Lennox Mini Split Error Codes: E1, EL 01, FP and dF

Lennox Mini Split Error Codes: E1, EL 01, FP and dF
Short answer

Lennox mini split indoor units show a code in place of the set temperature. dF, FP, CL, nF, CP and FC are status codes, not faults; dF is defrost. Lennox's user guide says to press ON/OFF twice, switch the power off and on at the disconnect if the code is still there, and call a licensed technician if it comes back.

Lennox mini split error codes appear on the indoor unit’s display, and Lennox’s user guide says the code replaces the set temperature there. If more than one fault has happened, the codes take turns so you see them all.

Not every code is a fault. Lennox’s own table marks dF, FP, CL, nF, CP and FC as status codes, and dF is simply defrost. Everything below comes from Lennox’s mini split user guide, its two mini split service manuals and its wired controller instructions.

Before you start

What to carry: a torch, the remote, a pen, and paper to write the code down. Only the filter check opens anything, the return air grille or front panel, and the reset Lennox gives takes no tools.

Gas or electric? Electric. A Lennox mini split is a ductless or ducted heat pump. The user guide covers the M22A and M33C ceiling cassettes, the MWMC and 3WMC wall units, the MCFA and MCFB ceiling or floor units, the MFMA floor console and the MMDB ducted unit.

Which code style do you have? The model is on the indoor unit’s label. Lennox’s table puts the M22A, MMDB, MCFA, MCFB and MFMA on short codes such as E1, and the M33C, MWMC and 3WMC on long codes such as EL 01.

Renting? Send the code, the model on the indoor unit’s label and what the system was doing to whoever arranges repairs.

When Lennox says to switch it off and call.
Turn the indoor and outdoor units off at the unit disconnect switch and call a licensed technician if water is leaking into the room from the indoor unit, or water or another liquid has been spilled on or splashed into it. Lennox’s user guide says the same if the breaker trips or the fuse blows frequently, if the system gets no signal from the remote or wired controller, or if either one indicates a system malfunction. Its error code section gives the reset in check 5 for a code on the display.

Hands and water out. Lennox warns never to spray water on the indoor unit, never to touch the unit or the controller with wet hands, and never to put hands, tools or anything else into the air intake or outlet of either unit. Do not remove the outdoor unit’s fan guard for any reason.

Power off first. Before any maintenance, even a filter clean, Lennox says power to the unit must be off at the unit disconnect switch.

Status or error

Lennox’s code table has a type column, and it splits the codes into two kinds. The status codes are the system telling you what it is doing.

Status code What Lennox’s table says
dF Defrost
FP Heating in room temperature under 8°C (46.4°F)
CL Filter cleaning reminder (shown for 15 seconds at power on), or active clean
nF Filter replacement reminder (shown for 15 seconds at power on)
CP Remote switched off
FC Forced cooling

The user guide adds one more. On units with Lennox’s wireless remote, pressing self clean in cooling or dry mode shows SC on the indoor unit while it dries the coil, and then the unit turns off.

Every other code in the table is typed as an error, including the two dashes, —, which Lennox lists as a mode conflict for multi-zone systems.

One fault, three names

The same fault shows differently depending on where you read it. Lennox’s user guide lists three columns: the short code indoor units, the long code indoor units, and its programmable wired controller, which it calls optional on most Lennox indoor units.

ONE LENNOX FAULT, THREE NAMES A Short code M22A, MMDB, MCFA, MCFB, MFMA B Long code M33C, MWMC, 3WMC C Controller programmable, wired, optional Communication indoor to outdoor E1 EL 01 E1 Indoor fan speed error (DC motor) E3 EH 03 E8 Indoor coil sensor error (T2) E5 EH 61 E3 Leak detection cooling mode only EC EL 0C EF E3 on an M22A is the fan speed error; E3 on the controller is the coil sensor.
Lennox shows one fault three ways. E3 on an M22A is the indoor fan speed error, but E3 on Lennox's programmable wired controller is the indoor coil sensor. Read the code where it appears and match it to that column.

