American Standard's 4A6H6018H1000A service chart uses one and two flashes for outdoor sensor faults, three for an open low pressure switch, four for hard lockout and five for soft lockout. Six through nine cover defrost and low outdoor temperature conditions. Match this outdoor model before using the counts.
American Standard heat pump error codes can be counted flashes on the outdoor defrost control, rather than a number on the thermostat. For model 4A6H6018H1000A, American Standard’s service chart gives one through nine flashes specific meanings.
This guide follows Service Facts 4A6H6018H-SF-1C-EN, dated August 2016. The document prints the American Standard name and lists that outdoor model on its cover. Its chart is different from the communicating control covered in our Trane heat pump alert guide.
Before you start
What to carry: the outdoor model information, a torch and something to record the message. If a technician has already reported a flash count, keep their description of which board showed it.
Which equipment? This page covers the outdoor heat pump in the named Service Facts. An indoor gas furnace has a different control, even when both cabinets carry the same brand. Use the American Standard furnace code guide for the furnace models listed there.
Renting? Give the maintenance contact the outdoor model and whether heating, cooling or both have stopped. Leave cabinet access to the service visit.
American Standard restricts installation and service to qualified personnel. Its safety section requires all electrical supplies, including remote disconnects, isolated before service, with lockout procedures to prevent accidental reconnection.
The same document warns about the hot compressor top and refrigerant under pressure. Stay outside the closed unit. If its indicator cannot be read without opening the cabinet, let the technician retrieve the code.
Do not use the board’s service tests or bridge a pressure switch to make the system run. This guide explains the reports so you can understand the service findings.
The 4A6H6018H1000A flash chart
The following meanings come from Table 3 on page 9 of American Standard’s Service Facts. Seven and eight flashes include checks of sensor placement and the switchover valve, abbreviated SOV in the chart.
| Flashes | Meaning on this outdoor control | What the report directs attention to |
|---|---|---|
| 1 | Ambient temperature sensor outside its range, open or shorted | Outdoor air sensor circuit |
| 2 | Coil temperature sensor outside its range, open or shorted | Outdoor coil sensor circuit |
| 3 | Low pressure switch open | Pressure protection and switch status |
| 4 | Hard lockout after the fourth low pressure cutout trip | The repeated trips that led to the stop |
| 5 | Soft lockout | The current protection delay |
| 6 | Defrost cycles too close together | Heating short-cycle fault and lockout sequence |
| 7 | Timed defrost mode | Ambient sensor placement and switchover valve operation |
| 8 | Timed defrost mode | Coil sensor placement and switchover valve operation |
| 9 | Soft lockout at low outdoor temperature | The control’s cold-weather operating limits |
One and two flashes: keep the sensors separate
Identify whether the code names air or coil temperature
American Standard assigns one flash to the ambient sensor and two to the coil sensor. Both rows include an open or shorted sensor as an out-of-range condition.
The manual describes timed defrost operation when sensor information is unavailable. A heat pump still making some heat can therefore need a sensor investigation; continuing operation does not erase the reported fault.
Ask the technician which sensor circuit the count identifies. The ambient and coil readings serve different places in the defrost checks, so an unspecified request to replace the temperature sensor leaves out useful information.
Three, four and five flashes: pressure and lockout
Distinguish an open switch from the lockout that follows
For three flashes, American Standard says the low pressure switch is open, and the indication clears if the switch closes. The chart does not identify a failed switch or prescribe adding refrigerant from that count alone.
Four flashes mean hard lockout. For this revision, the table says that follows the fourth low pressure cutout trip and can only be cleared by a power cycle. Preserve the reported condition for diagnosis rather than repeatedly cycling power to restart it.
Five flashes identify soft lockout, which clears after its specified period. The length depends on the trip history and operating mode; it is not one universal restart delay.
Include heating or cooling when describing a long pause
American Standard’s page 9 notes give a fifteen-minute soft lockout for the first low pressure cutout trip and thirty minutes for the second. For the third trip in cooling, the listed delay is one hour.
In heating, the third trip instead brings an eighteen-hour soft lockout. The note also allows it to clear if outdoor temperature rises above 40 degrees F for at least thirty minutes. The fourth trip produces hard lockout in either mode.
These are the control’s protective delays, not a recommendation to leave a house without heat while waiting for a fault to disappear. Include the operating mode and loss of heat when arranging service.
Defrost reports and cold-weather protection
Separate closely spaced defrosts from low ambient lockout
For six flashes, American Standard describes defrost cycles occurring too close together. Its heating short-cycle fault triggers both six and five flashes and follows the lockout sequence unless the condition clears.
Seven and eight flashes identify timed defrost operation in this chart, with the sensor-placement and valve checks shown above. Those entries should not be reduced to an instruction to replace the defrost board.
Nine flashes instead identify low ambient soft lockout. That is a cold-weather control condition, separate from the open low pressure switch at three flashes.
Describe any visible ice from outside the cabinet. The heat pump frozen in winter guide helps distinguish a frosting complaint from a unit that stays encased in ice.
What each one takes
| Finding | Work involved |
|---|---|
| One or two flashes | Testing the identified temperature sensor circuit |
| Three flashes | Determining why the low pressure switch is open |
| Four or five flashes | Reviewing trip history, mode and the underlying protection event |
| Six, seven or eight flashes | Checking defrost behavior, sensor placement and valve operation as the chart specifies |
| Nine flashes | Reviewing outdoor conditions against this control’s low ambient protection |
Questions people ask
Where is the American Standard heat pump code PDF?
The 4A6H6018H-SF-1C-EN Service Facts has its flash chart on page 9. The American Standard name and outdoor model appear on the cover.
Does this explain thermostat error 126?
No. This is a counted-flash table for the named outdoor defrost control, and 126 is not an entry. Keep the thermostat model, outdoor model and complete message together for the service agency.
What about American Standard 184.07?
This Service Facts does not define that decimal alert. A communicating system needs the alert chart for its own equipment. Do not turn 184.07 into a flash count or assign another model’s definition to it.
Can two flashes mean furnace ignition lockout?
This heat pump chart does not define furnace codes. For this outdoor heat pump, American Standard assigns two flashes to the coil temperature sensor. The cabinet and control matter as much as the count.
Are all pauses a low pressure fault?
No. This manual also lists defrost-related protection and low ambient lockout. With no readable code, the outdoor unit not running guide organizes the symptoms without guessing a flash count.
The other heat pump guides: heat pump resets, winter icing and auxiliary heat on the thermostat.
Sources: American Standard Service Facts 4A6H6018H-SF-1C-EN, August 2016, model 4A6H6018H1000A, pages 1, 2, 8, 9 and 16