For Coleman DGAA and DGAH gas furnaces, follow the labeled automatic ignition procedure and keep the filter and return air path clear. These models have no pilot to light. Their door mounted filter instructions differ from Coleman's residential furnace manual, which requires external filters.
Coleman furnace not heating after a shutdown? For the DGAA and DGAH, Johnson Controls gives a specific automatic ignition procedure, followed by a stop point if the burner will not light.
There is no pilot to relight on those models. Their owner’s manual says an ignition device lights the burner automatically and prohibits lighting it by hand. The useful checks are the thermostat request, restored power, correct startup and an open airflow path.
This guide concentrates on Coleman DGAA and DGAH manufactured home gas furnaces in manual 5165697-BUM-C-0818. It also identifies where Coleman’s residential manual differs. For a flashing light, use the Coleman DGAA/DGAH code guide alongside the observations here.
Before you start
What to carry: a torch, your phone and the complete furnace model and serial number. Johnson Controls asks for those numbers when requesting service so the repair contact can identify the equipment.
Gas or electric? Match DGAA or DGAH on the furnace label. The instructions here concern gas burners, an electric igniter and a circulating blower. An electric resistance furnace needs a different operating procedure.
Renting? Give maintenance the model and whether you hear startup, receive room airflow or get any warmth. Have them arrange the furnace access and any gas control work.
Johnson Controls’ DGAA/DGAH manual says a gas smell means no lighting attempts, electrical switches or phone use inside. Leave immediately. Call the gas supplier from outside, follow its instructions, and call the fire department if the supplier cannot be reached.
For overheating or gas that fails to shut off, this manual says to close the external manual gas valve and let the blower run until the furnace cools and the blower shuts off before disconnecting electrical power. Do not use the ordinary shutdown sequence below for that emergency. Leave and get help if you cannot reach the shutoff safely.
If a fault light is flashing and it is safe to look, record it through the clear viewing port before routine shutdown. Johnson Controls warns that cutting power clears the stored fault. Follow the emergency instructions above first if there is gas smell or overheating.
For routine access, disconnect electrical power before a door comes off. Never force a gas control or operate it with tools. The manual requires a qualified technician if its switch will not move by hand. Do not operate a flood damaged furnace.
Match the model before buying a filter
Johnson Controls catalogs the DGAA/DGAH manual under Coleman, Evcon and Guardian. It describes filters attached to the furnace door. Its separate residential manual, 1010352-UUM-N-0121, is also cataloged for Coleman, including TM9Y, and requires filters external to the cabinet.
That is why a filter instruction for another Coleman can be wrong for yours. Use the model’s own filter arrangement before following a general furnace maintenance tip.
The furnace stays quiet, or only the room fan runs
Give the furnace a clear heat request
The DGAA/DGAH owner’s checklist starts with the thermostat setting and HEAT/COOL switch. Confirm the heating mode and the wanted room temperature, then check that the external furnace power supply is on.
For a thermostat with a fan switch, Johnson Controls describes ON as continuous blower operation. Its heating sequence instead starts with HEAT and AUTO. Use those settings to observe a heating call, rather than judging the furnace from continuous room temperature airflow alone.
If yours is a residential Coleman covered by manual 1010352, its owner checklist adds the blower access door: removing it cuts electrical power. A door recently removed for maintenance should be correctly replaced before operation. Keep the door switch in service; do not hold it closed as a test.
If the thermostat itself will not respond, use the thermostat checks before working through the gas furnace startup procedure.
Starting a DGAA or DGAH after shutdown
Follow the furnace's operating label in order
Use the instructions attached to your furnace and match them to the DGAA/DGAH manual. Do not start it with a gas smell, water damage or an unresolved safety fault. If you cannot identify the illustrated gas control switch, leave this step to the servicing contractor.
Johnson Controls’ procedure first sets the thermostat to its lowest setting and turns off all electrical power to the appliance. Remove the furnace door, then move the gas control switch to OFF by hand without forcing it.
Wait five minutes to clear gas. Before continuing, smell around the appliance and near the floor as the manual directs. A gas smell means stop and follow the warning above.
If there is no gas smell, move the control switch to ON, replace the burner door, restore electrical power and set the thermostat to the desired temperature. The manual allows 30 to 60 seconds for burner ignition.
Its stop point is explicit: after three ignition trials without operation, follow the appliance shutdown instructions and contact the technician or gas supplier. Those are the furnace’s ignition trials, not an instruction to perform three more manual restarts.
For that ordinary shutdown, set the thermostat to its lowest setting, isolate electrical power before opening the burner access, put the gas control switch OFF and replace the access panel. Leave the unit for service. Overheating and uncontrolled gas still follow the earlier gas first warning.
What should happen during the heat call?
