On the Lennox XP25 control covered here, 411 is a low pressure lockout, 413 is a high pressure lockout, and 434 is lost communication with the inverter. Match the outdoor model before using the table. A code identifies the fault to investigate, not a part to buy.
Lennox heat pump error codes make more sense when you know which outdoor unit sent them. In Lennox’s XP25 service manual, 411 and 413 are pressure lockouts, while 434 points to communication between the outdoor control and the inverter.
This guide covers the XP25 with the iComfort Wi-Fi control described in that manual. If you have an XP21, SL25XPV or another model, use its own code table. The number on the thermostat is only half of the information you need.
Before you start
What to carry: a torch, your phone and something to write on. You are collecting the fault information, not opening the outdoor electrical compartment.
Gas or electric? This page concerns the electric outdoor heat pump. A gas furnace serving the same house has a separate control: use Lennox furnace error codes for that equipment.
Renting? Send the fault details to the person responsible for arranging repairs before buying parts or booking work yourself.
Lennox assigns installation and service to a qualified installer or service agency. Keep hands and tools away from the fan, wiring and refrigerant connections. An idle fan is not permission to reach inside.
Match the outdoor unit to the alert
Save the model and the complete message
Photograph the outdoor model label where it is safely accessible, then record the alert number, its wording and whether the system was heating or cooling. Include whether the house still has heat and whether the fault returned after earlier service.
Lennox says XP25 alerts appear on the outdoor control’s seven segment display and on the iComfort Wi-Fi thermostat. Use the indoor message rather than removing a panel to hunt for another display.
For screen priorities, maintenance reminders or indoor equipment messages, go to Lennox thermostat alert codes. The table below follows the outdoor XP25 control.
The XP25 pressure codes: 410 through 413
Lennox’s table 6 distinguishes a pressure switch opening from a lockout after repeated openings. That distinction matters when describing the problem to the service company.
| XP25 code | Meaning in Lennox table 6 | What to report |
|---|---|---|
| E410 | Low pressure switch opened; outdoor unit cycled off | A low pressure trip |
| E411 | Low pressure switch opened five times within one hour; outdoor unit locked out | A repeated low pressure fault |
| E412 | High pressure switch opened | A high pressure trip |
| E413 | High pressure switch opened five times within one hour; outdoor unit locked out | A repeated high pressure fault |
For 411, include the indoor airflow condition
Lennox’s XP25 E411 troubleshooting row includes dirty filters, an obstructed indoor blower, a clogged refrigerant metering valve and refrigerant charge checks. It also calls for checking that the evaporator coil is clean.
If you already know the condition of the household filter, include it in the report. Leave coil access, refrigerant measurements and blower testing to the service visit. A low pressure alert alone is not a sound reason to order refrigerant or a replacement switch.
For 413 in heating, mention the operating mode
Lennox specifically says indoor airflow, or zone airflow on a zoned system, may be set too low for heating under its E412 and E413 entries. This gives the technician an indoor check to make even though the outdoor unit reports the code.
The XP25 E413 row also includes the outdoor fan, refrigerant charge, the reversing valve, restrictions and outdoor unit cleanliness. From outside the cabinet, describe any visible buildup or obstruction without trying to remove a guard.
When the complaint is poor warmth without an alert, heat pump not heating follows the symptom instead.
Code 434 and the inverter faults
Treat 434 as an outdoor communication problem
Lennox describes XP25 E434 as the outdoor control losing communication with the inverter for more than three minutes. In its table 6, the paired inverter code is 53, shown as five red flashes and three green flashes.
Those flashes belong to the inverter inside the outdoor equipment. They are not a flashing thermostat light or a furnace blink sequence.
Lennox’s table 6 tells the technician to check electrical connections and the inverter’s main power supply.
Nearby entries in Lennox’s table 6 describe E435 as an internal inverter error and E436 as inverter heat sink temperature exceeding its limit. These entries call for electrical or inverter checks, not changes to the room temperature setting.
What happens after the code clears?
Lennox says the XP25 continues monitoring after an alert and can turn the alert off when conditions return to normal. Its E411 and E413 rows specify a power reset to clear those lockouts. Lennox says its manual reset procedure clears the codes currently on display.
That makes the original fault record useful even if the screen is clear when the technician arrives. Ask which condition caused the shutdown and what was checked before the system was returned to service.
What each one takes
| Task | What it involves |
|---|---|
| Identify the unit and message | No parts; an exterior label and the indoor alert screen |
| Investigate E411 | A service visit to separate airflow, refrigerant and restriction problems |
| Investigate E413 | A service visit that includes the heating airflow settings where applicable |
| Investigate E434 | Electrical and control diagnosis inside the outdoor equipment |
| Replace a component | A part only after the fault has been traced; the code is the starting point |
Questions people ask
Where is the Lennox heat pump error codes PDF?
The source used here is Lennox’s XP25 installation and service manual. Start with table 6 on printed page 30. The document also contains later troubleshooting tables, so keep the control context with the code.
Does 413 mean I need a new pressure switch?
No part is identified as the confirmed failure by that number. Lennox’s XP25 E413 entry directs the technician to check several conditions, including airflow, refrigerant charge and fan operation.
Is 434 a thermostat Wi-Fi problem?
In this XP25 manual, Lennox uses 434 for communication between the outdoor control and inverter. It is not described as the thermostat losing its home internet connection.
Why does the outdoor display show a fault instead of heating status?
Lennox says faults and lockouts take priority over normal XP25 status displays. Only the latest active fault or lockout is displayed when one is present.
Can I use this chart for every Lennox heat pump?
Keep this chart with the XP25 manual named above. A different outdoor model or control needs its corresponding literature, even when the thermostat looks the same.
The other Lennox and heat pump guides: thermostat alerts, furnace codes and heat pump not heating.
Sources: Lennox XP25 Installation and Service Procedure, Corp. 1252-L11, revised December 14, 2016, tables 6 and 21 and electrical safety warnings.