Amana Furnace Error Codes: AMVC96 E2, EE2 and Eb9

Amana Furnace Error Codes: AMVC96 E2, EE2 and Eb9
Short answer

Amana AMVC96 controls need the full model and code. The 2014 service manual uses E2 for a low stage pressure switch that stays open. The AMVC96 BB installation manual uses EE2. Its EE9 concerns high stage pressure, while Eb9 reports less airflow than demanded. These are displayed codes, not flash counts.

Amana furnace error codes such as E2 and EE2 need their letters kept intact. Amana’s AMVC96 manuals use both formats across different control versions, and neither message means that you should count two flashes.

For the AMVC96 AA models in the 2014 service manual, E2 identifies a low stage pressure switch that has not closed. The AMVC96*BB installation guide from July 2020 calls that condition EE2. Start with the version before deciding what needs attention.

Before you start

What to carry: your furnace records, a torch and a phone to capture the display.

Gas or electric? This guide covers Amana AMVC96 gas furnaces. The Amana PTAC codes belong to a different room heating and cooling unit.

Which manual? IOG-2015E covers the BB furnace revision used for the main table here. RS6612010r1 supplies the older AA model’s E2 and E3 comparison. Do not turn these into a chart for every Amana furnace.

Renting? Pass the model, code and heating symptoms to the person responsible for the property before arranging work on the furnace.

Keep gas and safety circuits out of a reset experiment.
Amana’s instructions say that a gas smell means no ignition attempts, electrical switches or phone use inside the building. Leave and immediately call the gas supplier from a neighbor’s phone. Follow the supplier’s instructions. Call the fire department if the supplier cannot be reached.

The BB installation manual requires the external manual gas valve to be shut before the electrical supply if the furnace overheats or gas fails to shut off. Only approach a shutoff you can reach safely.

For service or maintenance, Amana requires electrical power to be disconnected. Its internal checks belong to trained service personnel. Leave the doors and electrical covers in place while observing the display.

Keep E2, EE2 and a blinking light separate

AMVC96: KEEP THE COMPLETE CODEAE2AA models: 2014 service guideLow stage pressure switch stays open.This is a displayed E2, not two flashes.BEE2BB models: July 2020 install guideLow stage pressure circuit has not closed.The extra E belongs to this control version.Sources: RS6612010r1 and IOG-2015E. Display shapes are schematic.
The older AA service manual uses E2. The BB installation manual uses EE2 for the low stage pressure circuit. These are letter-and-number LED messages, not two flashes.
Check 1No replacement parts; identification before a service diagnosis

Match the message to the control version

Amana’s BB manual describes a seven segment LED display that reports letters and numbers. Copy the full model suffix and message, including the repeated E or a small b, and compare them with your furnace’s documentation. If it is not visible without opening the cabinet, ask the service agency to retrieve it.

The BB manual also lists operating messages, including heating and cooling states. A lit display is not itself a fault. Use its troubleshooting chart for an error message and its separate status table for operating information.

Our Goodman furnace code guide follows different named furnace families. The AMVC96 high stage and blower entries below need this furnace’s own chart.

The AMVC96 BB codes used on this page

Amana’s IOG-2015E troubleshooting chart gives the following meanings. The BB scope applies to every row, including the lower case b in the blower codes.

BB display What the installation guide reports Area to investigate
EE0 Lockout after unsuccessful ignition attempts Ignition and flame establishment
EE1 Low stage pressure circuit already closed at the start of heating Switch contacts and circuit wiring
EE2 Low stage pressure circuit has not closed Hose, vent, inlet, drain, inducer and switch
EE3 Primary limit circuit open Airflow and the limit circuit
E11 Rollout switch open Burner and combustion investigation
EE4 Flame sensed without a heat request Flame circuit and gas valve operation
EE6 Weak flame sensing current Sensor condition, position and combustion
EE8 High stage pressure circuit closed at the start of heating High stage switch contacts and wiring
EE9 High stage pressure circuit has not closed High stage draft system
Eb3 Blower operating at its power, temperature or speed limit Restricted airflow and duct sizing
Eb9 Airflow below the demanded amount Filter, registers and ductwork

What E2 or EE2 tells the service technician

Check 2Draft diagnosis; a switch is only one possible repair

Look for a low stage draft problem

For BB EE2, Amana lists a blocked, pinched or wrongly connected hose, restricted flue or inlet piping, a blocked drain, weak inducer operation, switch trouble and loose wiring. The code identifies the circuit that failed to close, rather than naming a part to buy.