That matters most for E3. On an M22A it is the indoor fan speed error, but on the programmable wired controller E3 is the indoor coil temperature sensor error. Selected rows from Lennox’s table:

Short code (M22A and others) Long code (M33C, MWMC, 3WMC) Wired controller What Lennox’s table says
E0 EH 00 E7 Indoor unit EEPROM error
E1 EL 01 E1 Communication error between the indoor and outdoor units
E3 EH 03 E8 Indoor fan speed error (DC motor)
E4 EH 60 E2 Indoor room temperature sensor error (T1)
E5 EH 61 E3 Indoor coil temperature sensor error (T2)
EC EL 0C EF Refrigerant leakage detection (cooling mode only)
EE EE High water level alarm
F0 PC 08 EA Outdoor current overload protection
F1 / F2 / F3 EC 53 / EC 52 / EC 54 E5 Outdoor ambient, outdoor coil and compressor discharge sensor errors
F5 EC 07 Ed Outdoor unit fan speed error (DC fan motor)
P0 PC 00 Inverter module IPM error
P1 PC 01 High or low voltage protection
P3 PC 0L Outdoor low ambient temperature protection
P6 PC 03 High pressure switch open, or low pressure switch open
P7 EF Outdoor IGBT temperature sensor error

On the wired controller, EF appears twice in that table, for refrigerant leakage detection and for the IGBT sensor, and E5 covers three outdoor sensors. It also has codes of its own: F0 there is a communication error between the wired controller and the indoor unit, and F1 means the cassette panel is abnormal. Give the technician the indoor unit’s code as well if it shows one.

What you can check

Check 1Free, nothing to open

Write the whole code down, and whether it is a status

Write down exactly what the display shows and which column of the tables above it belongs to. If it is dF, FP, CL, nF, CP, FC or SC, it is a status, not a fault, and the checks below cover the ones you can act on.

If two codes alternate, write both. Lennox’s user guide says the display takes turns when more than one error has happened.

Check 2Free; no repair

With dF in winter, let the defrost finish

dF is Lennox’s defrost status. Lennox’s 2024 service manual says the outdoor unit leaves defrost when its coil warms up, or after 10 minutes of defrost at most, and goes back to heating.

The user guide lists what comes with it as normal. When the system switches from defrost back to heating, moisture from the defrost becomes steam and may be seen blowing out of the indoor unit. On a new call for heat, the indoor fan waits until the indoor coil warms up, so it does not blow cold air, and the PRE-DEF light may be lit on units that have one.

Check 3Free, a few button presses

With -- on a multi-zone system, put every room in the same mode

Lennox lists the two dashes as a mode conflict for multi-zone systems. Its instructions for the M0STAT61Q-1 wired controller say Auto mode is not recommended for multi-zone units, and that all zones should be in the same mode so there is no conflict error.

In winter, set every indoor unit on that outdoor unit to HEAT. The same instructions say to allow at least one minute between mode changes so the system can settle.

Check 4Free, with the power off

With CL or nF, clean the filter

CL at power on and nF are Lennox’s filter reminders; CL also shows during active clean. Switch the power off at the unit disconnect switch first, then open the return air grille or front panel and lift the filter out; the user guide shows where it sits on each indoor unit.

Lennox says the filter can be cleaned with a vacuum cleaner, air entering side up, or with clean water, air entering side down. Let it air dry, never in direct sunlight or with any heat. If it cannot be cleaned, replace it with one of like kind and size. Lennox says to check the filters monthly, and that more often may be needed in a dusty room.

Check 5Free, nothing to open

With an error code, do the reset Lennox gives, once

Lennox’s user guide gives the owner one reset for an error code:

  1. Press ON/OFF on the wireless remote to reset the display.
  2. Press ON/OFF a second time to put power back to the system.
  3. If the code is still there, switch the power off and back on at the unit disconnect switch or the circuit breaker.
  4. If the code comes back after that, call a licensed professional HVAC service technician.

Lennox says a temporary problem will not reappear after that power reset. A code that keeps coming back is the call to make, not a reason to keep cycling the power.

