Coleman Furnace Error Codes: DGAA and DGAH Flash Guide
For Coleman DGAA/DGAH furnaces covered by manual 5165697-BUM-C-0818, one green flash is ignition failure, three flashes mean the pressure switch failed to close and four mean an open limit. Record the pattern through the viewing port before a routine power cycle clears it. Gas smell or overheating takes priority, and internal repairs belong to service.
Coleman furnace error codes need the model and control chart. For DGAA and DGAH furnaces covered by manual 5165697-BUM-C-0818, Johnson Controls lists one green flash as ignition failure, three as a pressure switch that failed to close and four as an open limit switch.
The manual places the green diagnostic light behind a clear viewing port in the blower-compartment door. Start by recording that pattern without opening the cabinet. Its diagnostics section warns that switching furnace power off clears the stored fault.
This page follows the August 2018 DGAA/DGAH manual, which the manufacturer’s document listing identifies for Coleman, Evcon and Guardian. Other Coleman series need their own charts. Our furnace blinking-light guide explains the wider model-first lookup.
Before you start
What to carry: a torch, a phone for a short video and the matching manual. Find the model and serial number on accessible paperwork or an outside label. Record whether the burner never lights or heating stops after starting.
Gas or electric? The DGAA/DGAH models covered here are gas furnaces with electrical controls. Johnson Controls identifies them as single-stage downflow furnaces. Do not apply this green-light chart to a Coleman electric furnace or a different gas control board.
Renting? Send maintenance the model, serial number, flash video and any known supply interruption. Mention if power has already been switched off, since that affects the fault record.
Johnson Controls says that if gas supply fails to shut off or overheating occurs, shut the gas valve before shutting off electrical power. Its fuller shutdown instruction says to use the external manual gas valve and let the furnace cool before electrical shutdown. Only approach it if safe.
For a gas smell, the manual says not to light an appliance, operate electrical switches or use a phone in the building. Leave immediately. Call the gas supplier from a neighbor’s phone and follow its instructions; if unreachable, call the fire department.
The manual prohibits using a furnace that has been under water. It also says not to operate it with damaged components, vent leakage or blockage, or water on a surface inside or outside the furnace. Arrange the specified qualified inspection.
Keep the doors fitted. Johnson Controls reserves service involving component removal or adjustment for qualified personnel. Do not bypass or adjust a pressure switch, reset an internal limit yourself, or try to light the burner by hand.
Count the green flashes before a routine power reset
Record complete flash groups through the port
Johnson Controls says the numbered pattern uses one second on and one second off for each flash, with a two-second off period separating code groups. Take a video long enough to capture the repeating group rather than counting one isolated blink.
For the following numbered entries, its printed page 8 gives these meanings. Keep them scoped to this manual and the control fitted to your furnace.
| Green-light pattern | Johnson Controls description | Useful next action |
|---|---|---|
| One flash | Ignition failure | Report a failed start and known supply history |
| Two flashes | Combustion-air pressure switch closed when expected open at cycle start | Qualified switch and wiring diagnosis |
| Three flashes | Combustion-air pressure switch failed to close at cycle start | Qualified airflow, inducer, hose and switch diagnosis |
| Four flashes | Primary or auxiliary limit switch open | Outside airflow observations and professional overheat diagnosis |
| Five flashes | Gas flow with no call for heat | Prompt qualified gas-valve and wiring assessment; no forced heat call |
| Rapid flashes | Reverse line-voltage polarity | Qualified electrical assessment |
Do not switch power off merely to make the indicator disappear before recording it. That is a diagnostic step, not permission to leave an unsafe furnace running. The safety instructions above always take priority.
Two and three flashes do not prove a bad pressure switch
Keep the listed causes as possibilities
For two flashes, Johnson Controls says the pressure-switch contacts were closed when the control checked for an open condition at the start of a heating cycle. Its listed possibilities are a faulty pressure switch or miswiring.
For three flashes, the expected closure did not occur. The manual names a faulty inducer, blocked vent, broken pressure-switch hose or faulty switch as possible causes. The number alone does not select which component needs replacing.
