York's Affinity YZV outdoor control uses written messages such as HPS OPEN and COMMUNICATIONS LOST. In its installation manual, a solid red LED accompanies many different faults. Read the message, operating mode and lockout wording together; the light alone does not identify the cause.
York heat pump error codes on the Affinity YZV are written fault messages, and Johnson Controls lists a solid red light beside many of them. Counting that light as if it were a furnace flash code will not tell you what stopped the outdoor unit.
This guide covers the YZV control in manual 5846134-UIM-B-0320. The manual also names HC20 and HL20. Keep YZH, other defrost boards and York mini splits with their own code lists. The existing York furnace error code guide covers the TM9M gas furnace instead.
Before you start
What to carry: a torch, the outdoor model from your installation papers and the complete message available at the thermostat. Include whether the system was heating, cooling or defrosting when it stopped.
Gas or electric? This is an outdoor electric heat pump chart. If your system also has a gas furnace, identify which piece of equipment is reporting the fault.
Renting? Give those details to the maintenance contact. You can gather the thermostat information without removing an equipment panel.
Johnson Controls’ owner’s manual says not to install or service the equipment yourself. It warns that improper work can cause fire, electric shock or other hazardous conditions, and that the refrigerant operates at high pressure.
The outdoor display and inverter lights described below are service references. Have the technician read them if access requires opening a cover. Do not bypass a pressure switch or try the manual’s forced test modes to make the compressor run.
Read the message and its last words
Separate a present fault from stored history
Johnson Controls says the YZV outdoor display can show current and stored system faults. Its main control retains the ten most recent fault codes for the service technician, even when power is removed.
Ask which list the displayed entry came from. An old stored message and an active stop need different attention. Include the full wording, especially SOFT LOCKOUT, HARD LOCKOUT, NORMAL or DEFROST, rather than shortening everything to a red light.
The manual has separate tables for the outdoor control and inverter drive. If your service report mentions an inverter LED pattern, use the inverter table for this model, not the furnace chart linked above.
HPS OPEN: the operating mode changes the checks
Start with the airflow side named in the chart
Johnson Controls defines HPS OPEN as a high pressure switch fault before lockout. For cooling, its YZV table lists reduced outdoor airflow and asks the repairer to check the outdoor coil, fan and air movement.
For heating, the same row points to reduced indoor airflow, including a dirty filter, blower trouble, a dirty indoor coil or restricted ductwork. Look for blocked room grilles; filter care is covered below. Keep coil access and blower work for the repairer.
The table also lists switch connections, a faulty switch, expansion valve trouble, a restriction and excess refrigerant as possible causes in all modes. A filter check is useful information; it does not settle the whole pressure fault.
For HPS SOFT LOCKOUT with DEFROST, Johnson Controls also lists a reversing valve that did not switch. Tell the technician if the stop occurred during a winter defrost cycle. The frozen heat pump guide covers that symptom separately.
The YZV messages to look up
This selected list follows table 7 in the Johnson Controls YZV installation PDF. Punctuation on the display may differ from the plain wording shown here.
| Outdoor message | Meaning in the YZV table |
|---|---|
| HPS OPEN | High pressure switch fault, not yet in lockout |
| HPS SOFT LOCKOUT or HARD LOCKOUT, NORMAL | High pressure lockout after normal compressor operation |
| HPS SOFT LOCKOUT or HARD LOCKOUT, DEFROST | High pressure lockout after defrost operation |
| LOW VOLTAGE, BELOW 19VAC | Low control voltage |
| COMMUNICATIONS LOST, INVERTER DRIVE | Communication fault between outdoor control and inverter |
| COMMUNICATIONS LOST, SYSTEM MASTER | JCI RS-485 system communication lost |
| INVERTER CONFIGURATION ERROR | Replacement drive tonnage selection does not match the stored factory value |
| OUTDOOR AMBIENT SENSOR, SHORT or OPEN | Outdoor air sensor circuit failure, with lockout wording identifying the state |
Communication and sensor faults need circuit checks
Give the repairer the complete equipment history
For COMMUNICATIONS LOST, INVERTER DRIVE, Johnson Controls lists wiring, the outdoor control board and the inverter board. For SYSTEM MASTER, it lists wiring and system phasing. Neither message alone establishes that the thermostat needs replacement.
Mention any recent control, thermostat or drive replacement. Johnson Controls’ configuration error entry specifically asks the repairer to verify the correct replacement drive model.
For the outdoor ambient sensor fault, the YZV table lists the thermistor, its wiring and the main outdoor control. Johnson Controls tells the technician to compare the sensor’s resistance with its temperature chart and check the wires. These are technician checks, not a reason to order a sensor just because its name appears on the screen.
What to do while arranging service
Keep the simple owner checks separate from a reset
Johnson Controls’ owner’s manual asks owners to check for a dirty indoor filter and outdoor leaves or debris. It says to replace disposable filters and clean reusable ones to their maker’s instructions, with the airflow arrow pointing along duct airflow.
A quiet outdoor unit is not automatically a fault. The YZV installation manual describes a five minute delay during which the compressor and outdoor fan do not operate, including after a compressor cycle.
Johnson Controls says to keep the main power on to protect the compressor and use the thermostat control switch when you need to turn the system off. The linked owner’s manual says that after main power has been off for eight hours or longer, allow eight hours with power restored before restarting. It directs owners to emergency heat if needed during that period.
After the cause is corrected, confirm that the rooms reach the requested temperature. If they do not, report that result alongside any returning alert. The heat pump not heating guide helps describe a comfort problem without a fault message.
What each one takes
| Finding | Work involved |
|---|---|
| Blocked airflow | Filter care or clearing an accessible obstruction; deeper coil or blower work needs service |
| HPS lockout | Airflow, switch, valve and refrigerant diagnosis |
| Communication lost | Wiring, power and control checks |
| Ambient sensor fault | Resistance, wiring and board assessment |
| Configuration error | Verification of the replacement drive and its setup |
Questions people ask
Is solid red enough to diagnose this York heat pump?
No. Johnson Controls lists solid red LED1 for pressure, communication, voltage and sensor faults on this control. The written message supplies the distinction.
Is every York Affinity code on this page?
No. The source is the named YZV installation manual. Affinity branding alone is not a control model; use the complete outdoor model to choose its manual.
Does turning power off erase the service history?
Johnson Controls says the YZV main control retains its stored faults through a power loss. Its history helps the technician check what happened before the visit.
Why does the history show only one repeated pressure fault?
The YZV manual says consecutive identical faults are stored once when no different fault occurs between them. One history entry need not represent just one occurrence.
Can I use a furnace pressure switch guide for HPS OPEN?
This YZV table concerns the outdoor heat pump’s pressure protection. The TM9M furnace guide concerns a different control and its combustion system. Keep their tests separate.
The other heat pump guides: outdoor unit not running, short cycling, and not cooling.
Sources: Johnson Controls YZV/HC20/HL20 installation manual 5846134-UIM-B-0320, pp. 10 to 16, 20 to 24; Johnson Controls outdoor split system User's Information Manual 6136937-UUM-A-0622, pp. 2 to 3, 7 to 8.