Bosch IDS Heat Pump Error Codes: E5, P1, H5 and AtL
On a Bosch IDS 2.0 heat pump, AtL, dF and a letter followed by two numbers are not faults: the unit is outside its temperature range, defrosting, or running in a limited way. E5 is the power supply, E6 and P8 the outdoor fan, H5 a lockout that needs the power switched off and on, and the P codes are pressure and temperature protections for a technician.
The Bosch IDS 2.0 is an inverter heat pump. Its outdoor unit, the BOVA, speeds its compressor up and down instead of just switching on and off. It shows codes on a small display on the control board inside the outdoor unit, and some of what appears there is not a fault at all.
Everything on this page comes from Bosch’s own installation, operation and maintenance manual for the IDS 2.0 BOVA. Bosch says any maintenance and repair of the outdoor unit is for qualified service people. So most of this page is about knowing what a code means, and which few things are yours to check.
Before you start
What to carry: a torch, and your phone to photograph the code. Five minutes.
Gas or electric? Electric. The outdoor unit runs on a 208 or 230 volt supply.
Where the code shows. On the display of the main control board in the outdoor unit. The board sits behind a service panel, so leave opening it to the technician.
What normal looks like. Bosch says that with no fault, the display shows the outdoor temperature while the unit waits, and the compressor speed while it runs.
Power off for any check. Bosch says to turn the heat pump off and disconnect the power before cleaning or maintenance.
After a long cold shutdown. Bosch recommends powering the unit with the thermostat off for at least 12 hours before the compressor runs. That lets the crankcase heater warm the compressor.
Readings that are not faults
Read it before you worry
AtL: outside its temperature range. Bosch’s range is 15 to 125°F for cooling and -4 to 86°F for heating. Outside it, Bosch’s chart says no service is required: wait for the temperature to come back.
Below -4°F. Bosch says the heat pump then sends the call to the indoor unit’s electric heat, if it has any.
dF: defrost. Bosch says the display shows dF alone while the unit defrosts its outdoor coil: why a heat pump ices up in winter.
A letter, then two numbers. Bosch says the unit keeps running in a limited way, and the two numbers are the compressor speed. L, D, F and C mean it is holding back for coil temperature, discharge temperature, module temperature or current. U is low voltage, P is the compressor ratio and A is oil return.
E4 in deep cold. Bosch’s E4 chart says no service is required when it is below -4°F outside.
A minute of cooling. Bosch says that on first time operation, a heat call runs about a minute in cooling to build pressure for the reversing valve.
Codes with an owner check
Work the owner checks
E5: high or low voltage. Bosch’s chart checks the supply for 270 volts or more, or 172 volts or less. The fix is the supply, and Bosch names the utility company.
E6 and P8: the outdoor fan. Bosch’s charts ask whether the weather is stopping the fan. If so, power the unit off until the severe weather passes. Bosch calls P8 its hurricane or typhoon protection.
E6 and a blocked fan. Bosch’s chart also asks whether something is blocking the fan or the blade is damaged: power off, then clear it.
H5: a lockout. Bosch says low pressure protection tripped five times in 100 minutes, and H5 needs a hard restart, meaning the power off and on. If it comes back, the low pressure needs a technician.
Air in and out. Bosch’s check at the start of each season: power off, look for damaged wires and leaks, and make sure nothing blocks the air inlets and outlets. It asks for at least 12 inches to shrubs.
Snow and ice
Keep it clear in winter
Raised. Bosch says to raise the unit 3 to 12 inches above the pad, so the water from defrost drains away before it can refreeze.
Drain holes. Bosch says the drain holes in the base pan must not be blocked.
Drifts and drips. Bosch says to avoid spots prone to snow drifts, or to fit a snow barrier, and to keep water, snow or ice from a roof or overhang from falling on the unit.
Every code in Bosch’s table
| Code | What Bosch calls it |
|---|---|
| C3 | Outdoor coil sensor not seated right, in cooling |
| E4 | Temperature sensor fault |
| E5 | High or low voltage protection |
| E6 | Outdoor fan motor fault |
| E7 | Discharge sensor not seated right |
| E9 | EEPROM fault |
| H0 | Communication fault in the main control chip |
| H5 | Low pressure five times in 100 minutes, lockout |
| H8 | Pressure transducer fault |
| P0 | Control board module too hot |
| P1, F1 | High pressure switch protection |
| P2 | Low pressure protection |
| P3 | Compressor over current |
| P4 | Compressor discharge too hot |
| P5 | Outdoor coil too hot in cooling |
| P8 | Fan protection in hurricane or typhoon winds |
| PH | Low discharge superheat |
| L0 to L9 | Inverter module protection |
| AtL | Outside temperature beyond its range |
When it needs a technician
Know when to stop
P1, P3, P4, P5 and PH. Bosch’s charts check the service valves, the refrigerant charge, the airflow and whether it is over 120°F outside. Refrigerant work needs a licensed technician: the signs of a refrigerant leak.
Sensor and board codes. C3, E7, E9, H0 and H8, and E4 in normal weather, point to wiring, a sensor or the control board.
L0 to L9. Bosch’s chart starts with whether the power supply is stable, then moves to the refrigerant circuit and the compressor.
Heating stopped altogether. The wider checks for a heat pump that blows cold are here: why a heat pump is not heating.
Questions people ask
What does AtL mean on a Bosch heat pump?
Ambient temperature limited: it is too hot or too cold outside for the heat pump to run. Bosch says no service is required, so wait for the temperature to come back into range.
What does dF mean?
Defrost. The unit is melting ice off its outdoor coil, and the display shows dF alone until it finishes.
What does E5 mean on a Bosch IDS?
High or low voltage. Bosch’s chart checks for 270 volts or more, or 172 volts or less, and the fix is the power supply.
What does H5 mean?
A lockout after five low pressure trips in 100 minutes. It needs the power switched off and on, and a technician if it returns.
Why does the display show a letter and a number?
The unit is running in a limited way, for example holding back for coil temperature or low voltage. The number is the compressor speed. It is not a fault.
Can I clean the outdoor unit myself?
Bosch says maintenance and cleaning of the outdoor unit are for qualified service people. What you can do is keep snow, leaves and plants clear of it.
Sources: Bosch IDS 2.0 BOVA installation, operation and maintenance manual (04.2021), from bosch-homecomfort.com
By 