Daikin Mini Split Error Codes: U4, A5, U0 and the Rest

Ray BennettBy Ray Bennett · Updated 2 October 2026 · 7 min read · Checked against the maker’s manual
Daikin Mini Split Error Codes: U4, A5, U0 and the Rest
Short answer

A Daikin wall unit blinks its operation lamp when it stops on a fault, and the remote reads the code: hold the timer Cancel button until 00 blinks, then press until a long beep. U4 means the indoor and outdoor units are not talking, A5 is often a clogged filter, U0 is a refrigerant shortage, and E7 is the outdoor fan.

A Daikin wall unit does not show its fault code on the front. It stops and blinks its operation lamp, and the code is read with the remote, which beeps when it lands on the right one. It takes a minute once you know the button.

Everything on this page comes from Daikin Industries’ own documents: its “Simple Self-Diagnosis by Malfunction Code” list and “How to Check Error Codes” guide from the after sales service division, and Daikin’s operation manual for its residential wall units. The meanings and likely causes are Daikin’s.

Before you start

What to carry: the remote, a torch and a pen. Ten minutes.

Gas or electric? A mini split is all electric, a heat pump that heats and cools.

Check the remote’s model. It is printed on the remote, starting with ARC. Most Daikin wall remotes use the timer Cancel method below, and a few use a three button method.

Give it three minutes first. Daikin says the unit restarts by itself about 3 minutes after a power cut, and may stop for the same time after a big voltage swing.

Two things Daikin says before any repair. Breaker off for anything more than the remote. Daikin says to stop the unit and turn off the circuit breaker if there is a burning smell, abnormal noise, water leaking from the indoor unit or a breaker that trips often, and to call your dealer.

Do not attempt the repair yourself. Daikin’s manual warns that incorrect work can cause electric shock or fire. The checks on this page stop at things an owner can see and clear.

What the operation lamp is telling you

WHAT THE OPERATION LAMP IS DOING Blinking Will not start breaker off, then start again with the remote Blinking Stopped while running clear anything blocking the vents, in or out Lit steady Stopped while running voltage protection; it restarts in about 3 minutes Still blinking after that? Read the code with the remote before calling.
Daikin's own first steps depend on whether the lamp is blinking or lit, and whether the unit would not start or stopped while running.
Check 1Free, ten minutes

Do Daikin's first step for your lamp

Blinking and the unit will not start. Daikin says to turn off the power at the circuit breaker, then restart with the remote. If the lamp is still blinking, read the code and call your dealer.

It stopped while running and the lamp is blinking. Daikin asks whether anything is blocking the air inlet or outlet of the indoor or outdoor unit. Stop it, switch off the breaker, remove the obstruction and restart.

It stopped while running and the lamp is lit. Daikin says the unit may stop after a sudden large voltage swing to protect itself, and restarts in about 3 minutes.

The outdoor fan runs after you switch off. Normal. Daikin says it keeps turning for about a minute to protect the system.

Reading the code with the remote

THE REMOTE FINDS THE CODE, THE BEEP CONFIRMS IT Step 1 Aim the remote at the indoor unit, close enough to hear Step 2 Hold Cancel the timer Cancel key, 5 seconds: 00 blinks Step 3 Press, press next code each time; a short beep: not it Step 4 A long beep the code on the screen is the fault; write it 00 with a long beep means no fault. Hold Cancel 5 seconds again to leave.
Hold the timer Cancel button until 00 blinks, then keep pressing it. The code on the screen when the unit gives a long beep is the fault.
Check 2Free, five minutes

Find the code

Hold the timer Cancel button for 5 seconds, with the remote pointed at the indoor unit. Daikin says 00 blinks in the temperature display.

Press the timer Cancel button again and again. Each press shows the next code. A short beep means it is not that one. A long beep means the code on the screen is the fault.

00 with a long beep means no fault is stored. To leave, hold the Cancel button for 5 seconds again, or leave the remote alone for a minute.

The three button remotes. Daikin says some ARC433B remotes enter the check by pressing TEMP up, TEMP down and MODE together. The ten’s figure blinks, and you step it with TEMP until the beeps say it is right: two short beeps for the first figure, a long beep for both.

The ARC447A remote. Daikin says holding its timer Cancel button for 5 seconds takes the display straight to the code, with a long beep.

What each code means

These are the codes Daikin lists for its residential units, from its operation manual and its service list, with the likely causes from the service list.

