Carrier Infinity Error Codes: 32, 41, 45, 82 and 83

Carrier Infinity Error Codes: 32, 41, 45, 82 and 83
Short answer

A Carrier Infinity code comes from the furnace or the outdoor unit; on the 59MN7A furnace and the 24VNA0 or 25VNA0 it flashes as short then long blinks. The number only means something next to the model: 45 is a control circuitry lockout on the 59MN7A and a compressor winding fault on a 24VNA0 or 25VNA0 with software V9 or later. 82 and 83 on those outdoor units are 4 hour lockouts.

Carrier Infinity error codes are status codes that come from the equipment, the furnace or the outdoor unit, and Carrier’s outdoor unit manual says they are easily read from the wall control. On the 59MN7A furnace and the 24VNA0 and 25VNA0 outdoor units, the same two digit code flashes on an amber light on that unit’s circuit board.

The number on its own is not enough. On a Carrier 59MN7A furnace, 45 is a control circuitry lockout. On a 24VNA0 or 25VNA0 outdoor unit with software V9 or later, 45 is a compressor winding fault. Everything below comes from Carrier’s own manuals and its page on furnace smells, and each code stays with its model.

Before you start

What to carry: a torch, your phone to film the amber light, and a pen. Nothing to open: on the 59MN7A, Carrier’s guide says do not remove the blower door, and to watch the amber light for at least 30 seconds.

Gas or electric? The furnace codes here are for the 59MN7A, a modulating gas furnace. The outdoor codes are for the 24VNA0 and 25VNA0 variable speed air conditioner and heat pump, and the newer 24VNA6 and 25VNA4. If your model number starts with something else, use its own manual.

Renting? Send the code, the model number and a short video of the light to whoever arranges repairs.

Leave the codes alone if you smell gas.
Rotten eggs or sulfur. Carrier treats that smell as an emergency: leave the area and contact your gas utility or emergency services, and do not keep running the furnace.

The line Carrier draws. Its furnace troubleshooting guide says only trained and qualified people should install, repair or service heating equipment. Untrained people can do basic maintenance such as cleaning coils and cleaning or replacing filters, wearing safety glasses and work gloves. Everything else is for trained service personnel.

Two furnace codes that point at the gas valve circuit. On the 59MN7A, code 21 is a gas heating lockout that will not reset itself, and Carrier lists a stuck closed gas valve relay among the checks. Code 22 means flame is proved while the gas valve is switched off, and Carrier’s checks are a leaky or stuck open gas valve. Both are a call to a technician.

Read the code and find where it came from

Check 1Free, nothing to open

Count the flashes, then note the model

On the 59MN7A and the 24VNA0 and 25VNA0, Carrier flashes a code the same way: short flashes give the first digit, long flashes the second. Carrier’s own example is 3 short flashes followed by 2 long flashes, which is code 32.

On the 59MN7A furnace, the amber light has three other states. Continuously on means the control has 24 volt power. Continuously off means the technician checks for power at the board. Rapid flashing means the 115 volt line polarity is reversed, which is wiring work.

On the Infinity Touch control, Carrier says the run and fault history is stored in the equipment circuit boards, when they are communicating, and displayed on the control. Its list of the last 10 system events shows which piece of equipment generated each one. That is why the model matters: the wall control tells you which piece of equipment, the furnace or the outdoor unit, sent the code.

On the 24VNA0, 25VNA0, 24VNA6 and 25VNA4, read the code on the wall control and do not open the outdoor unit. Carrier’s manuals say the main disconnect must be off before servicing, there may be more than one, and the control box cover stays on for 2 minutes after power is removed. That is technician work.

HOW THESE CARRIER MODELS FLASH A CODE

3 short first digit 2 long second digit

Code 32 Carrier's own example On the 24VNA0 and 25VNA0: a short flash is 0.25 s on, a long flash 1 s on

A Furnace board 59MN7A: an amber light flashes the code

B Outdoor unit board 24VNA0, 25VNA0: amber light 24VNA6, 25VNA4: a display

C Infinity wall control shows the code that the furnace or outdoor unit sent

How Carrier flashes a status code on these models: short flashes are the first digit, long flashes the second. Carrier's example, 3 short and 2 long, is code 32.

59MN7A furnace codes

These come from Carrier’s troubleshooting guide for the 59MN7A Series 100 modulating furnace. Carrier says stored codes are erased automatically after 72 hours, so write a code down when you see it.

Code What Carrier’s chart says
11 No previous code
12 Blower on after power up, normal operation; the blower runs 90 seconds if power comes on during a call for heat
13 Limit circuit lockout; auto resets after 3 hours
14 Ignition lockout; auto resets after 3 hours
15 Blower motor lockout; auto resets after 3 hours
21 Gas heating lockout; does NOT auto reset
22 Abnormal flame proving signal
24 Secondary voltage fuse is open
31 / 32 A pressure switch did not close or reopened
33 Limit circuit fault
34 Ignition proving failure
41 / 42 Blower motor fault / inducer motor fault
45 Control circuitry lockout; auto resets after 1 hour
Check 2Free if it is clean; a filter if it is not

With 33 or 13, look at the filter

Carrier’s checks for code 33, limit circuit fault, include a dirty filter or a restricted duct system. The filter is the part Carrier leaves to you. Change or clean it before anything else.

Carrier says that if the limit stays open longer than 3 minutes, 33 turns into lockout 13, which auto resets after 3 hours. The other checks on Carrier’s list, a loose blower wheel, the switch and its connections, the gas input adjustment and the limit switch and its gasket, are for the technician. A flame rollout switch needs a manual reset, and that is part of the same technician visit.