THE RESET LENNOX GIVES FOR AN ERROR CODE

A Press ON/OFF on the wireless remote this resets the display ON/OFF

B Press ON/OFF a second time this puts power back to the system ON/OFF

C Code still showing? Power off, then on at the unit disconnect switch or the circuit breaker

D Code comes back? Call a technician a licensed professional HVAC service technician E1

Lennox says a temporary problem will not reappear after the power reset.

The reset Lennox's user guide gives for an error code: ON/OFF on the wireless remote twice, then off and on at the disconnect or breaker if the code is still there, then a licensed technician if it comes back.

Check 6Free to look; a service call if it stays

With P3 or PC 0L on the indoor unit, note the weather and keep the outdoor unit clear

Lennox’s table lists P3 and PC 0L as outdoor low ambient temperature protection. Write down how cold it was outside when it appeared, for the technician.

Lennox says not to block the air intake or outlet of either unit and not to store items on top of the outdoor unit. Look at it from a short distance. Do not reach into the intake or outlet, and leave the fan guard on.

The outdoor unit’s own display

Some Lennox outdoor units show codes too. Lennox’s 4/2022 service manual gives outdoor code tables for the 3PC single zone units and the MPC036, MPC048, MLB036 and MLB048 single zone units and notes that smaller single zone outdoor units have no display. On every MLB and MPC multi-zone unit, it says the display is on the main control board, so a technician reads it.

Selected rows from its outdoor tables, which use long codes. Do not read an outdoor short code against the indoor table: its outdoor reference pairs P3 with PC 08, current overload.

Outdoor code What Lennox’s table says
EL01 Communication malfunction between indoor and outdoor units
FL14 Capability mismatch between indoor unit and outdoor unit
EC07 Outdoor DC fan motor malfunction, fan speed out of control
PC00 Inverter module (IPM) protection
PC08 Outdoor over current protection
PC0L Low temperature protection of outdoor unit
PC10 Outdoor unit low AC voltage protection
PC30 / PC31 System high pressure / low pressure protection
PC40 Communication error between outdoor main chip and compressor driven chip
PH90 / PH91 High / low temperature protection of evaporator

For E1 and EL 01, the service manual says the indoor unit shows the code when it has had no reply from the outdoor unit for 110 seconds, four times in a row. Its listed causes are a wiring error or a fault in the indoor or outdoor main control board.

What each one takes

What you see What the work involves
dF, steam after it, or a fan that waits on heat Nothing; Lennox lists these as normal
CL at power on, or nF Power off, then a filter clean or a like for like filter
— on a multi-zone system Every room set to the same mode
An error that clears after the reset Nothing more unless it returns
An error that comes back A licensed technician, with the code and the model
EC or EL 0C, refrigerant leakage detection A licensed technician for the refrigerant circuit

Questions people ask

What does E1 mean on a Lennox mini split?

Lennox’s table lists E1 as a communication error between the indoor unit and the outdoor units. The M33C, MWMC and 3WMC show the same fault as EL 01, and the programmable wired controller shows E1.

What does dF mean on a Lennox mini split?

Defrost. Lennox marks it as a status code, not an error. Its 2024 service manual says defrost ends when the outdoor coil has warmed, or after 10 minutes at most.

What does FP mean on a Lennox mini split?

Lennox’s table lists FP as a status code: heating in room temperature under 8°C (46.4°F). It is not on the error list.

How do I reset a Lennox mini split error code?

Lennox’s user guide says to press ON/OFF on the wireless remote, press it again to put power back to the system, and if the code is still there, switch the power off and on at the disconnect switch or breaker. If the code comes back, call a licensed technician.

Why does my wired controller show a different code from the indoor unit?

Lennox’s programmable wired controller uses its own codes. E3 there is the indoor coil sensor, while E3 on an M22A display is the indoor fan speed error, so always say where you read the code.

The other mini split guides: mini split error codes, mini split not heating and mini split won’t turn on. For a central Lennox heat pump, see Lennox heat pump error codes.

Sources: Lennox mini split indoor units user guide 507550-06 (7/2021), Lennox mini split service manual 100030 (4/2022, error codes) and 100029 (04/2024), Lennox wired controller M0STAT61Q-1 instructions 507561-04