Daikin's DM96VC, DM80VC and DM97MC manuals use E0 for an ignition lockout. E3 needs the model: DM96VC and DM80VC include primary, auxiliary and rollout limit circuits; DM97MC lists its primary limit as E3 and rollout as Ed. Check the display before opening a door.
Daikin furnace error codes E0 and E3 point to different kinds of trouble: Daikin’s manuals use E0 for an ignition lockout, while E3 reports an open limit circuit. For E3, the model matters because the circuits included under that number change between controls.
This guide covers the controls in Daikin’s DM96VC/DC96VC, DM80VC/DC80VC and DM97MC/DC97MC installation manuals named below. A Daikin wall unit with a handheld remote belongs on the Daikin mini split error code page instead.
Before you start
What to carry: a torch, a pen and the furnace model from your paperwork or an accessible label. Keep a record of the screen before changing any setting.
Gas or electric? These are gas furnace charts. They do not describe an electric air handler, heat pump or outdoor air conditioner.
Renting? Give the model, code and heating symptoms to the person responsible for maintenance.
Daikin says that if overheating occurs or the gas supply fails to shut off, close the manual gas valve outside the furnace before turning off the electrical supply. That warning takes priority over ordinary power reset instructions.
For a gas smell, Daikin says not to light appliances, touch electrical switches or use a phone inside. Get outside, call the gas supplier and follow its directions. Call the fire department if the supplier cannot be reached.
If a carbon monoxide alarm sounds, CPSC says to get outside without searching for the source, call emergency services and count everyone to check that nobody is missing. Wait for permission to return. If an appliance caused the alarm, CPSC says not to use it until trained personnel have serviced it.
Daikin says not to bypass safety devices and reserves service work for trained personnel. That includes pressure switches, rollout switches, the gas valve and control wiring. Its manuals require electrical power to be disconnected before service or maintenance.
Read the furnace display, not just the thermostat message
Keep the exact characters and model together
Look through the viewing window if your cabinet has one. Do not remove a powered blower door to reach the control: Daikin says its door interlock interrupts voltage when that door opens and must not be defeated.
The tables here use the furnace control’s diagnostic display. Daikin’s charts have separate columns for a ComfortNet thermostat message and code. A message such as Call for Service is a prompt to identify the furnace fault, not a diagnosis by itself.
For a Goodman furnace, use the separate Goodman furnace code guide.
E0: the furnace has locked out after ignition trouble
Start with what happened before the lockout
For the named Daikin furnaces, the reset sections describe E0 after three unsuccessful ignition attempts during one call for heat. The DM97MC troubleshooting chart also includes repeated flame recycles under E0.
Daikin’s E0 checks cover interrupted gas supply, the igniter, flame sensing, piping blockages and the induced draft blower. Tell the technician about a known fuel interruption, recent service, or a furnace that lights and then loses its flame. Those observations help separate the possible causes.
Leave electrode cleaning, burner adjustment and pressure measurements to the repairer. The E0 entry does not establish that the ignition board or gas valve is bad.
E3: check which limit circuit your model includes
Daikin’s IOD-2008R and IOD-2012H charts include primary or auxiliary limit open, and rollout limit open, under E3. A dirty filter is only one possible cause in those charts.
The DM97MC/DC97MC manual IOD-2007Q separates the circuits: E3 is primary limit open, Ed is manual reset rollout open, and EF is the auxiliary input open.
Check the accessible filter, then respect the limit fault
Daikin lists blocked filters, restricted ductwork, incorrect blower speed and blower failure among E3 causes. On the DM96VC and DM80VC, it also lists rollout, burner alignment and flue problems. Do not assume every E3 can be settled by changing a filter.
For an ordinary inspection of an accessible external filter, after any overheating emergency is handled, turn the furnace power off first. Use the installed filter’s maintenance instructions and correct replacement. Put the filter and its access cover back before operation; Daikin requires filters on these furnaces.
If the open circuit has not been identified, leave the restart to the technician. The furnace limit switch guide explains the airflow side, while the rollout switch guide explains why that safety needs investigation.