Describe the last part of startup that happened
Johnson Controls describes the inducer starting first to purge the heat exchanger. The hot surface igniter then warms, the gas valve opens and the burner lights. The circulating blower starts afterward to distribute the warm air.
The detailed DGAA/DGAH sequence puts circulating blower startup 30 seconds after the gas valve opens, provided flame is established through its stabilization period. A brief interval between ignition and room airflow therefore belongs in the expected sequence.
Keep the cabinet closed while it operates. Tell the repair contact whether there was a small motor sound, an ignition attempt, flame visible through an existing viewing opening, or room airflow. If the burner lights and then goes out, include that rather than reporting only “cold air.”
When the thermostat is satisfied, the manual says gas shuts off and the blower continues to distribute remaining heat. Tell service whether the fan continued after a completed heat call or the burner never lit.
It tries to light, then stops
Leave ignition proving and retry faults for service
In the DGAA/DGAH heating sequence, Johnson Controls says failure to detect flame shuts the gas valve and starts a retry. Its description of disrupted flame includes a momentary gas supply loss, flame blowout and a faulty flame probe circuit.
Give service the sequence you observed and any known interruption of the gas supply. The possibilities need checking before a part is selected. A brief flame does not identify a failed igniter by itself.
Do not bridge a pressure switch, adjust the gas valve or reset an internal limit to keep it running. Keep any visible fault pattern for the matching Coleman code explanation. Component testing belongs with the technician; the ignition guide explains that separate diagnosis.
The airflow check that belongs to these models
Keep the specified filters and air passages clear
The DGAA/DGAH owner checklist calls for clean filters, unobstructed return grilles, open supply registers and clear flue piping. Inspect accessible openings from a safe position. Leave roof access and vent disassembly to service.
For the filter work itself, Johnson Controls requires ventilation, routine shutdown and metal surfaces cooled to room temperature. Its maintenance warning says to turn the thermostat off, let a running blower stop automatically, then turn off gas and electrical supplies before proceeding.
The manual specifies two filters, 16 by 20 by 1 inches, of the same size and type, and says not to use a pleated filter in this furnace. It calls for checks every three months, with more frequent checks during new construction.
The door rack filter slides down for removal. Refit a replacement of the specified type, or a fully dry cleanable filter, then replace the door and make sure it snaps into its retaining clips. Follow the labeled operating instructions to return it to service.
Stop if you find water, damaged parts, vent leakage or blockage, or excessive dust and lint on internal components. Johnson Controls says not to operate the furnace in those conditions and reserves internal cleaning for a service professional.
What each one takes
| What is happening | Work involved |
|---|---|
| Only continuous room airflow | Confirm a HEAT and AUTO request on DGAA/DGAH |
| Furnace was deliberately shut down | Use the matching operating label, including the gas clearing wait |
| Burner never establishes operation | Stop at the manual’s failed ignition instruction and arrange service |
| Burner lights and goes out | Have gas supply and flame proving investigated |
| Restricted room airflow | Correct model specific filters and clear registers and returns |
| Water, damaged parts or vent defects | Leave the furnace off for qualified inspection |
Questions people ask
Does the same filter rule apply to my Coleman TM9Y?
The saved residential manual covering TM9Y requires external filters, in a rack attached to the casing or in the return duct. It specifically says not to install filters inside the cabinet. Use that installation’s specified filter rather than the DGAA/DGAH door filter instructions.
What if I cannot find the residential filter?
Johnson Controls’ residential user manual says to ask the installer or technician when the filter location or replacement procedure is unclear.
Can the furnace’s fuel type be changed to restore heating?
The DGAA/DGAH manual reserves fuel conversion for a qualified technician and warns that improper conversion can cause unsafe operation. Tell service the fuel available and the furnace label information.
When should professional maintenance be arranged?
The DGAA/DGAH manual calls for service at the beginning of each heating season. Its list includes the combustion chamber, vent and roof jack, gas connections and operating adjustments.
Where are the original startup instructions?
The manufacturer catalogs DGAA/DGAH manual 5165697 for Coleman. Startup is on printed page 4 and shutdown and filters are on page 5. Match the revision and the instructions attached to your furnace.
The other furnace guides: Coleman DGAA/DGAH fault lights, ignition faults and identifying a true pilot light system.
Sources: Johnson Controls Unitary Products DGAA and DGAH Series User's Information, Maintenance and Service Manual 5165697-BUM-C-0818, August 2018, operating instructions pages 4 and 5, filters page 5, heating sequence page 7; Johnson Controls Ducted Systems Residential Multi-position Gas Furnace User's Information Manual 1010352-UUM-N-0121, January 2021, external filters page 4 and owner troubleshooting page 5. Johnson Controls' saved catalog listings explicitly assign both documents to Coleman; residential listing includes TM9Y.