On Rheem's RP17 outdoor control, d means defrost, 21 means the low pressure control is open, and 29 means the high pressure control is open. An alternating L marks a lockout. Code 16 needs the accompanying EcoNet message because the RP17 manual gives it several meanings.
Rheem heat pump error codes need the outdoor model number beside them, especially if the display says 16. Rheem’s RP17 manual uses that number for several inverter faults, while 21 and 29 point to the refrigerant pressure controls.
This guide covers the RP17 three stage outdoor heat pump and its EcoNet variable speed unitary control in manual 92-105074-05 Rev. 05. Match that document to your equipment before using the list.
Before you start
What to carry: a torch, phone and pen. You are gathering information for the repair, with the service covers closed.
Gas or electric? This page follows the electric outdoor heat pump. For a code at the gas furnace, use Rheem furnace error codes; a hybrid hot water tank belongs on the Rheem water heater code page.
Renting? Send the model and displayed message to whoever handles heating repairs for your home.
Do not press the board’s TEST button to clear a complaint. Rheem says that button can energize the compressor without a thermostat call.
Read the whole message
Match the display to the outdoor control
Record the outdoor model, the full EcoNet text and whether the house is still warming. If a technician has supplied a board reading, keep its sequence too: 21 followed by L is more useful than just 21.
Rheem warns that its board codes must be read from the correct side. A photograph taken upside down can send the diagnosis in the wrong direction.
On this RP17 control, Rheem calls 0 standby, h low stage heating, H high stage heating, and d defrost. Its c and C displays are the cooling stages. Those steady mode letters are operating information, not an instruction to replace a part.
RP17 codes to look up
These meanings come from Rheem’s RP17 control description and diagnostic chart. This is a selected outdoor code list, not a chart for every Rheem heat pump or every EcoNet appliance.
| Display | Rheem’s RP17 meaning | Where the diagnosis goes |
|---|---|---|
| 09 | Low control supply voltage | Transformer loading and supply checks |
| 16 or L with 16 | Several inverter or configuration faults | Full EcoNet message, explained below |
| 21 | Low pressure control open | In heating, outdoor ice is one possible cause |
| 21 alternating with L | Low pressure protection lockout | Heating lockout conditions below |
| 27, 28 | Incoming AC voltage too low or too high | Electrical supply diagnosis |
| 29 | High pressure control open | In heating, indoor blower operation is one check |
| 29 alternating with L | High pressure protection lockout | Pressure trip investigation |
| 31 | Compressor outside its allowed operating range | Operating conditions and refrigerant checks |
| 35, 36, 42 | Suction temperature, suction pressure or compressor temperature sensing fault, respectively | Sensor and connection tests |
| 83, 84 | Outdoor coil or outdoor air temperature sensing fault, respectively | Sensor position, connection and readings |
| 93 | Failure restoring configuration data | Control and model data checks |
Code 16 needs more than a number
Use the EcoNet detail with code 16
Rheem’s RP17 description names T926_O as missing high pressure switch configuration in the inverter. It also puts A929_O communication failure under L16, and A959_O supply brownout in the same section.
Those are different jobs. Configuration, communication and incoming power do not all call for the same replacement part.
For A959_O specifically, Rheem says the control stops the compressor during the low voltage condition and restarts it after voltage recovers. That automatic recovery does not apply to every fault shown with 16.
Pressure codes when you need heat
Separate a pressure trip from its possible cause
For 21 in heating, Rheem lists a frozen outdoor coil among the possible causes. From outside the cabinet, notice whether the coil is lightly frosted or buried in ice, and pass that observation along. The manual also lists low refrigerant charge and an expansion valve problem.
For 29 in heating, Rheem’s chart points to an indoor blower that is not running, alongside a liquid line restriction or excessive refrigerant charge. Notice whether air is coming from the house vents. A pressure code by itself is not a refrigerant refill instruction.
In heating, Rheem says three low pressure trips within 120 minutes during the same heating call trigger a hard lockout, displayed as 21 followed by L. It separately describes a cold weather soft lockout after three openings during a heating call below minus 10 degrees F.
For that cold weather case, Rheem says protection clears when outdoor temperature rises above minus 10 degrees F. Rheem also tells the technician to wait until it is warmer than that before further diagnosis. Tell the technician how cold it was when the trouble began; the heating behavior differs from the cooling chart.
Defrost and the two outdoor sensors
Tell d apart from 83 and 84
Rheem identifies d as an active defrost cycle. By contrast, its RP17 list assigns 83 to coil temperature sensing and 84 to outdoor air temperature sensing. Do not buy a defrost board just because one of those numbers appears.
Rheem’s sensor section says an ambient sensor failure makes this control initiate defrost every 34 minutes in heating when coil temperature is below 35 degrees F. The condition matters: it is not a normal defrost schedule for all Rheem models.
For a pump that is cold without one of these messages, continue with heat pump not heating. That guide handles the comfort checks this code list does not.
What happens after the fault is found
Rheem’s RP17 reset section lists cycling line power or the control’s 24 volt supply after active protection lockout. Leave that procedure to the person diagnosing the fault, especially the method involving control wires. A reset removes the stop; the pressure, sensor or supply problem still needs attention.
For a replacement control, Rheem says the correct model data must transfer from the old board and forbids using another unit’s memory card. Include any recent board replacement in the repair history.
What each one takes
| Finding | Work involved |
|---|---|
| Normal mode or defrost display | Observation, with no part ordered from that display alone |
| 21 or 29 pressure protection | Service diagnosis of the relevant airflow and refrigerant conditions |
| 83 or 84 sensing fault | Sensor checks before any replacement |
| Voltage or communication complaint | Electrical testing and connection checks |
| Configuration problem after board work | Correct model data and control setup |
Questions people ask
Is this the list for my RP17H side discharge unit?
This page uses the RP17 three stage EcoNet manual named at the top. Do not select it from the RP17 letters alone; match the complete model and document.
Does a flashing h mean the heating has failed?
Rheem’s RP17 control description allows h to flash while a compressor timer is active. Distinguish that letter from a numbered fault before treating the wait as a breakdown.
Should I replace the compressor for code 31?
Rheem says the control first slows the compressor if its calculated torque exceeds the allowed range, then stops it if slowing does not help. That code alone is not a compressor replacement diagnosis.
Can I use a Rheem furnace pressure switch chart?
Use the chart for the equipment showing the complaint. The outdoor RP17 list here concerns refrigerant pressure controls; the furnace has its own guide.
Where is the PDF used for these codes?
Rheem provides RP17 installation instructions, revision 05. Its control descriptions begin on page 40 and diagnostic charts on page 56.
The other heat pump guides: resets and lockouts, a heat pump frozen in winter, and an outdoor unit that is not running.
Sources: Rheem RP17 installation instructions 92-105074-05 Rev. 05, pages 3, 40, 43-51 and 55-59; saved in data/sources/rheem-heat-pump-codes/rp17-install.pdf