Mitsubishi's SLZ-KA09, KA12 and KA15NA installation manual lists E6 and E7 as communication errors, U8 as an outdoor fan protection stop, and P8 as a pipe temperature error. Match the indoor model before using this chart. A blinking wall unit needs a different list.
Mitsubishi heat pump error codes need a model name beside them. For the SLZ-KA09, KA12 and KA15NA ceiling units, Mitsubishi’s installation manual separates indoor faults from errors reported by the outdoor unit.
This page follows that specific chart. If you have an MSZ wall unit flashing its operation lamp, use the Mitsubishi blinking light guide. A flash count is not a letter code.
Before you start
What to carry: a torch, your phone and the installation paperwork. There is no need to open a cabinet to use this list.
Gas or electric? These are electric split systems. This guide concerns the ceiling cassette’s check codes, not a gas furnace or a Mitsubishi boiler.
Find the full model. Compare your paperwork with SLZ-KA09NA, SLZ-KA12NA or SLZ-KA15NA. Keep the outdoor model and controller model with it. Do not climb up or remove a grille just to reach a concealed label.
Renting? Send the displayed message and the room affected to the person who arranges your heating repairs.
Mitsubishi also says not to touch switches with wet hands or operate without the air filter installed. If refrigerant leaks during operation, its instruction is to ventilate the room; refrigerant meeting a flame can release poisonous gases.
Match the display to the right chart
Save the message before changing settings
Take a photo of the complete display. Include whether one room or the whole system stopped, and whether you had selected heating or cooling.
Mitsubishi’s section 8.3 sends the installer to the particular controller’s installation manual for the self check procedure. It does not supply one button sequence for every controller. Leave installer menus alone if the normal display already gives you a code.
E6, P8 and the indoor unit’s other codes
The following meanings are Mitsubishi’s entries for the SLZ-KA09, KA12 and KA15NA indoor units.
| Code | Mitsubishi’s SLZ-KA chart meaning |
|---|---|
| E6, E7 | Communication error between indoor and outdoor units. |
| EE | Communication error between indoor and outdoor units. |
| E4 | Remote controller signal receiving error. |
| P1 | Intake sensor error. |
| P2, P9 | Pipe sensor error: TH2 for P2, TH5 for P9. |
| P4, P5 | Drain sensor error for P4; drain pump error for P5. |
| P6 | Freezing or overheating safeguard operation. |
| P8 | Pipe temperature error. |
| PA | Forced compressor error. |
| Fb | Indoor control system error, including memory errors. |
Keep E6 and E4 separate
In Mitsubishi’s SLZ chart, E6 concerns the link between the indoor and outdoor units, while E4 concerns reception from the controller. Tell the repairer which message you have rather than describing both as a remote problem.
The chart identifies the communication fault without naming a single failed component. It does not justify ordering a replacement controller just because the message appears on that controller.
Read P8 as a temperature fault
Mitsubishi calls P8 a pipe temperature error on these SLZ models. It lists the pipe sensors separately under P2 and P9. Keep that distinction when asking for help: P8 does not say to replace a particular sensor.
For P4 or P5, describe any water you can see from floor level as well as the message. Mitsubishi’s chart points to the drain sensor or pump respectively. Leave ceiling access and drain pump testing to the repairer.
U1, U8 and messages from the outdoor side
Mitsubishi puts these in the SLZ manual’s separate table for errors detected outside the indoor unit. Its note directs the technician to the outdoor controller board’s LED display for further detail.
| Code | Mitsubishi’s outdoor error entry in the SLZ-KA manual |
|---|---|
| U1, Ud | Abnormally high pressure, with 63H operated, or overheating safeguard operation. |
| U8 | Outdoor fan safeguard stop. |
| U2 | Abnormally high discharge temperature, 49C operation, or insufficient refrigerant. |
| U3, U4 | Open or short circuit in outdoor temperature sensors. |
| U5 | Abnormal heat sink temperature. |
| UP, UF | Compressor overcurrent interruption; UF specifies a locked compressor. |
| U6 | Compressor overcurrent interruption or abnormal power module. |
| U7 | Abnormal superheat due to low discharge temperature. |
| U9, UH | Voltage or main circuit synchronizing signal abnormality, or a current sensor error. |
| E9 | Outdoor unit transmitting error in communication with the indoor unit. |
Arrange service with the outdoor details
Mitsubishi’s outdoor table calls U8 a fan safeguard stop, not an instruction to replace the motor. The repairer needs the matching outdoor manual before deciding what failed.
Likewise, Mitsubishi’s U2 entry contains several possibilities. Treating that line as a request to add refrigerant would skip the diagnosis. Do not remove the outdoor cover to read the board yourself.
What happens after the code is identified?
Keep your original record if the display clears before the service appointment.
For a planned power shutdown, Mitsubishi’s SLZ instructions say to wait at least five minutes after stopping operation before switching off the main power. That is a shutdown precaution, not a five minute reset recipe. For the installer test run, Mitsubishi requires main power on more than 12 hours before operation; starting immediately after power is restored can severely damage internal parts.
If your system has no letter code and simply fails to warm the room, the mini split not heating checks cover that different starting point.
What each one takes
| Situation | What to allow for |
|---|---|
| Matching the model and display | Your paperwork and a clear photograph; no replacement parts. |
| Communication or sensor code | Technician diagnosis before a wiring or component repair is chosen. |
| Drain code on a ceiling unit | Service access to the cassette and its drainage equipment. |
| Outdoor protection code | The outdoor model’s service procedure and a repair estimate after testing. |
Questions people ask
Where is the Mitsubishi heat pump error codes PDF?
The SLZ-KA09, KA12 and KA15NA installation PDF has the chart on page 12, section 8.3. Use it for those ceiling units and their listed check codes.
Does this list cover every Mitsubishi heat pump?
No. Its scope is the SLZ-KA manual named above. Do not carry its meanings over to a different family merely because the brand matches.
Why is L9 missing?
Mitsubishi does not list L9 in this manual’s self check chart. Send that code with the full equipment model to the installer instead of substituting a similar looking entry.
Can I use it for a four digit code such as 7101?
This SLZ chart uses the letter codes shown here. It does not give a meaning for 7101, so this page cannot decode that message.
Is U1 on my model sticker an error?
This page reads an error displayed by the controller. A character sequence in the equipment model is part of the model record; do not look it up as though the controller had reported it.
The other mini split guides: codes by brand, Mitsubishi lamp patterns and no heat.
Sources: Mitsubishi Electric SLZ-KA09, KA12, KA15NA installation manual, section 8.3, page 12; safety precautions, page 2. https://s3.amazonaws.com/enter.mehvac.com/DAMRoot/Original/10005/SLZ_Install.pdf