American Standard Furnace Error Codes: 2 to 8 Flashes

American Standard Furnace Error Codes: 2 to 8 Flashes
Short answer

On the American Standard AUE1 and ADE1 models in guide 18-CD19D4-26, two flashes mean ignition lockout, three mean a draft pressure fault and four mean an open temperature limit circuit. A steady fast blink is a normal heat call. Match the model before using this chart.

American Standard furnace error codes can be easy to misread when a normal fast blink looks like a warning. For the AUE1 and ADE1 furnaces in installation guide 18-CD19D4-26, slow and fast blinking are normal signals; counted flashes identify faults.

This page covers that guide’s AUE1 and ADE1 models, including AUE1A060A9361A and ADE1B080A9451A. It does not assign their flash counts to the S9V2 or S9X2. Our Trane furnace code guide covers the separate E-code display used by the named models there.

Before you start

What to carry: a torch, your phone and the furnace paperwork. You are identifying the signal, not opening the control compartment to test it.

Gas or electric? The AUE1 and ADE1 guide is for gas furnaces. An electric air handler needs its own fault list. For the 4A6H6018H1000A outdoor unit, use the American Standard heat pump flash-code guide.

Match the model. Compare the model on your paperwork or accessible rating label with the list on the manual’s first page. Its asterisk allows either an A or T prefix. Use this page for the listed American Standard A-prefix models only.

Renting? Send the fault information to the landlord or maintenance contact and let them arrange access and repairs.

Gas smell and overheating come before the light.
The AUE1/ADE1 manual says that if you smell gas, do not operate electrical switches, use a phone inside the building or try to light an appliance. Leave the building and immediately call the gas supplier from a neighbor’s phone. Follow the supplier’s instructions. Call the fire department if you cannot reach the supplier.

For overheating, or gas that fails to shut off, the manual requires shutting off the gas valve before the electrical supply. Do that only if you can reach the shutoff safely; otherwise leave and get emergency help.

For electrical, fuel or mechanical failures, the guide tells the owner to shut off the gas supply and electrical power, then contact the service agency. Use an accessible shutoff; do not open the furnace to reach one.

The same guide requires power off before removing the blower door or servicing filters. It warns that running with a door open can release dangerous fumes, so all panels must be securely closed for operation.

Read the pattern before choosing a fault

READ THE RHYTHM FIRSTAASlow blinkingNormal status:no request for heat.BBFast blinkingNormal status:heat is requested.CgapCA counted group: threeDraft pressure fault.Use the model-specific fault chart.AUE1 / ADE1 only. Source: installer guide 18-CD19D4-26.
The AUE1/ADE1 guide separates normal slow or fast blinking from counted fault flashes. The dots show a pattern, not a measured timing scale.
Check 1Observation only, no parts or service visit needed to record the signal

Separate a steady rhythm from a counted group

The manual calls slow flashing normal when there is no request for heat, and fast flashing normal when heat is requested. Fast blinking alone is not the two-flash lockout code.

Record a repeating group as a count, along with whether the burners ever light and whether the room blower runs. A short video is useful if the pattern is hard to describe. If the light cannot be seen with the panels closed, leave access to the service technician.

In this guide, a continuously dark indicator directs the technician to check power. A continuously lit indicator directs them to replace the integrated furnace control, called the IFC. Do not buy a board just because an unfamiliar light appears steady.

The AUE1 and ADE1 flash table

These are the meanings in the manufacturer’s 18-CD19D4-26 table on page 21. The action column separates an observation you can report from work inside the furnace.

Flash count Meaning on these AUE1/ADE1 controls Next step
2 Ignition attempts or flame recycles have reached the lockout limit Report whether flame appeared before it stopped
3 Draft pressure fault; possible vent, pressure switch or inducer trouble Arrange a check of the complete draft system
4 Temperature limit circuit is open Follow the filter and limit guidance below
5 The control senses flame when none should be present Leave diagnosis to the service agency
6 Reversed supply polarity, inadequate grounding or low supply voltage Electrical measurements are needed
7 Gas valve circuit fault Gas valve and control diagnosis
8 Weak flame sensing signal Have the flame signal investigated

What two, three and four flashes lead to

Check 2A service diagnosis; parts depend on the fault found

Two flashes: describe the failed heating attempt

The manual groups retries and recycles under two flashes. That is why the useful detail is whether you saw ignition at all, or saw flame that later disappeared.

