On a Bosch Climate 5000 wall mounted mini split, codes are four characters shown two at a time on the indoor display. Bosch lists EL 01 as an indoor and outdoor unit communication error, EL 0C as a refrigerant leak and PC 03 as pressure protection. In winter, PH 09 is anti-cold air in heating mode and pc 0L means it is too cold outside, while dF is simply a defrost.
Bosch mini split error codes on the Climate 5000 wall mounted unit are four characters, and Bosch’s user manual says they are displayed two at a time on the indoor display. So EL 01, which Bosch lists as an indoor and outdoor unit communication error, arrives in two halves.
Two winter displays have plain meanings in Bosch’s manuals. Bosch’s user manual lists dF as defrost, and its 2025 service manual error code table lists PH 09 as anti-cold air in heating mode. Everything below comes from those two Bosch manuals for the Climate 5000 wall mounted unit.
Before you start
What to carry: a torch, the remote, and your phone to film the display through a full code. Only the front panel opens, for the filter in check 5.
Gas or electric? Electric. Bosch calls the Climate 5000 wall mounted unit a ductless split air conditioner and heat pump.
Renting? Send the code, the model number and the serial number to whoever arranges repairs. Bosch asks for a detailed description of the malfunction, the model number and the unit serial number.
Bosch’s stop list. Turn the unit off immediately if the power cord is damaged or abnormally warm, you smell burning, it makes loud or abnormal sounds, a fuse blows or the breaker trips often, or water or objects fall into or out of it. Bosch says not to fix these yourself and to contact a qualified service person immediately. Its safety page adds that in an abnormal situation like a burning smell, you immediately turn the unit off and pull the power plug.
Power off before cleaning. Bosch says always turn off the system and disconnect its power supply before cleaning, maintenance or changing the filter. The metal edges inside are sharp, and water must never be used inside the indoor or outdoor unit.
The outdoor unit is not yours. Bosch says any maintenance and cleaning of the outdoor unit, and any repair, must be done by qualified service personnel only.
Read the whole code
Watch for both halves of the code
Because Bosch shows four character codes two at a time, film the display until the pattern repeats and write down both halves in order. Then match the whole code, not just its first half, against the tables below.
Displays that are not faults
Rule out the reminders and features
Bosch’s user manual display code table gives these meanings:
| Display | What Bosch says it means |
|---|---|
| dF | Defrost |
| CL | Filter cleaning reminder, shown for 15 seconds at power on; or Active Clean |
| nF | Filter replacement reminder, shown for 15 seconds at power on |
| FP | Heating in room temperature under 46°F (8°C) |
| FC | Forced cooling |
| CP | Remote switched off |
CL has two meanings. Bosch says the filter cleaning reminder flashes CL after 240 hours of use. Active Clean also shows CL, and Bosch says the unit then turns off by itself after 20 to 45 minutes. nF, the filter replacement reminder, comes after 2,880 hours.
To clear either reminder, Bosch says press the LED button on the remote 4 times, or the MANUAL CONTROL button 3 times. If you do not reset it, it flashes again at the next start.
Bosch error codes
These are selected rows from Table 13 in Bosch’s 2025 service manual for the wall mounted unit.
| Display | What Bosch’s table says |
|---|---|
| EH 00 / EH 0A | Indoor unit EEPROM parameter error |
| EL 01 | Indoor / outdoor unit communication error |
| EH 03 | Indoor fan speed operating outside the normal range |
| EC 51 | Outdoor unit EEPROM parameter error |
| EC 52, EC 53, EC 54 or EC 56 | A temperature sensor open or short circuited: T3 condenser coil, T4 outdoor, TP compressor discharge or T2B evaporator coil outlet |
| EC 07 | Outdoor fan speed operating outside the normal range |
| EH 0b | Indoor PCB/display board communication error |
| EL 0C | Refrigerant leak detected |
| PC 00 | IPM malfunction or IGBT over-strong current protection |
| PC 10 / PC 11 | Over low voltage / over voltage protection |
| PC 02 | Compressor top high temperature protection |
| PC 03 | Pressure protection |
| PC 06 | Compressor discharge temperature protection |
| PC 08 | Outdoor current protection |
| PC 40 | Communication error between the outdoor main chip and the compressor drive chip |
This page shows selected rows only. Bosch’s note under its table says to contact the manufacturer about an error code not displayed in its Table 14, as that error is for development purposes only.
