Boiler Circulator Pump Not Working or Won’t Stop Running
First check whether anything asks the pump to run: the thermostat and the relay's lights, then its power. On a Taco 007e, red means a locked or sticking rotor, and power off and on starts about 15 minutes of restart tries; with its light on and the house cold, Taco says the system may be air bound. A short run after the heat stops can be normal.
A boiler circulator pump not working stops the heat at the boiler. John Barba, a trainer, in an article on Taco’s site, puts the pump’s job simply: the boiler makes the heat, the radiators or baseboard deliver it, and the circulator carries it out and back.
The pump can also be fine and simply not asked to run, or be asked and not get through. So this page goes in order: is anything asking for it, does it have power, is it turning, and is it moving any water.
Before you start
What to carry: a torch, gloves, a long screwdriver for Taco’s listening test below, and a phone to photograph the pump’s label and any relay box near it. A Taco 007e’s restart tries take about 15 minutes, Taco says.
Gas, oil or electric? The pump has its own power supply: Taco’s 007e runs on 110 to 120 volts. For electric baseboard heaters, see a baseboard heater not working.
Which pump is it? Read the label. Taco’s 007e has a coloured light, orange when powered and green in its Green Mode. The Taco 007-IFC has a three speed dial. Grundfos’s ALPHA2 has a display and light fields, and Bell and Gossett makes the NRF. Taco’s Priority Zoning Circulator has its own relay and a green light.
One pump, or one per zone? HUD’s rehab guide says each zone has its own temperature control, with a small pump or a zone valve in each loop. With zone valves on a control such as Taco’s ZVC403, one system pump turns on when any valve opens: a zone valve not working.
Renting? New York’s tenants’ rights guide from the Attorney General says landlords are required to keep the heating system in good and safe working order, so tell the landlord.
Power off before any cover comes off. Grundfos says switch off the power before starting any work on its pump, and make sure it cannot be switched on by accident. Taco says disconnect the power when servicing.
Hot and under pressure. Grundfos says the pumped water may be scalding hot and under high pressure, so before the pump is taken apart the system is drained or the valves on either side are closed. Taco says let the system cool first to prevent scalding, and Bell and Gossett says let the water cool to at least 100 degrees before draining.
Never run it dry. Taco says never run its 007e dry, or permanent damage may result, and Bell and Gossett says the same of its NRF.
A leaking pump. Bell and Gossett says any leak or sign of one means repairing or replacing the unit.
What is the pump doing?
Turn the thermostat up, then stand by the pump and look and listen.
Silent with no light points to no call or no power: checks 1 and 2. A light on but not turning points to a stuck rotor: check 3. Running while the house stays cold points to air, a closed valve or low pressure: check 4. Noisy: check 5. Running when no heat is wanted: check 6.
It will not run
Is anything asking it to run?
Read the relay’s lights. On a Taco SR501 switching relay, Taco says the green light should always be on, showing the power is connected and the fuse is good, and the red light comes on when a thermostat calls, sending power to that zone’s pump. If the red light does not come on, check the thermostat and its wiring. Argo’s ARM relays light “Circulator On” when the relay closes, and Taco’s Priority Zoning Circulator turns its green light on when the thermostat calls.
Zone valves call the pump. On Taco’s ZVC403 zone valve control, the system pump and boiler turn on when any zone valve opens, so a valve that never opens leaves the pump off.
The thermostat. If no light comes on with the thermostat turned up, see a thermostat not working. Grundfos’s own list for too little heat includes checking the thermostat’s setting and replacing its batteries.
It may be waiting on purpose. With Taco’s SR502 relay wired to a boiler control that has a low limit, Taco says the pump comes on only once the boiler is above that low limit. Bosch says that in summer mode, or warm weather shutdown, its Greenstar switches the heating pump off while hot water stays on.
Is it running, and does it have power?
