and three long is 13, its lockout. One short and two long is 12, a blower startup sequence.
Payne furnace error codes on the PG92ESA use two groups of flashes, so the pause between them matters. Payne’s service label reads three short flashes and three long flashes as 33; one short and three long becomes 13.
Below is the chart for that named furnace, including the one short, two long pattern that can appear after power returns. Keep the full model number handy: this is a single stage gas furnace, and a different Payne control may need a different chart.
Before you start
What to carry: a torch and a phone for a video of the light. Payne places the status indicator in the blower door, where you can watch it without opening the control compartment.
Gas or electric? The PG92ESA manual covers a condensing gas furnace. It is not the code list for an electric air handler or heat pump.
Renting? Send the recording and model number to your maintenance contact, and ask them to arrange repair.
The Carrier code guide mentions Payne, but the definitions here come from the PG92ESA’s own installation manual and service label.
If you smell gas, do not try to light an appliance. Leave the building without operating electrical switches or using a phone inside. Lochinvar’s gas safety instructions say to call the gas supplier immediately from a nearby phone, follow its instructions, and call the fire department if it cannot be reached.
Payne allows basic owner maintenance such as filter care; other repairs belong to trained personnel. Its manual says to correct the cause of a rollout trip before resetting the switch. Do not bridge it or hold the blower door switch closed.
Before maintenance, Payne requires the gas and electrical supplies off and a lockout tag, following the furnace operating label. Its manual warns there may be more than one electrical disconnect; all must be off. Reinstall access doors when finished.
Read the short group first
Match the pattern to the PG92ESA label
Payne describes an amber status light. Watch a complete repeating pattern and compare both groups, rather than adding every flash together.
On Payne’s service label, a continuously lit light means the control has 24 volt power. Rapid flashing means reversed incoming voltage polarity; an unlit control leads to power supply checks.
A dark light does not identify a failed board. The manual’s troubleshooting chart also checks the door switch, circuit breaker and incoming supply. You can report the visible condition; electrical measurements need the technician.
Three short, three long: code 33
Check the filter without treating 33 as a filter diagnosis
Payne defines 33 as an open limit or flame rollout circuit. Its checks include a dirty filter, restricted ducts, a loose blower wheel, faulty connections and incorrect gas input.
Filter care is the owner task here. With the shutdown precautions above, inspect an accessible filter and clean or replace it according to its instructions. Payne says the PG92ESA filter is outside the furnace casing, so there is no need to hunt for one behind the burner door.
Payne also says a filter’s airflow arrow must point toward the blower. If the filter is inaccessible or you cannot identify its type, leave that part of the inspection for service.
A clean filter leaves the other causes on Payne’s list unresolved. The furnace limit switch guide explains the overheating side; a rollout trip needs its own safety investigation.
One short, three long: code 13
Recognize the lockout that follows an open safety circuit
Payne’s PG92ESA service label gives code 13 when a limit or rollout switch remains open longer than three minutes. The control automatically resets after three hours.
That explains why a recording may show 33 first and 13 later. Give the service company that sequence, including whether the furnace resumed heating by itself. The timer describes the control’s retry, not a repair you have completed.
There is no reason to buy a switch from this number alone. Payne’s chart sends the technician back to the limit circuit causes, rather than naming one replacement part.
One short, two long: code 12
Separate the startup blower run from a heating fault
Payne calls 12 normal blower operation after power up. Its chart specifies a 90 second run if power returns during a heat call, or if the heat call ends during the blower on delay.
If this followed a power interruption, let that sequence finish and observe what the light shows next. A later 13 or 14 gives different information from the initial 12. Report that later code if the house still has no heat.
The remaining PG92ESA service codes
These are Payne’s definitions for this model. The pressure switch names are especially worth preserving when you book service.
| Code | PG92ESA meaning | Where the manual points |
|---|---|---|
| 14 | Ignition lockout after four unsuccessful attempts to ignite and prove flame | Code 34 checks; automatic reset after three hours |
| 21 | Gas heating lockout | Gas valve relay and wiring checks by a technician |
| 22 | Flame proved while the gas valve is deenergized | Leaking or stuck open valve; urgent qualified service, no further attempts to heat |
| 23 | Pressure switch did not open | Obstructed tubing or a switch stuck closed |
| 24 | Secondary voltage fuse open | Shorted low voltage wiring, including thermostat leads |
| 31 | HPS pressure switch did not close or reopened | Vent, inducer, combustion air, tubing and condensate drainage checks |
| 32 | LPS pressure switch did not close or reopened | Label refers to code 31 troubleshooting |
| 34 | Ignition proving failure | Gas supply, igniter, flame sensing and grounding checks |
| 45 | Control circuitry lockout | Flame circuit, gas valve relay or software checks |
Payne includes restricted venting and condensate drainage among its pressure fault checks. Report anything already visible at the outside pipe openings from safe ground level. Leave pressure tubing, drains and the internal component test to the technician.
What each one takes
| Task | Work involved |
|---|---|
| Identify the flash pattern | Observation through the door indicator; no parts |
| Care for an accessible filter | Owner maintenance with shutdown and the correct filter |
| Find a pressure or ignition fault | Service visit and measurements before choosing parts |
| Investigate rollout or abnormal flame | Qualified safety diagnosis before further operation |
Questions people ask
Where is the Payne furnace error code PDF?
The PG92ESA installation manual IM-PG92ESA-03 contains the service label on page 63 and the troubleshooting chart on pages 64 and 65. This guide uses the July 2021 edition.
What does one short flash and one long flash mean?
Payne calls code 11 no previous code. Its chart says stored codes are erased after 72 hours, so the absence of a stored fault does not establish that the furnace has never had one.
Does cutting power erase the PG92ESA’s stored code?
Payne says interrupting the 115 volt or 24 volt supply does not erase stored status codes. Its retrieval procedure involves internal wiring, so ask the technician to retrieve the history.
Is code 34 definitely a dirty flame sensor?
No. Payne’s chart also checks gas supply, grounding, ignition and flame carryover. Describe whether the burners lit and then stopped, using what you already observed.
Can I use this for a PG96VTA?
Use that model’s own label and instructions. This page is scoped to the PG92ESA; even a familiar flash number should be matched to the installed control.
The other furnace guides: a blinking furnace light, pressure switch faults and Bryant 926TB codes.
Sources: Payne PG92ESA Installation, Start-up, Operating and Service and Maintenance Instructions, IM-PG92ESA-03, edition 7/21, pages 3, 49, 56, 57, 63 to 65; Lochinvar Knight KB-USER-07, page 1, gas odor precautions.