Check 3A service visit; the cause decides the cost

With 32 or 43, tell the technician about water and venting

For code 32, Carrier’s checks include a restricted vent, a plugged condensate drain, water in the vent piping, possibly from a sagging pipe, excessive wind, and the pressure switches and their tubing. Code 43 has a similar list. These are inside the furnace and its venting, so the useful thing you can add is what you saw: water on the floor, a windy day, or snow around the outside pipes.

For code 34, ignition proving failure, Carrier says the control will try three more times before lockout 14 occurs. Its checks include low gas pressure, the igniter and the flame sensor, all technician work.

24VNA0 and 25VNA0 outdoor unit codes

Carrier prints two tables in the 24VNA0, 25VNA0 service manual: one for software V9 and later and one for 25VNA0 units with software V8 and earlier. 82 and 83 read the same in both, but 45 is a compressor winding fault in the newer table and a control fault in the older one.

ONE NUMBER, DIFFERENT FAULTS 45 A 59MN7A furnace Control circuitry lockout B 24VNA0 and 25VNA0, software V9 and later Compressor winding fault C 25VNA0, software V8 and earlier Control fault 82 D 24VNA0 and 25VNA0 Suction over temp lockout, 4 hour reset E 24VNA6 and 25VNA4 82-13: the drive reset after a line voltage loss
One number, different faults. These meanings come from Carrier's 59MN7A furnace guide and its 24VNA0, 25VNA0 and 24VNA6 / 25VNA4 service manuals.
Code Carrier’s description (V9 and later) Reset time
16 Communications loss N/A
31 High pressure switch open 15 minutes
32 Low pressure trip 15 minutes
46 Brownout event Reverts to a 5 minute cycle delay
53 Outdoor air temp sensor fault N/A
62 Compressor no start 15 minutes
82 Suction over temp lockout 4 hours
83 Low pressure lockout 4 hours
84 High pressure lockout 4 hours
88 Inverter temp lockout 4 hours
95 / 99 High current lockout / high torque lockout 2 hours
Check 4Free to look; a service visit if it keeps locking out

With 32 or 83 in winter, look at the outdoor coil

Carrier’s manual says that after a low pressure trip or lockout, the checks are the refrigerant charge and indoor airflow in cooling, and outdoor fan operation and the outdoor coil in heating. The outdoor unit manual says service on these units is for trained technicians and warns that rotating fan blades can cause injury, so only look. From outside the unit, check the coil for the clogging Carrier’s 25VNA0 table names, ice or debris, and check the indoor filter too.

Carrier explains how 83 is reached: if the pressure drops below the instantaneous level three times in a row, operation locks out for 4 hours and code 83 goes to the wall control. The trip counter resets to zero if 15 minutes of successful operation come before the third trip. The refrigerant charge is technician work.

24VNA6 and 25VNA4: codes with two parts

Check 5Free to read; wiring checks if it repeats

Read both halves of the code

The newer 24VNA6 and 25VNA4 outdoor units use a two part code, and their matrix display scrolls up to four active codes, highest priority first. Here 82 is not a suction lockout. Carrier’s code 82-13 means the drive reset itself after a line voltage loss.

Carrier says the system should resume after its 5 minute compressor protection delay. Three 82-13 codes within an hour become 82-53 and a 2 hour lockout. Carrier adds that occasional 82-13 codes can come from a momentary power loss or electrical noise from the utility. Its next step, checking that every line voltage connection is tight, is electrical work for the technician.

Carrier also says the software in these units can be updated through the Infinity control once the homeowner or the service technician approves it.

What each one takes

What you see What the work involves
59MN7A 11 or 12 Nothing; Carrier lists them as no code and normal operation
59MN7A 33 or 13 A filter first, then the technician’s limit checks
59MN7A 21 or 22 A technician and the gas valve checks
24VNA0 or 25VNA0: 32 or 83 in heating A look at the coil and the filter, then the technician’s charge and airflow checks
24VNA6 or 25VNA4: 82-13 now and then Possibly a momentary power loss; repeats mean the wiring checks

Questions people ask

Is code 82 the same on every Infinity outdoor unit?

No. On the 24VNA0 and 25VNA0, Carrier calls 82 a suction over temp lockout with a 4 hour reset. On the 24VNA6 and 25VNA4, codes starting 82 are drive codes such as 82-13, a reset after a line voltage loss.

Why does my furnace flash 12 after a power cut?

On the 59MN7A, Carrier calls 12 blower on after power up and describes it as normal operation. The blower runs for 90 seconds if power comes back during a call for heat.

Can I clear the furnace’s stored codes?

On the 59MN7A, Carrier says stored codes erase themselves after 72 hours. Its manual way of clearing them uses a setup switch on the control board, which is technician work, so write the codes down instead.

What does code 24 on the furnace mean?

Carrier’s 59MN7A chart calls 24 an open secondary voltage fuse. Its check is for a short circuit in the 24 volt wiring, including the thermostat wires, which is a job for the technician.

My Infinity code is not on this page.

These are selected codes for named Carrier models. Read the model number on your furnace or outdoor unit and ask for that model’s own chart, because the same number changes meaning between them.

The other Carrier and heat pump guides: Carrier furnace error codes, Carrier AC and heat pump codes, how to reset a heat pump and heat pump not heating.

Sources: Carrier 59MN7A Series 100 Troubleshooting Guide (59MN7A-01T); Carrier Service Manual 24VNA0, 25VNA0 (tables 4 and 5, pp. 12 and 13); Carrier Service Manual 24VNA6 / 25VNA4 (table 6); Carrier Infinity Touch Control installation instructions (SYSTXCCITC-07SI); Carrier's page on furnace burning smells