Free, independent repair guides
HeatCoolFix

Rheem Furnace Not Igniting: R96V Spark Checks

Rheem Furnace Not Igniting: R96V Spark Checks
Short answer

The Rheem R96V in instructions 92-24161-124-08 uses direct spark ignition. It does not wait for a glowing hot surface igniter. Its sequence starts with pressure checks and a purge, then an ignition trial. Report the last event you observed before choosing a repair.

A Rheem furnace not igniting is easy to misdescribe if you are waiting for the wrong kind of igniter. Rheem’s R96V instructions 92-24161-124-08 specify direct spark ignition. For that furnace, the question is whether the startup reached its spark and gas trial, rather than whether a ceramic bar glowed.

This page follows that named R96V document. It adds the actual starting sequence and the manual’s dry trap explanation to the existing Rheem furnace code guide. Keep another model’s measurements and reset instructions with its own paperwork.

Before you start

What to carry: your phone and a torch. Collect the model, the whole control message and what you noticed during the failed heat call. Include whether this was the first heating operation after installation or a long summer shutdown.

Gas or electric? Rheem identifies the covered R96V as a condensing gas furnace with an ECM blower. An electric air handler has a different heating system; this page follows the gas furnace’s ignition.

Renting? Pass these details to the person responsible for heating repairs before anyone opens the equipment.

Observe the sequence without opening the furnace. Rheem says that a suspected gas leak means leaving immediately, without operating switches, using an indoor phone or trying to light anything. Call the gas supplier from outside and follow its directions. If unavailable, call the fire department; do not return until authorized. Rheem also says not to search for the leak yourself or test for it with an open flame.

For overheating or gas that fails to shut off, Rheem requires closing the manual gas valve before shutting off electrical power. Use an accessible shutoff only if safe to do so.

Rheem requires the main electrical supply disconnected before maintenance. Its safety warning prohibits resetting safety controls without corrective action or verification of safe operation by qualified service personnel. Do not bridge a switch, handle the spark wiring or attempt to light these burners by hand.

Confirm that the ignition type matches the complaint

Check 1Model identification before a parts decision

Use the full model when describing no ignition

Say whether the furnace is completely silent, starts its small exhaust fan, or makes an ignition attempt. If it never responds at all, begin with the general furnace power and thermostat checks.

Rheem’s R96V sequence energizes a spark igniter after the purge and gas valve opening. An absent orange glow therefore does not identify a broken hot surface igniter on this model.

The general furnace ignition guide explains the different ignition types. Tell service the actual model and event you observed, rather than ordering an igniter from a photograph of another furnace.

The exhaust fan has work to do before the spark

R96V: DIRECT SPARK, THEN THE MAIN BLOWERABCAProve pressure, then purgeRheem specifies a 30 secondpurge before gas admission.BDirect spark ignition8 second gas trial; spark forup to 7 seconds after opening.CMain blower follows flame20 seconds after flame sensing,stage follows thermostat demand.Do not wait for an orange glowThe named R96V uses sparkto light the main burners.
Rheem's R96V sequence uses a pressure check and purge before direct spark ignition. The indoor blower comes later, after flame sensing. This functional sketch does not show service access.
Check 2Pressure proving and vent system diagnosis

Locate the stop before the ignition trial

Rheem first checks that both pressure switches are open when a legacy thermostat heat contact closes or a communicating thermostat sends a heat request. Its inducer then starts a purge at high stage.

The R96V sequence requires both air proving pressure switches to close. Rheem specifies a 30 second purge before the gas valve opens on high stage for the ignition trial.

If the small exhaust fan was the only thing you noticed, report that without calling it a successful ignition attempt. The technician needs to establish whether pressure proving and the purge completed before testing the spark circuit.

Leave tubing, vent connections and switch testing to service. The pressure switch guide explains why the vent path and its proving controls are considered together.

What the actual ignition attempt looks like in the manual

Check 3Spark, gas delivery and flame sensing checks

Separate no flame from flame that was not maintained

For this R96V revision, Rheem gives an eight second ignition trial after the gas valve opens. Its spark igniter stays energized for up to seven seconds after that opening.