Listen to it. On a Taco 007, Taco’s test is to put a screwdriver’s tip to the pump casing and the handle to your ear, have someone switch the boiler off and on, and listen for the pump to slow down and speed up. Taco says the pump is so quiet you would normally only hear a hum.
Read its light. Taco’s 007e shows an orange light when it is powered. With the light off and the pump not running, Taco’s causes are no power supply, a tripped breaker, which it says to check at the panel and reset if needed, a failed pump, or overheating. For overheating it says let the pump cool for some minutes, then try to restart it, and check the water and room temperatures are within its ratings. Grundfos gives the first three for an ALPHA2 whose light is off.
A breaker that trips again: see a breaker that keeps tripping. The boiler’s own switch and breaker are in a boiler not working.
A light on, but stuck
A Taco 007e with a red light. Taco says red means the pump is locked or sticking. Switch the power off and on to start its automatic release: it makes 100 attempts to restart over about 15 minutes, with a short white flash at each. If it still shows red after that, Taco’s next steps mean closing the valves, letting the pump cool and taking the motor off to clean the impeller. Taco says servicing this double insulated pump should be done by qualified service personnel. Taco’s table also gives too low a supply voltage for a red light, which a technician checks against the name plate.
A Grundfos ALPHA2. With its light on and the pump not running, Grundfos lists a rotor blocked by dirt, cleared by removing the impurities, a technician’s job, or a supply voltage that is too high.
Why pumps stick. Burnham’s Alpine control runs each pump for 20 seconds after it has sat unused for more than 7 days, to help stop the rotor seizing. In its manual summer mode, Grundfos’s ALPHA2 starts the pump for two minutes every 24 hours, to stop lime deposits blocking it.
Three speed pumps. On a Taco 007-IFC, a new motor or cartridge goes in with the pressure at 0 psi, the system at room temperature and the pump closed off by its valves or drained, Taco says. That is a technician’s job.
It runs, but the heat does not come
Air, a closed valve, or low pressure
Air. Taco’s 007e table gives a house that does not warm up, with the light on, as a system that may be air bound: vent it, and have the installer repeat the fill and purge steps. Taco lists air as the cause of loud water noise with a flashing white light, too. Grundfos says you cannot vent the system through its pump, and Weil-McLain’s gas boiler manual says bleed air through the vents on the radiators or baseboard: see a radiator not heating. Taco also asks whether the system was drained lately, which can leave an air block.
The valves. For an ALPHA2 running dry, Grundfos says make sure the system is filled and vented and open the isolating valves. For too little heat, it says make sure all valves are working, with lime deposits removed. A closed zone valve is in a zone valve not working.
The pressure. For a noisy ALPHA2, Grundfos lists too low an inlet pressure: raise it and check the air in the expansion tank, a technician’s job, as pressure leaks can lead to cavitation. Taco gives cavitation from low suction pressure as a cause of a noisy 007e. Weil-McLain’s gas boiler user manual says never add cold water to a hot boiler, as the shock can crack the heat exchanger. For low pressure, it says fill to the correct pressure and have a technician repair any leak at once. See boiler pressure.
The speed setting. Grundfos lists the pump set too low as a cause of too little heat, fixed by raising its speed. Ask the installer before changing it.
It is noisy, or will not stop
A noisy pump
Air in the pump. Grundfos says air in its ALPHA2 may cause noise that stops after a few minutes running. A short spell on speed III vents it faster, and once the noise stops Grundfos says set the pump back to its recommended setting.
The rest of Grundfos’s list. In the pump: too low an inlet pressure, or no water in it. In the system: air, too much flow, which means reducing the speed, or pipes growing as they warm, which means checking their brackets.
Taco’s list for the 007e. A noisy pump with its light on can mean cavitation from low suction pressure, or something caught in the impeller, which means taking the motor off to clean it: a technician’s job. More sounds are in a boiler making noise.
