Radiator Leaking? Valve, Vent or the Radiator Itself
Dry the radiator, then watch where the water comes back: the valve stem, the joint where the valve meets the radiator, the bleed screw or steam vent, or the radiator itself. A weeping valve stem points to its gland or packing. For a spitting steam vent, Danfoss's one-pipe valve instructions check the pitch, the valve and the pressure. A leak in the radiator itself needs a repair or a new radiator.
This page covers four places a radiator itself can leak: the valve, the joint where the valve meets the radiator, the bleed screw or steam vent, and the radiator body. Find which one it is first. Each has its own fix, and only a leak in the body means repairing or replacing the radiator.
This page is about radiators on a boiler, hot water or steam. A small leak is still worth fixing soon: the water it loses is replaced with fresh water, and the boiler makers explain below why that matters.
Before you start
What to carry: a torch, old towels, a bucket or a baking tray, kitchen paper, an adjustable wrench and a radiator key.
Gas, oil or electric? It makes no difference here: the radiators only carry the heat. A plug-in electric oil-filled radiator is a different machine. If a De’Longhi one leaks oil, its manual says to unplug it, let it cool, and contact the maker or an authorized service center.
Hot water or steam? A hot water radiator has two pipes and a small bleed screw near the top. A one-pipe steam radiator has one big pipe at the bottom and an air vent on the other end, typically about halfway up, Castrads says. A radiator with two pipes on a steam boiler is two-pipe steam: Castrads says it has no vent on the radiator. The steam rules here apply to it. The drawing in a radiator not heating shows the difference.
Renting? EPA says to report all plumbing leaks to the owner, manager or superintendent straight away. In New York City, a tenant can call 311 if the owner does nothing about a leaking radiator, the city’s housing agency says.
Old pipe wrap. EPA says asbestos is most common in homes built before the 1970s, that the insulation on hot water and steam pipes may contain it, and that water damage can make it release fibers. Do not touch it. If it is wet or falling apart, EPA says to have it sampled by a trained professional, not to sweep or vacuum any bits, and to keep children away.
Steam you cannot stop. NYC’s inspection manual says to close the radiator valve, check it holds, and keep the system off until the leak is fixed. If closing the valve does not stop it, the boiler is shut down until it is inspected. Weil-McLain and Peerless print the steps to turn the gas off inside the boiler’s jacket panel. If you rent, tell the owner at once.
Water near wiring. Ready.gov says not to touch electrical equipment if it is wet or if you are standing in water, and to turn the electricity off if it is safe to do so. If the boiler itself has been sprayed or sat in water, Weil-McLain says not to run it.
Do not overtighten. Burnham warns that overtightening with PTFE tape can crack the tappings on its cast iron baseboard, and Caleffi gives the same warning for its vents.
Find where the water comes from
Catch it, dry it, watch. Put the towels and the tray under the radiator. Wipe the valve, the joints and the radiator dry with a towel, then wait for the water to come back. Stelrad says to hold kitchen paper against each fitting in turn to find which one is wet.
Start at the top. A drip can run down the outside before it falls. Look at the floor and the wall next to the radiator too: NYC’s inspection manual checks both.
Cold and hot. If nothing shows with the heat off, look again once the radiator is hot, without touching it. Myson says leaks can appear in a heated system that did not show when it was cold.
On steam, listen as well. Hoffman says that in many cases a small steam leak leaves no water, because it evaporates. NYC’s inspection manual listens at each radiator for hissing.
Water at the valve stem
What it looks like. Water around the spindle, just under the knob or the thermostat head. Stelrad says a valve leak often starts when the spindle packing becomes worn or damaged.
A thermostatic valve. Oventrop’s first fault for a leaking valve is a loose gland nut: tighten it. If its O-ring is damaged, Oventrop fits a new gland nut without draining, because the valve has an extra seal, but not on its AV6, ADV6 and RFV6 series. Danfoss says the gland seal on its RA 2000 valves can be replaced in a few minutes with the system running, but on steam it says to consider doing it during an off cycle. On any other valve, follow Burnham’s rule: cool and no pressure first.
A steam valve. HUD’s Rehab Guide says the stem packing on most radiator inlet valves wears with time, and the valve can be repacked. Hoffman says an ordinary two-pipe steam supply valve has a packing nut that tightens that packing.
Fully open or fully shut. On one-pipe steam, Castrads, Hoffman and Peerless say the valve is never left halfway; Peerless says that holds water back in the radiator and causes hammer. DOE says a valve that will not fully open or shut may need replacing.
Water at the joint between the valve and the radiator
What it looks like. Water at the big union nut where the valve meets the radiator, or at the threads where the pipe goes in.