Eight seconds after the gas valve opens, Rheem requires the remote flame sensor to confirm flame for one second. Tell service whether you observed spark without flame, no visible ignition, or flame that appeared and went away.

If ignition is unsuccessful, Rheem describes repeating the sequence up to four times before a one hour lockout. That pause is part of the documented failed ignition response. Repeatedly interrupting power is not a diagnosis of the original failure.

Do not confuse the change after lighting with a failed start

Check 4Compare staging and blower response with the sequence

Include what happened after flame appeared

Rheem starts the ignition trial on high stage. Twenty seconds after flame is sensed, its sequence sets the gas valve to the thermostat’s low or high demand and energizes the main blower at the corresponding heating stage.

That means the first firing stage and the continuing heating stage can differ in Rheem’s specified operation. Give service the order of events if the furnace lit, changed its sound and then lost heat.

For a furnace that maintains flame but sends cool air to the rooms, continue with the furnace cold air guide. Keep that complaint separate from a start that never reached flame at all.

A first seasonal start can involve the condensate trap

R96V: THE DOCUMENTED SELF PRIMING PROCESSADRY TRAPAfter a long off periodBWATER HELDIn the collector boxCPRESSURE EASESWater falls into trapAAir enters through a dry trapNegative pressure holds waterwhile the inducer runs.BWater reaches the sensorRheem ends the heat attempt;the inducer stops after purge.CWater can prime the trapRheem describes up to 4 repeats,particularly in horizontal units.Give service the historyFirst seasonal start, leakage,or a continuing heating failure?
Rheem describes this self priming process after installation or a long off period. It is an explanation to discuss with service, not a direction to keep restarting a furnace or pour water into a hose.
Check 5Drain and startup assessment by service

Mention a long shutdown or new installation

Rheem calls this R96V condensate trap self priming. Its drain section says a dry trap after installation or a long off period can admit air, holding condensate in the collector box while the inducer runs.

Rheem says the rising water reaches the electronic level sensor, ending the heat attempt. After the inducer stops following its purge, the pressure is relieved and water falls into the trap.

The guide says that process can repeat up to four times before full priming, particularly in horizontal installations. Give the technician that seasonal history along with any leakage or continuing failure. The manual’s specific explanation is not a reason to dismiss water trouble throughout the heating season.

Leave drain alterations and internal inspection to service. Do not apply another furnace’s manual filling procedure to the self priming trap described here.

What each one takes

Observation Next work
No response to a heat request Power and thermostat diagnosis
Inducer runs without an ignition trial Check the starting safety and pressure proving sequence
Spark trial without maintained flame Test ignition, gas delivery and flame sensing
Furnace lights, then changes stage Compare the response with the thermostat demand
Failure after a long shutdown Assess trap priming and the installed drain arrangement

Questions people ask

Where is the R96V manual used here?

Rheem’s R96V installation library lists revision 92-24161-124-08 from June 2016. That is the revision saved and used for this page.

Is the small fan meant to stop immediately after heating?

Rheem’s normal sequence gives the inducer a 10 second purge after the heat request ends and the gas valve closes. The main blower continues according to the control’s off timing.

Does this sequence require a communicating thermostat?

Rheem describes both a legacy W heat call and a heat request from a communicating thermostat. Include the installed wall control model in the repair information.

Can I borrow the Ruud code table?

Use the model and revision attached to each table. The Ruud code guide follows an R96T document; this ignition page follows Rheem’s R96V instructions.

Should I relight a pilot before checking anything else?

Rheem describes direct ignition of the main burners on this R96V, and prohibits manual lighting. A standing pilot procedure does not belong to the documented startup here.

The other furnace guides: furnace flame sensor, furnace inducer motor, and furnace leaking water.

Sources: Rheem R96V installation instructions 92-24161-124-08, official R96V installation document library, safety warnings, condensate section page 67, sequence page 83 and maintenance warnings