Its operating section says that after flame is lost during heating, the control retries ignition up to twice after the sensor cools. If ignition is not achieved, it locks out. The two-flash label itself does not identify a failed igniter, gas valve or sensor.

This page does not prescribe a reset sequence for a different American Standard control.

Check 3A draft system inspection, with repair time decided after testing

Three flashes: keep the vent and switch together

The manufacturer’s three-flash row names three possible areas: venting, the pressure switch and the inducer. The inducer is the small fan that establishes draft through the furnace.

The guide explains that when the pressure switch does not sense pressure, the gas valve cannot open. If that failure happens during a heating cycle, the valve closes and the unit stops. A switch code therefore does not establish that the switch itself needs replacing.

The furnace pressure switch guide explains the parts involved. Leave hose removal, switch testing and vent disassembly to the service visit.

Check 4Filter maintenance if due; a service visit for a continuing limit fault

Four flashes: attend to the filter, then the limit circuit

For these models, the manual describes the temperature limit as a safety device that closes the gas valve when the furnace overheats. It assigns the limit’s operating test to the installer.

If the furnace has cooled and there is no gas smell or emergency condition, an overdue filter is something you can address using the shutdown rule above. The manual calls for cleaning or replacing filters monthly, and more frequently during heavy use, using its specified filter type.

Use the correct filter for the installation and secure any access cover afterward. If the fault remains, the technician needs to examine the limit circuit and airflow. Do not imitate the manual’s installer test, which deliberately restricts airflow.

A CODE NAMES THE TEST AREAAAThree flashes: draftVent, switch or inducer.The switch is not the only possibility.BBFour flashes: temperature limitAn open safety circuit.Filter care and airflow investigation.CCEight flashes: flame signalA weak sensing signal.Diagnosis comes before a new part.AUE1 / ADE1 only. Source: installer guide 18-CD19D4-26.
For the AUE1/ADE1 table, three flashes have several possible draft causes. Four flashes identify a safety circuit, while eight identify a weak flame signal.

What each one takes

The manufacturer’s service section assigns installation and service to qualified personnel. The table below describes the scope of the next step; it is not a price or a promised repair time.

Task What it involves
Identify the model and blinking pattern Paperwork and an observation from outside the closed cabinet
Routine filter maintenance The specified filter or cleaning method, with power isolated
Investigate ignition, draft or a continuing limit fault A service visit; the cause determines whether parts are needed
Diagnose five, six or seven flashes, or a steady indicator Control, gas or electrical testing by qualified personnel
Investigate eight flashes Flame signal diagnosis before deciding on a repair

Questions people ask

Where is the American Standard error code PDF?

The source for this table is installer’s guide 18-CD19D4-26, page 21. The model list is on page 1. Compare the full model number before treating its chart as yours.

Does eight flashes tell me to replace the flame sensor?

The AUE1/ADE1 chart reports a weak flame signal, rather than specifying a replacement part. Ask for the signal to be diagnosed before ordering a sensor.

Is the rollout device the same as the normal temperature limit?

The manual describes a separate thermal device on the burner cover that interrupts gas flow if flame rolls out. Its limit check is a separate procedure. The rollout switch guide explains why a tripped safety needs investigation.

Can I use this table for an E04 display?

No. This table is for the listed AUE1/ADE1 flash controls. An E04 display belongs with the documentation for the furnace and control displaying it.

What happens after a power cut?

The AUE1/ADE1 operating guide says the ignition sequence restarts when power returns if the thermostat still requests heat. That describes recovery from lost power, not proof that an existing fault has been repaired.

The other furnace guides: counting a furnace light, furnace limit switches and flame sensing.

Sources: Trane / American Standard Installer's Guide 18-CD19D4-26, AUE1 and ADE1 gas furnaces, pages 1, 11, 20, 21 and 22; https://fergusonprod.a.bigcontent.io/v1/static/2887427_1786940_installation