From a safe ground-level position, note visible vent damage or obstruction for the technician. Do not climb onto the roof, disconnect tubing, open the vent or bridge switch terminals to obtain heat. Johnson Controls explicitly prohibits pressure-switch bypassing and adjustment.
Give service the flash group and whether the inducer appeared to start. If you cannot tell from outside the closed cabinet, record that uncertainty. Leave measurements and combustion-system inspection to the qualified person.
Four flashes: report airflow conditions and leave the limit alone
Look at the accessible airflow path
Johnson Controls says four flashes means a primary or auxiliary limit opened. It lists a dirty filter, improperly sized ducts, incorrect blower speed, incorrect firing rate or a faulty blower motor as possible causes.
The same code description says the supply-air blower and inducer operate during this fault. A running blower therefore does not establish that the furnace is heating normally or that a limit can safely be reset.
Check accessible return grilles for objects blocking them and note closed supply registers. The manual’s owner troubleshooting checklist calls for clean filters, unobstructed returns and open registers. Report known filter condition or overdue maintenance without opening the furnace here.
Do not change blower-speed wiring, gas settings or an internal limit. Johnson Controls requires qualified cleaning of furnace surfaces and components. A return grille cleared from outside is useful information, but it does not confirm the whole cause of a limit trip.
Five flashes, steady light and the automatic reset
Use the matching label when the manual is unclear
Johnson Controls defines five flashes as gas flow with no call for heat and directs checks of the gas valve and its wiring. Do not force another heat call or keep restarting it. Arrange prompt qualified assessment, using the overheating or gas-shutoff safety instruction if that condition is present.
The same page’s code list labels steady on as normal operation. However, its preceding prose also associates a continuously lit indicator with control replacement. Those statements conflict; do not condemn a board from a steady light alone. Use the fitted control’s label and qualified diagnosis for a no-heat complaint.
The page mentions numbered sequences one through six but supplies no separate six-flash definition. Do not import one from another Coleman family. Record six flashes, confirm the model and control revision, and have service identify its applicable chart.
Johnson Controls also describes a 60-minute automatic lockout reset for specified conditions. That is control behavior, not an owner instruction to cycle power or wait through repeated unsafe operation. It does not remove the requirement to resolve an ignition, airflow or gas-control fault.
What each one takes
| Finding | Work involved |
|---|---|
| One flash | Qualified ignition and supply diagnosis |
| Two or three flashes | Switch-state, wiring and combustion-air assessment |
| Four flashes | Airflow, blower, firing-rate and limit diagnosis |
| Five flashes | Prompt gas-valve and wiring assessment |
| Rapid flashes | Qualified supply-polarity testing |
| Unclear steady or six-flash indication | Confirm fitted control and its exact documentation |
Questions people ask
Where is the Coleman DGAA/DGAH code manual?
The official Johnson Controls document listing identifies Coleman, Evcon and Guardian for manual 5165697-BUM-C-0818. Its diagnostic chart is on printed page 8.
Does three flashes mean replace the pressure switch?
No. Johnson Controls also lists the inducer, vent and hose among possible causes of the failed-to-close condition. The switch must not be bypassed or adjusted to force operation.
Does four flashes mean the filter is definitely dirty?
No. A dirty filter is one possible cause in this manual. Duct, blower-speed, firing-rate and motor conditions are also listed.
Can switching power off erase the code?
Yes. The diagnostics section says that power-off clears the fault memory. Record the pattern first for an ordinary diagnostic visit, while keeping emergency shutdown instructions first.
Does this chart cover all Coleman furnaces?
No. It follows the specified DGAA/DGAH manual. Electric furnaces, other gas series and replacement controls require their own labels and instructions.
For other systems, use the model-specific Nordyne code guide or the furnace light-pattern guide instead of transferring these meanings.
Sources: Johnson Controls Unitary Products, DGAA and DGAH Series User's Information, Maintenance and Service Manual 5165697-BUM-C-0818, revision C, August 2018, printed pages 1 to 9. Official manufacturer document lists Coleman, Evcon and Guardian. Original page 8 diagnostics visually checked; steady-on text inconsistency and undefined six-flash entry disclosed.