Code What Daikin says it means Likely causes Daikin lists
00 Normal No fault stored
U0 Refrigerant shortage A shortage, or a blockage in the piping
U2 Voltage drop or main circuit overvoltage Supply voltage, a brief power cut
U4 Indoor and outdoor units not communicating Wiring, outdoor unit power off, a board
UA Indoor and outdoor units do not match Wrong model or board connected
A1 Indoor control board The board, or electrical noise
A3 Drain level control A clogged drain, an uphill drain, the pump
A5 High pressure control in heating, freeze-up protection in cooling A clogged indoor filter, blocked airflow
A6 Indoor fan motor The motor, its wiring, the board
C4 Indoor coil temperature sensor The sensor or its plug
C9 Room air temperature sensor The sensor or its plug
CC Humidity sensor The sensor or its plug
E1 Outdoor control board The board or the wiring between units
E3 High pressure switch tripped A dirty outdoor coil, the switch
E5 Compressor overload A locked compressor, high pressure
E6 Compressor failed to start The compressor, a stop valve not opened
E7 Outdoor fan motor Something caught in the fan, the motor
E8 Compressor overcurrent The compressor or the outdoor board
EA Cooling and heating switching error The four way valve, a gas shortage
F3 Discharge pipe too hot The pipe temperature or its sensor
F6 High pressure control in cooling Too much refrigerant, a sensor unplugged
F8 Stopped on compressor internal temperature Technician
H0 Compressor sensor system A loose harness, the board
H6 Compressor position detection The compressor cable or the compressor
H8 Compressor current sensor The inverter wiring or the board
H9 Outdoor air temperature sensor The sensor or its plug
J3 Discharge pipe temperature sensor The sensor or its plug
J6 Outdoor coil temperature sensor The sensor or its plug
J8 Liquid pipe temperature sensor The sensor or its plug
L3 Electrical parts overheating Hot air short circuiting, the outdoor fan
L4 Inverter heatsink too hot Hot air short circuiting, the fin sensor
L5 Output overcurrent The compressor or the inverter board
P4 Inverter heatsink temperature sensor The sensor or the inverter board

The checks that are yours

Check 3Free, twenty minutes

Work the owner checks, breaker off first

A5: the filters. Daikin’s first listed cause is a clogged indoor filter. Wash the filters, and make sure nothing sits in front of the unit where its air could loop straight back in: how to wash mini split filters.

U4: the outdoor unit’s power. Daikin lists the outdoor unit’s power supply being off. Check its breaker and the disconnect switch beside it.

E7: the outdoor fan. Daikin lists a fan that cannot turn because something is caught in it. With the breaker off, look for sticks, leaves or ice.

E3, L3 and L4: the outdoor unit’s air. Daikin names a dirty outdoor coil and hot air short circuiting, meaning the unit breathes its own exhaust. Clear space around it and rinse the coil: how to rinse an outdoor coil without bending the fins.

A3: the drain. Daikin lists a clogged drain and an upward slope. The drain hose must run downhill all the way: where a mini split’s water goes and how it backs up.

U2: the power. A voltage drop or a brief power cut. Switch off at the breaker, restore and restart.

When it needs a technician

Check 4

Know when to stop

U0. A refrigerant shortage means a leak somewhere, or a blockage. Sealed system work for a licensed technician: signs the refrigerant is leaking.

E6 on a new install. Daikin lists a stop valve that was never opened. That is the installer’s job to put right.

F6 after a recharge. Daikin’s first listed cause is too much refrigerant. Tell whoever last added gas.

E5, E8, H6, L5 and EA. The compressor, its drive or the four way valve. Technician work.

The sensor and board codes. C4, C9, CC, H9, J3, J6, J8, P4, A1 and E1 are a sensor, its plug or a board. Give the technician the code you read with the remote.

Questions people ask

What does U4 mean on a Daikin mini split?

The indoor and outdoor units are not communicating. Daikin lists wiring faults, the outdoor unit’s power being off, and a faulty board. Check the outdoor unit has power, then call a technician if the code returns.

What does A5 mean on a Daikin?

High pressure control in heating or freeze-up protection in cooling. Daikin’s first listed cause is a clogged indoor filter, so wash the filters first.

What does U0 mean?

A refrigerant shortage. Daikin lists a shortage or a blockage in the piping. A reset will not fix it, and it needs a technician.

How do I check the error code on a Daikin?

Point the remote at the unit and hold the timer Cancel button for 5 seconds until 00 blinks. Keep pressing it, and the code showing at the long beep is the fault.

What does 00 mean on the Daikin remote?

No fault. It is the first code the check shows, and a long beep on 00 means nothing is stored.

Why is my Daikin blinking but working again after a reset?

Daikin says lightning or radio waves can make the unit malfunction, and a restart from the breaker can clear it. If the lamp blinks again, read the code before you call.

Sources: Daikin Industries "Simple Self-Diagnosis by Malfunction Code" and "How to Check Error Codes" (SM-TS3), and Daikin's operation manual for residential wall units