Try a small turn. Viessmann’s advice for a dripping pipe fitting is to try tightening the connector a quarter turn with a spanner, since a seal may have come loose. Do it with the heat off and the radiator cool, and stop if it does not move easily.
When the seal has gone. Viessmann says corrosion can wear seals away, and then a qualified heating contractor replaces them. Myson says the straight threads on its column radiators need professional sealing. On steam, DOE says leaks at threaded connections or the inlet valve seal may let steam into the room.
Shutting one radiator off. On hot water, Castrads says the water leaves through a second valve at the other end, the lockshield, and Stelrad says to turn off both valves before working on a leak. Castrads says a thermostatic valve still lets a little water through unless the decorator’s cap made for it is fitted.
Water from the bleed screw or air vent (hot water)
A bleed screw. It should only let water out while you bleed. Danfoss says to turn the heat down first, and both Danfoss and Viessmann say to close the screw as soon as water comes out. If it still drips once closed, have a heating technician look at it.
An automatic vent. On the Bell and Gossett No. 97 and the Caleffi 5026, the makers say the cap is opened one turn to vent and screwed down tight to shut the vent off. Both say a vent that leaks or is corroded must be replaced, and Caleffi says that is work for qualified personnel, with the pressure at zero and the water below 100 degrees.
Two makers’ own rules. Resideo says the red cap on its EA122 must be tightened all the way, by hand only, never with tools. Taco says never to take the cap off its Hy-Vent.
Vent it cold. Bell and Gossett says only to vent by hand below 100 degrees and to keep out of line with a vent’s opening. Weil-McLain warns that water from an air vent may be very hot.
Bleeding all the time. Castrads says frequent bleeding may mean a problem with the system. Have a heating technician find it.
A steam vent that spits water or hisses steam
What is normal. Hoffman says vapor or slight moisture from its 1A and 1B radiator vents is normal, but steam passing through all the time means the vent has failed. It says to replace them as needed or every 10 years.
A vent that blows steam. Xylem says a vent that keeps discharging steam may have a collapsed float or a pinhole leak, and cannot be repaired: replace it. Fit the new one with the heat off and the radiator cold; Heat-Timer says its opening faces up.
A vent that spits water. Heat-Timer says vents clog over the years with rust from the radiator and pipes. Its fix is to take the vent off with the heat off, as Danfoss says, soak it in hot vinegar for 30 minutes, wrap the thread with Teflon tape and refit it. Do not overtighten it, and watch from the side when the heat comes back on. If it still blows steam, replace it.
Danfoss’s list. For a spitting vent, Danfoss’s one-pipe steam valve instructions say to check the radiator’s pitch, open the supply valve fully, check the riser air vent, and check for too much pressure. HUD says the radiator should slope slightly toward the valve, with a shim under the feet farthest from it.
Too much pressure. Hoffman rates its 1A vent for a maximum of 1½ psig in use, and Weil-McLain says typical one and two pipe systems need less than 2 psig. Bell and Gossett says a setting above the vents’ rating can hold them shut. Ask a technician to check it.
Wet steam. DOE says wet steam can make the master vents on the steam pipes leak water, and that a common cause is oily residue in the boiler water after pipe work. Weil-McLain says a boiler whose water line jumps about because of dirt or oil is skimmed by a technician. Hammer is in a boiler making noise.
Water from the radiator itself
What it looks like. A wet patch or a rust stain on the radiator, between two sections, or a pinhole that weeps. Stelrad says rust inside eats away at the metal until it makes holes.
Cast iron. Castrads says pinholes or damaged joints in very old cast iron radiators are usually repairable, at a cost. Burnham’s instructions for joining sections warn that a missing gasket or a forced thread makes the radiator leak.
Steel. Stelrad says a radiator that leaks from corrosion has to be replaced. Myson’s warranty does not cover rust from oxygen corrosion. If it is a fairly new Runtal radiator, Runtal says to tell it at once if a defect is suspected, and the US guarantee on Purmo radiators holds only if they were not repaired or changed without approval.
Stop-leak. Weil-McLain says never to use petroleum-based sealing or stop-leak compounds, because they can damage system parts. Stelrad says leak sealer is only a short-term fix.
On steam, take it out of use. NYC’s housing agency says a steam radiator with corroded pipes or faulty valves can rupture without warning and release high-pressure steam. Close its supply valve fully and check it holds, and if you rent, tell the owner at once.
Why a small leak still matters
Fresh water wears the boiler. Weil-McLain says continual fresh make-up water shortens a boiler’s life, bringing in minerals and oxygen, so leaks must be fixed at once. Leaking water may also cause severe property damage. Myson says automatic fill valves let oxygen in to attack the radiators from inside.