The older AA service manual’s E2 description likewise includes hose, switch, wiring and intake or flue problems. It says the control enters an hour of lockout if the low stage switch does not close within five minutes after the inducer starts.

Report whether you hear the inducer running without ignition, and mention any visible damage to the outside pipe termination from a safe ground-level position. Leave pressure measurements, tubing and drain disassembly to the technician. The pressure switch guide explains the relationship between those parts.

Some faults leave the furnace on low heat

Check 3A service visit to investigate why higher output is unavailable

Separate a high stage fault from no heat at all

Amana’s BB chart says EE8 and EE9 can leave the furnace operating on low stage while high stage is unavailable. Tell the service agency if the house receives some heat but struggles to reach the thermostat setting.

For EE9, Amana tells the technician to check the pressure hose, flue and inlet pipes, drain system, inducer and wiring. For EE8, it points to sticking high stage switch contacts or a short in that circuit.

Keep those two faults separate from Eb9. Amana describes Eb9 as airflow below demand and notes that the furnace can run at reduced performance or on low stage when high stage is expected.

AMVC96 BB: TWO REASONS FOR REDUCED HEATABAEE9: high stage draftHigh stage pressure circuit stays open.The chart lists operation on low stage.BEb9: airflow below demandThe chart calls for filter, registerand duct checks.Source: IOG-2015E, pages 47 and 48. Parts shown schematically.
On the BB control, EE9 concerns the high stage pressure circuit. Eb9 concerns delivered airflow. Both can explain reduced heating, but they lead to different checks.
Check 4Filter maintenance if needed; further work depends on airflow testing

For airflow messages, start with accessible filter care

Amana’s BB chart includes blocked filters and restrictive ductwork among the causes of EE3, Eb3 and Eb9. Amana also requires externally installed filters, with their location depending on the installation.

With power disconnected, inspect an accessible filter and clean or replace it according to its type and the furnace instructions. Fit it back securely and close any access panel. Check that furniture is not covering room registers; the Eb3 and Eb9 chart asks for registers to be fully open.

If the message returns, the technician may need to check blower operation, airflow settings or duct sizing. For E11, skip filter-based troubleshooting: Amana’s rollout row calls for gas pressure, burner alignment and burner restriction checks.

What each one takes

Finding What the next step involves
Unclear model revision or display Identification from records or a service visit before selecting a chart
Dirty accessible filter with an airflow message Cleaning or a matching replacement, with power off
E2 on AA, or EE2/EE9 on BB Draft system diagnosis; the fault decides which repair is needed
Continuing Eb3 or Eb9 on BB Blower and duct assessment rather than an assumed board replacement
E11 or EE4 on BB Qualified combustion, gas valve or flame circuit investigation

Questions people ask

Where is the Amana furnace error codes PDF?

The main chart is in Amana installation instructions IOG-2015E, pages 46 to 48. The older E2 comparison comes from service manual RS6612010r1. Keep each manual with its listed revision.

My Amana gives three, four or six flashes. Can I use this table?

No. Those counts do not identify this display system. The AMVC96 entries here are complete LED messages. Find the chart for the furnace and board producing the flashes.

Does E3 mean the same thing as EE3?

The older AA service manual groups primary, auxiliary and rollout limits under E3. The BB installation chart lists EE3 for the primary limit and gives rollout its own E11 entry. Do not drop the extra E when comparing them.

Does EE6 mean the furnace has already stopped?

Amana’s BB table lists normal furnace operation alongside the weak flame current warning. It gives sensor coating, sensor position and combustion conditions as possible causes. Continued heating still leaves a signal problem to investigate.

Why does BB EE0 disappear and come back?

Amana gives this control an automatic retry after an hour of ignition lockout. The installation manual also says it returns to lockout if the original condition remains. Restored operation alone does not identify what went wrong.

The other furnace guides: reading a blinking light, limit switch faults and rollout switch trips.

Sources: Amana / Goodman Installation Instructions IOG-2015E (July 2020), AMVC96*BB and ACVC96*BB, pages 1, 4, 42, 43 and 45 to 48; Amana / Goodman Service Instructions RS6612010r1 (November 2014), AMVC96/ACVC96 AA models, product identification and troubleshooting; https://resource.ecmdi.com/is/content/Watscocom/Gemaire/amana_amvc96_en_ii.pdf ; https://documents.alpinehomeair.com/product/Amana%20AMVC96%20Service%20Manual.pdf