Bryant's 926TB uses short flashes for the first digit and long flashes for the second. Three short and three long is 33, a limit circuit fault; one short and three long is 13, a limit lockout. Its pressure codes also distinguish low heat from high heat. Match the model before using the chart.
Bryant furnace error codes on the 926TB are read in two parts: Bryant assigns the short flashes to the first digit and the long flashes to the second. Three short flashes followed by three long flashes means 33, not six.
The useful next question is which circuit that number names. Bryant’s 926TB is a two stage gas furnace, and its service chart separates low heat pressure faults from high heat pressure faults. Those distinctions can get lost in a general brand list.
Before you start
What to carry: a torch and a phone to record the blinking light. Bryant says the status LED can be viewed at the indicator in the blower door.
Gas or electric? This chart is for the Bryant 926TB gas furnace. An electric air handler, a heat pump or another Bryant furnace needs its own instructions.
Renting? Give the model and flash sequence to your landlord or maintenance contact. Ask them to arrange any repair.
The Carrier furnace code guide covers related controls. Here the definitions come from Bryant’s own 926TB manual, including its service label and troubleshooting chart.
If you smell gas, do not light any appliance, touch electrical switches or use a phone inside. Leave and call the gas supplier from outside, then follow its instructions. If it cannot be reached, call the fire department.
Bryant says the cause of a rollout trip must be corrected before its switch is reset, and forbids bypassing the furnace’s safety controls. Leave rollout, gas valve and live electrical checks to trained service personnel.
Bryant permits basic owner maintenance such as filter care. Before maintenance, Bryant says to shut off the gas and electrical supplies and install a lockout tag, following the operating label on the furnace.
Count two groups, not a single total
Read the light through the door
Watch the full repeating pattern and save a video before changing anything. Read the model information already available in your paperwork or on an accessible label.
Bryant identifies the 926TB control light as amber. Its service label says a continuously lit LED means the control has 24 volt power. Rapid flashing points to reversed incoming power polarity or a furnace grounding problem.
Do not remove the door and hold its switch shut to get a better view. Bryant’s manual warns that doing so exposes electrical components during service.
Three short, three long: 33 and the later 13
Keep a limit fault separate from a rollout diagnosis
Bryant’s code 33 covers an open limit or flame rollout circuit. The 926TB label also uses it when the furnace runs in high heat only after two successive low heat limit trips.
A dirty filter is one item in Bryant’s troubleshooting chart, alongside restricted ducts, blower problems and other causes. Check an owner accessible filter only with the shutdown precautions above, and replace or clean it as its own instructions require.
The number cannot tell you which safety device opened. A filter change is not a reason to reset a rollout switch. The rollout switch guide explains why that fault needs investigation.
Bryant says 13 is a lockout when a limit or rollout switch stays open longer than three minutes, or after ten successive limit trips during high heat. Its control automatically resets after three hours.
So one short flash and three long flashes is useful information even if the heat later returns. Report both 33 and 13 when you saw them in that order.
Code 34: the flame was not proved
Describe whether the burners lit
Bryant calls 34 an ignition proving fault. Its service label says the control will try three more times before code 14 lockout; the troubleshooting chart describes four unsuccessful ignition and flame proving attempts in total.
Tell the technician whether you noticed ignition followed by shutdown, or no ignition at all. Use what you already observed; do not open the burner compartment to recreate the failure.
Bryant’s code 34 checks include flame sensor deposits, grounding, gas supply, the igniter and flame carryover between burners. That is why a search result saying “34 means a dirty flame sensor” leaves out other possibilities.
Bryant’s code 14 entry gives an automatic reset after three hours. That timed restart does not show that the ignition problem is fixed.
The 926TB pressure and service codes
Keep 31, 32 and 43 distinct
Bryant’s 926TB table uses 31 for the high heat pressure switch or its relay, 32 for the low heat pressure switch, and 43 when the low heat switch is open while the high heat switch is closed.
For code 32, Bryant lists a plugged condensate drain, restricted combustion air, vent problems, pressure tubing and other checks. From a safe ground level position, report visible snow or debris at the outside pipe openings. Leave tubing, drain disassembly and pressure measurements to the service visit.
Keep any recent change in the report, such as work on the vent or the fault beginning in windy weather. Bryant includes excessive wind among its code 32 checks.
| 926TB code | Bryant’s description | Who takes it further |
|---|---|---|
| 22 | Flame proved with the gas valve deenergized; the checks include a leaking or stuck open valve | Urgent qualified service; do not keep trying to run the furnace |
| 25 | Model selection or setup error | Installer checks the model plug and setup switches |
| 31 | High heat pressure switch or HPSR relay did not close or reopened | Technician checks the high heat circuit |
| 32 | Low heat pressure switch did not close or reopened | Technician checks draft, drain and related inputs |
| 43 | Low heat pressure switch open while high heat pressure switch is closed | Technician compares the two inputs |
| 45 | Control circuitry lockout | Technician checks control operation |
What each one takes
| Job | What to expect |
|---|---|
| Read the current code | No parts or open panels; watch through the door indicator |
| Check an accessible filter | Basic maintenance, with safe shutdown and the correct filter |
| Retrieve fault history | A technician uses the control’s service procedure |
| Investigate ignition or pressure faults | A service visit with electrical, gas or draft measurements as appropriate |
| Investigate a rollout or abnormal flame signal | Qualified safety diagnosis before further operation |
Questions people ask
Where can I download the Bryant error code PDF?
Bryant’s 926TB installation and service manual has the service label on printed page 67 and the troubleshooting chart on pages 68 and 69. This guide uses revision D.
Does switching the 926TB off erase its stored faults?
Bryant says interrupting either the 115 volt or 24 volt supply does not erase stored status codes. The control stores up to the last seven codes in order. Leave retrieval to the technician because the procedure involves the open control compartment.
What does code 11 mean?
Bryant labels it no previous code. Its chart says stored codes are erased after 72 hours, or by the specified service procedure. A blank history is not a record of everything the furnace has ever done.
Why did the blower run when power came back?
For code 12, Bryant describes a 90 second blower run if power returns during a heat call, or the heat call ends during the blower on delay. That entry is different from an ignition failure.
Does this cover a Bryant 987M or 915S?
No. This is the 926TB chart. Match a 987M, 915S or other model to its own manual instead of transferring the stage specific definitions here.
The other furnace guides: reading a blinking furnace light, the limit switch and the rollout switch.
Sources: Bryant 926TB Installation, Start-up, Operating and Service and Maintenance Instructions, II926TB-04 REV D (2023), pages 60, 67 to 69; gas odor precautions crosschecked against Lochinvar Knight KB-USER-07, page 1.