A pump that keeps running
Running on after the burner stops is normal. Weil-McLain’s EG and PEG manual says that when the water is hot enough the burner shuts off and the circulator keeps running until the thermostat is satisfied. Burnham’s MPO-IQ and Series 2E have a circulator overrun that runs on after the call ends to send out the boiler’s leftover heat, and Lochinvar’s Noble runs its boiler pump on for a factory set 30 seconds.
Short runs with no call. Burnham’s Alpine exercises an idle pump for 20 seconds after 7 days, and Caleffi’s ZSR multi-zone pump control, with exercise switched on, run each pump for 30 seconds after 72 hours. Rinnai says its I-Series Plus may run the pump to stop the boiler freezing.
Running all the time. If a Taco SR501’s red light stays on with the thermostat turned right down, Taco’s own reading of that light is power going to the pump, so have a technician check the thermostat, its wiring and the relay. A zone that keeps heating is in a radiator that won’t turn off.
After it is fixed
Watch one full cycle. Thermostat up: the relay light, then the pump, then warm pipes. Thermostat down: the pump stops, after any run-on the boiler’s maker describes.
Keep the water in. Bell and Gossett recommends service valves on both sides of every circulator, so it can be serviced or replaced without draining the system; ask for them if yours has none.
What each one takes
| What stops it | What it takes |
|---|---|
| No call from the thermostat | A thermostat or wiring fix |
| A tripped breaker | Resetting it at the panel; the breaker guide if it trips again |
| A stuck rotor on a Taco 007e | Power off and on, then about 15 minutes of restart tries |
| A rotor still stuck | A technician to clean it, or a new pump |
| Air in the system | Bleeding the radiators or vents, or a technician to purge it |
| Low pressure | Refilling with the boiler cold, the way its maker says, and a technician for any leak |
| Power to the pump with no call | A technician to check the thermostat, its wiring and the relay |
| A leak | A repaired or new pump, from a technician |
Questions people ask
How do I know if my boiler circulator pump is running?
On a Taco 007, Taco’s test is a screwdriver tip on the casing and the handle to your ear while someone switches the boiler off and on. A Taco 007e also shows an orange or green light when it has power.
Why does my boiler pump keep running after the heat shuts off?
It can be by design: Weil-McLain’s EG and PEG, Burnham’s MPO-IQ and Series 2E and Lochinvar’s Noble manuals all describe the pump running on after the burner or the call stops. A pump that never stops, with the thermostat turned right down, is one for a technician.
Can a stuck circulator pump be freed?
A Taco 007e tries by itself: switch the power off and on and it makes 100 attempts over about 15 minutes. After that, freeing the impeller means taking the motor off, a technician’s job.
Is it normal for a circulator pump to be hot?
Grundfos warns of a hot surface on its ALPHA2, and says the water it pumps may be scalding hot. A Taco 007e that has overheated needs to cool for some minutes, and Taco says check the water and room temperatures are within its ratings.
Can I replace a circulator pump myself?
Taco and Grundfos both say power off and closed valves or a drained system first, and Taco says let it cool. Taco says servicing its double insulated 007e should be done by qualified service personnel. It is a technician’s job.
The other boiler guides: a zone valve not working, boiler pressure, a boiler making noise, a boiler not working and radiant floor heating not working.
Sources: Taco 007e and 007-IFC instruction sheets, SR501 and SR502 switching relay sheets, ZVC403 sheet, Priority Zoning Circulator sheet, flow control valves FAQ and its circulator article, Grundfos ALPHA2 instructions, Bell and Gossett NRF circulator manual, Argo ARM switching relay manual, Caleffi ZSR pump control manual, Burnham Alpine, MPO-IQ and Series 2E manuals, Lochinvar Noble manual, Weil-McLain gas boiler user manual and EG and PEG Series 7 boiler manual, Bosch Greenstar operating instructions, Rinnai I-Series Plus manual, the HUD Rehab Guide and the New York Attorney General's tenants' rights guide