The selected E code list
The following definitions come from the three Daikin installation manuals. The family column is part of the meaning, particularly for the limit circuits.
| Control display | Models covered | Daikin’s fault description |
|---|---|---|
| E0 | All three families | Ignition lockout |
| E1 | All three families | Low stage pressure switch circuit closed at the start of heating |
| E2 | All three families | Low stage pressure switch circuit not closed |
| E3 | DM96VC/DC96VC and DM80VC/DC80VC | Primary, auxiliary or rollout limit circuit open |
| E3 | DM97MC/DC97MC | Primary limit circuit open |
| E4 | DM96VC/DC96VC and DM80VC/DC80VC | Flame sensed with no call for heat |
| E4 | DM97MC/DC97MC | Flame sensed when it should not be present |
| E5 | All three families | Open fuse |
| E6 | All three families | Low flame sensing current |
| EC | DM97MC/DC97MC | Inducer motor overcurrent |
| Ed | DM97MC/DC97MC | Manual reset rollout switch open |
| EF | DM97MC/DC97MC | Auxiliary input open |
| E7 | DM97MC/DC97MC | Igniter circuit problem |
Keep pressure switch, flame and fuse faults separate
For E2 on DM96VC/DC96VC, Daikin lists pressure switch tubing, blocked flue or inlet air piping, the condensate drain, the induced draft blower, wiring and switch contacts. Report an outside blockage visible from the ground or a nearby drain leak. Do not disconnect hoses or bypass the switch.
For E4, the charts include a shorted flame sensing circuit, lingering flame and a slow closing gas valve. Keep that fault for qualified assessment before further heating attempts. It is different from E6, where Daikin describes a weak flame signal and checks sensor condition, position and combustion.
For E5, Daikin lists a short in low voltage wiring. Replacing fuses without finding that short leaves the cause unresolved. The technician’s job is to trace the circuit before selecting the repair.
How to reset an E0 lockout
In the reset sections for these three families, Daikin gives three ways: an automatic attempt after a one hour lockout, interruption of furnace power, or a thermostat cycle. These are E0 lockout instructions, not a method for clearing a gas smell or a tripped rollout safety.
For the thermostat method, Daikin says to lower the setting so there is no call for heat for 1 to 20 seconds, then restore the previous setting. Only use that ordinary reset after the fault has been assessed and the safety conditions above have been ruled out.
Daikin warns that the control will lock out again if the original condition remains. After it restarts, check whether the house reaches the thermostat setting. A recurring E0 needs the cause found, not a longer series of resets.
What each one takes
| Finding | Work involved |
|---|---|
| E0 | Supply, ignition and flame proving diagnosis |
| E2 on DM96VC | Venting, condensate, pressure switch and inducer checks |
| E3 | Identifying the open limit circuit, then airflow or combustion checks |
| E4 | Qualified flame circuit and gas valve investigation |
| E5 | Tracing a low voltage short before replacing the fuse |
| E6 | Flame sensor condition, position and combustion checks |
Questions people ask
Does E3 mean the same thing on a Daikin mini split?
No. This page uses gas furnace installation manuals. A remote control or outdoor heat pump code must be read against that equipment’s own list.
Why is the blower still running with E3?
Daikin’s E3 rows describe the circulator blower running continuously while the furnace is not heating. That fits the reported fault; it does not establish which limit opened.
Is On an error code?
Daikin marks On as normal operation in these charts. If the furnace shows that status but does not warm the house, use the furnace not working checks rather than treating On as a failed component.
Can the furnace still run with E6?
Daikin’s E6 rows describe normal furnace operation alongside a low flame signal. Give that code to the repairer even if heat is still reaching the rooms.
Does DM97MC E7 always mean a broken igniter?
No. Daikin’s IOD-2007Q chart also lists igniter connections, poor grounding and an igniter relay fault on the control module. The technician needs to check the circuit before choosing a part.
The other furnace guides: furnace pressure switch, furnace flame sensor, and Goodman furnace error codes.
Sources: Daikin DM96VC/DC96VC Installation Instructions IOD-2008R, June 2023, pp. 1 to 3, 25, 35, 48 to 49, 51 to 52; DM80VC/DC80VC Installation Instructions IOD-2012H, June 2023, pp. 1 to 3, 12, 31 to 32, 34 to 35; DM97MC/DC97MC Installation Instructions IOD-2007Q, August 2024, pp. 1 to 3, 27, 48 to 49, 51 to 52; CPSC Carbon Monoxide Questions and Answers.