Watch the boiler gauge. On hot water, Slant/Fin says the gauge on most installations reads about 12 to 15 psi at 70 to 100 degrees. If it drops from normal, the system is losing water. Stelrad says pressure that is too high can cause leaks at valves and joints, and Slant/Fin says to call for service either way. More in boiler pressure too low or too high.
On steam, count the top-ups. Burnham says a steam boiler needs a little water now and then for what the vents lose, but if it needs water more than once a month, a technician should check for leaks or bad vents. Bell and Gossett says a buried return pipe has a good chance of leaking.
Never cold water into a hot boiler. Weil-McLain says it can crack it.
The relief valve. Water from the pipe below the boiler’s relief valve is not a radiator leak. Weil-McLain says a relief valve that often weeps can mean an expansion tank problem on hot water, or a limit set too high on steam: call a technician. Apollo’s relief valve tag says never to cap or plug that pipe.
After the leak
Dry it within two days. EPA says that if wet materials are dried within 24 to 48 hours, mold will not grow in most cases. It says mold can hide under carpet pads and inside walls around leaking pipes.
Mold that is already there. EPA says a patch smaller than about 10 square feet is usually a job you can do yourself; for more, EPA points to its guide for larger cleanups. Ready.gov says people with asthma or a weak immune system should not enter buildings with indoor leaks or mold that can be seen or smelled.
Freezing. Weil-McLain says a power cut or an empty house in cold weather can freeze pipes within hours. DOE says to keep cooler rooms above 50 degrees. See frozen pipes.
What each one takes
| Where it leaks | What it takes |
|---|---|
| The valve stem | Tightening the gland nut, a new gland seal, or repacking |
| The joint with the radiator | A small turn, or a technician to reseal it |
| A hot water bleed screw or air vent | Closing it, or a technician to fit a new vent |
| A steam vent spitting or hissing | Pitch, valve and pressure checks, or a new vent |
| The radiator itself | A paid repair for cast iron, or a new radiator |
| The boiler keeps losing water | A technician to find the leak |
Questions people ask
Why is my radiator leaking from the bottom?
The bottom is where the valve and its joint sit. Dry it all and watch where the water comes back first: a drip from higher up can run down and fall from the bottom.
Is a leaking radiator dangerous?
Weil-McLain says leaks should be fixed at once, and leaking water can cause severe property damage. A steam leak you cannot stop by closing the valve is more serious: NYC’s inspection manual says the boiler is shut down until it is inspected.
Can I use a radiator stop-leak?
Weil-McLain says never to use petroleum-based stop-leak compounds, because they can damage system parts. Stelrad says leak sealer is only a short-term fix.
Is it normal for a steam radiator vent to hiss or let out a little moisture?
Hoffman says vapor or slight moisture from its 1A and 1B vents is normal, and HUD says a vent that hisses all the time needs replacing. Steam all the time, or water spitting, is not: check the pitch, the valve and the pressure, and replace a vent that keeps blowing steam.
Can I turn off just one leaking radiator?
On hot water, Stelrad says to close both the supply valve and the lockshield at the other end, and Castrads says a thermostatic valve still lets a little water through unless its decorator’s cap is fitted. On one-pipe steam, close the supply valve fully, and NYC’s inspection manual says to check it holds.
The other radiator and boiler guides: a radiator not heating, boiler pressure too low or too high, a boiler making noise, a boiler not working and a boiler or radiator that smells.
Sources: Danfoss RA 2000 and RA-N valve data sheets, one-pipe steam valve instructions and radiator bleeding page, Oventrop Uni XH valve instructions, Resideo EA122 sheet, Caleffi 5026 air vent instructions, Bell and Gossett No. 97 and A90602D vent manuals and Steam Team articles, Taco Hy-Vent sheet, Hoffman Specialty 1A radiator vent instructions and steam manual TES-181A, Xylem steam manual TES-375B, Heat-Timer vent guides, Castrads radiator guides, refurbishment terms and terms of sale, Myson, Buderus, Runtal, Purmo and Burnham radiator manuals, Stelrad leak advice, De'Longhi oil-filled radiator manual, Viessmann leak and bleeding guides, Weil-McLain, U.S. Boiler (Burnham), Peerless and Slant/Fin boiler manuals, Apollo relief valve tag, NYC HPD steam radiator inspection manual and Local Law 151, DOE Building America steam guides, HUD Rehab Guide, EPA mold and asbestos guides, CPSC scald guide and Ready.gov floods