Trane's 4TWV0 ComfortLink II service chart separates outdoor sensor alerts such as 67.00 from pressure lockout 80.01 and hard lockout 184.08. Keep the digits after the decimal point: they identify the specific alert. The outdoor display and thermostat do not always show the same message.
Trane heat pump error codes make more sense when you keep the decimal point: 67.00 and 67.07 describe different outdoor sensors in Trane’s ComfortLink II service chart. An alert that still lets the house warm also needs a different response from one that locks the compressor out.
The list below follows Trane Service Facts 4T-V0-SF-1A, dated September 2013. Its heat pump models are 4TWV0024A1000A, 4TWV0036A1000A, 4TWV0048A1000A and 4TWV0060A1000A. Use it for that outdoor control, with the complete model matched first.
For the conventional American Standard 4A6H6018H1000A outdoor unit, use its separate heat pump flash-code chart.
Before you start
What to carry: a phone, pen and torch. Start at the thermostat, where you can read the message without removing a cover.
Which machine? These are electric outdoor heat pump alerts. An indoor gas furnace belongs on the Trane furnace code page, while TAM9 and TEM8 indoor units have their own air handler codes.
Renting? Pass the full message to the person responsible for the heating system, along with whether you still have heat.
Trane also warns against touching the hot compressor top. A thermostat alert gives you a useful starting point without reaching into the outdoor unit.
The number and the place both matter
Keep the full alert and its location
Copy the complete number, the accompanying words and where you saw them. Trane’s chart has separate columns for the outdoor display assembly and the A/TZONE 950 thermostat. Some outdoor alerts have no corresponding numeric thermostat entry.
For example, Trane places DFT FAULT A under outdoor alert group 68 but marks the thermostat column N/A. A technician reporting that outdoor message is not necessarily describing an error number you can find on the wall thermostat.
Include what the heating was doing when the alert appeared. That detail helps separate the heating and cooling rows in this manual.
The outdoor temperature sensor codes
Trane’s 4TWV0 table makes these distinctions.
| Thermostat alert | Trane’s sensor description | Listed behavior |
|---|---|---|
| 67.00 | Outdoor ambient temperature sensing | Heating changes to timed defrost |
| 67.01 | Outdoor coil temperature sensing | Heating changes to timed defrost |
| 67.03 | External temperature sensor shorted | Cooling continues |
| 67.04 | Compressor dome sensor fault in cooling | Cooling continues |
| 67.05 | Compressor dome sensor fault in heating | Heating compressor speed is limited |
| 67.06 | Suction temperature sensor fault in cooling | Cooling continues |
| 67.07 | Suction temperature sensor fault in heating | Compressor speed is limited and the outdoor valve holds a safe position |
Treat continued heating as a clue, not a cleared fault
For 67.00 and 67.01, Trane lists an open, shorted or missing sensor among the possibilities. Its heating fallback uses timed defrost until the sensor reading is restored. The system carrying on does not mean that the alert has disappeared.
For 67.05 and 67.07, Trane limits compressor speed to 2,400 RPM in heating. That gives the technician a reason to investigate reduced output alongside the sensor message, rather than judge the unit only by whether its fan runs.
If the thermostat has no alert and the concern is simply cool feeling air, use heat pump not heating for the wider comfort checks.
Defrost messages at the outdoor display
Separate normal defrost from a defrost alert
Trane says the outdoor display shows DEFROST during the defrost cycle. In its fault table, DFT FAULT A instead points to low heat pump capacity, with possible causes including an inoperative compressor, lost charge or a sensor fault.
Trane says DFT FAULT B means ten defrost cycles ended at the time limit. DFT FAULT C means the sensor temperatures are too far apart. Those descriptions give the technician a path through the defrost system; neither is a homeowner instruction to force another cycle.
If you can see the unit safely, describe the ice coverage without reaching through the grille. For the difference between frosting and a unit staying iced over, see a heat pump frozen in winter.
Pressure stops and the lockout that follows
Look for the alert before the hard lockout
For HP SHORT LO, Trane gives a five minute compressor lockout and a thermostat message of Wait. The control then restarts at reduced capacity. In heating, its possible causes include an indoor fan failure or clogged coil, as well as refrigerant conditions.
Trane’s 80.01, HP HARD LO, follows six high pressure short lockout events. Its chart says compressor operation remains locked out until power is cycled. That is a reason to investigate the pressure trips before treating power cycling as a repair.
For low suction pressure in heating, Trane uses outdoor group 184, subalarm 4, with LSPP HTG CO and a thermostat message of Wait. Its possible causes include low charge, a restriction, pressure sensor calibration or outdoor temperature below minus 10 degrees F.
Trane’s 184.07 means the maximum number of protection shutdowns has been reached. For 184.08, the general hard lockout message, Trane specifically directs the technician to investigate the alerts that led to it. Preserve that history for the visit.
What the outdoor lights tell the technician
On this integrated variable speed control, Trane identifies the STATUS light separately from COMM. A flash count only helps when you know which light it came from.
| Trane STATUS pattern | Meaning on this board |
|---|---|
| Once per second | Standby or idle |
| Twice per second | A capacity request |
| Five times per second | Power up delay |
| Steady | Test mode |
| One flash every four seconds | Hard lockout |
Trane’s COMM light instead flashes a device count in normal communication, or five times per second for lost communication. These patterns belong to the outdoor control named here; do not count the indoor air handler light against this table.
What each one takes
| Finding | Work involved |
|---|---|
| 67 sensor alert | Checking the named sensor and its circuit |
| Defrost fault | Checking capacity and sensor behavior against the defrost sequence |
| 80.01 pressure lockout | Finding the pressure problem before returning the compressor to service |
| 184.07 or 184.08 | Reading earlier alerts and tracing the shutdown cause |
| 155.02 outdoor valve motor fault | Electrical testing of the outdoor expansion valve motor circuit |
Questions people ask
Can 155.02 stop heating but leave cooling working?
Yes. Trane’s chart says that outdoor expansion valve motor fault prevents heating while allowing cooling. It lists an open or shorted motor coil as the cause to investigate.
Does clearing history only tidy the display?
No. Trane’s technician menu notes say clearing alert history also clears active alerts and resets the outdoor control. Leave it intact while the fault is being diagnosed.
Does Wait always mean high pressure?
No. In this chart Trane uses Wait for high pressure short lockouts and several other protective stops. The outdoor alert text and history identify which one occurred.
Can I use this chart for every XV or XL model?
Match the complete model to the four listed at the top. This page does not assign the 2013 control’s codes to other outdoor platforms or newer revisions.
Where can the repairer find the full table?
The Trane 4T-V0-SF-1A Service Facts PDF starts its variable speed alert tables on page 19. The file includes the outdoor light chart and diagnostic procedures.
The other heat pump guides: resetting and normal waits, the outdoor unit not running, and aux heat on the thermostat.
Sources: Trane Service Facts 4T-V0-SF-1A, September 2013, 4TWV0024A1000A, 4TWV0036A1000A, 4TWV0048A1000A and 4TWV0060A1000A; pages 1-2, 11-14, 19-21, 26 and 50-51; data/sources/trane-heat-pump-codes