The winter codes
With PH 09 or pc 0L, check what it is doing and how cold it is
PH 09 is anti-cold air in heating mode in Bosch’s table. Bosch’s service manual says that in heating mode the indoor fan is regulated by the anti-cold wind function, which has priority, using the room temperature and the indoor coil temperature.
pc 0L is outdoor ambient temperature too low. Bosch’s user manual gives the outdoor range for HEAT mode as -13°F to 86°F on the regular 9K to 24K units, -22°F to 86°F on the Max Performance 9K to 24K, and 5°F to 86°F on the 30K and 36K. Outside those ranges, Bosch says safety protection features may activate and cause the unit to disable.
Bosch’s table also lists LC and LH codes as frequency limits, for example LC 05 caused by voltage, and nA as no malfunction or protection.
Keep it powered below freezing
When it is below 32°F outside, Bosch strongly recommends keeping the unit plugged in at all times. It says a base pan heater in the outdoor unit prevents ice build up, and ice may build up if the unit is unplugged.
So below 32°F, keep it plugged in. For a long break in use, Bosch’s routine is to run FAN until the unit dries out, turn it off, disconnect the power and clean the filters, but Bosch also says ice may build up in the outdoor unit if it is unplugged below 32°F.
Clean the filter, then try one restart
Bosch says a clogged air filter can reduce the cooling efficiency and make the airflow irregular and noisy. With the unit off and its power disconnected, its steps are to pull the filter up and out without touching the metal parts inside. Next, unclip any small air freshening filters and clean those with a hand held vacuum, then wash the large filter in warm soapy water with a mild detergent, rinse, shake it, and dry it out of direct sunlight. Bosch also says not to touch the air freshening filter for at least 10 minutes after turning the unit off.
For operation that is erratic, unpredictable or unresponsive, Bosch suggests disconnecting the power, reconnecting it and pressing ON/OFF on the remote. Bosch also notes a 3 minute protection feature, so the unit cannot restart within three minutes of being turned off. If a problem persists, contact a local dealer or a qualified service provider.
What each one takes
| What you see | What the work involves |
|---|---|
| dF, FP, CP or FC | Nothing; a defrost or a feature |
| CL or nF reminder | Cleaning or replacing the filter, then a reset |
| PH 09 in heating | Knowing the indoor fan is under Bosch’s anti-cold air control |
| pc 0L in cold weather | Checking the outdoor temperature against Bosch’s range |
| EL 01 or an EC sensor code | A qualified service person |
| EL 0C or PC 03 | A qualified service person on the refrigerant side |
Questions people ask
Is CL on my Bosch an error?
No. Bosch lists CL as the filter cleaning reminder after 240 hours of use, or as Active Clean running. If it is the reminder, turn the unit off and disconnect its power, clean the filter, then reset the reminder with the LED button pressed 4 times. Active Clean turns itself off after 20 to 45 minutes.
Why does my Bosch show pc 0L in a cold snap?
Bosch’s service manual calls pc 0L outdoor ambient temperature too low. Compare the outdoor temperature with the HEAT mode range for your model line in Bosch’s user manual.
Should I unplug my mini split for the winter?
Below 32°F, Bosch strongly recommends keeping the Climate 5000 wall mounted unit plugged in at all times, because a base pan heater prevents ice build up in the outdoor unit and ice may build up if it is unplugged.
Is PC 03 a refrigerant leak?
Bosch’s 2025 table calls PC 03 pressure protection; its leak code is EL 0C. Either one is work for a qualified service person.
Does this cover my Bosch ducted unit or cassette?
No. These tables are for the Climate 5000 wall mounted unit, so use your own unit’s manual. The ducted Bosch IDS heat pump has its own codes.
The other mini split guides: mini split error codes, Carrier mini split error codes, mini split not heating and mini split freezing up.
Sources: Bosch Climate 5000 Series wall mounted ductless split air conditioner / heat pump user manual BTC 769103302 B (06.2022) and service manual BTC 769102301 C (05.2025)