Home / Boilers / Boiler Making Noise: Kettling, Banging, Gurgling, Whistling

Boiler Making Noise: Kettling, Banging, Gurgling, Whistling

Ray BennettBy Ray Bennett · Updated 26 September 2026 · 11 min read · Checked against the sources at the end
Boiler Making Noise: Kettling, Banging, Gurgling, Whistling
Short answer

Gurgling in hot water pipes is air: bleed the radiators, Weil-McLain says. Popping or rumbling inside the boiler points first to scale from a leak topped up with fresh water; a technician de-limes it. Banging steam pipes mean water left where the steam flows: open the radiator valves fully and check the pitch. A bang as the burner lights means turn it off, stop resetting it and call a technician.

A noisy boiler is usually telling you about air, scale or water in the wrong place, and the makers’ manuals name each sound. Some are yours to fix in minutes. Two are not.

Start by noticing when the noise happens, because that points at the cause.

Before you start

What to carry: a torch, and your phone to record the noise and note when it happens. Five minutes to look, then listen through one whole heating cycle, from the burner lighting to it shutting off.

Gas, oil or electric? Most of these noises come from the water and the pipes, so they are the same for all three. A bang as the burner lights only happens on gas or oil, and oil burners have two noises of their own, near the end.

Hot water or steam? A hot water boiler has a round gauge and pumps. A steam boiler has a round gauge too, but also a glass tube on its side showing the water level. Steam systems bang for their own reasons, covered below.

Two noises mean stop, and one rule. A bang or boom as the burner lights. Burnham says late ignition is the cause of start-up noise on its oil boilers, and it is a technician’s check. Triangle Tube says its recalled Prestige boilers can release carbon monoxide due to delayed ignitions. If you smell gas, do not touch any electrical switch, the boiler’s included: Weil-McLain says to call the gas supplier from a phone outside the building. Otherwise, turn the boiler off and do not keep resetting it. If a carbon monoxide alarm sounds, do not stay to find the source: CPSC says move outside to fresh air right away, call 911, and stay out until the responders say you can go back in.

Hissing or water from the relief valve. That is the brass valve with a lever and a pipe running down to the floor. Keep clear of the end of its pipe, because Watts warns the discharge can scald, and never cap or plug it: Watts says no shutoff valve may go in its discharge line. Watts also says that when it lets go, a licensed contractor must find and correct the cause right away: boiler pressure too low or too high.

Never add cold water to a hot boiler to quiet it. Weil-McLain says the thermal shock can crack the heat exchanger.

What the noise usually means

WHAT THE NOISE USUALLY MEANS Gurgling in hot water pipes or radiators Air in the system: bleed the radiators You Popping or rumbling in the boiler Scale inside it, or too little water flowing through A pro Rushing water or loud water noise Water moving too fast, or the pressure too low You first A bang when a zone valve closes Water hammer; Weil-McLain recommends a bypass valve A pro Ticking or creaking as it warms up Pipes expanding against loose brackets You Banging steam pipes or radiators Water left where the steam flows: valves and pitch You first A bang as the burner lights Late ignition: turn it off, do not keep resetting it Stop
The sounds the makers' manuals name, what each one points at, and who deals with it.

Some noise is normal. Navien says not to mount its boilers on a shared wall, because the unit makes some operating noise while it runs.

Hot water boilers

Check 1Free, a radiator key

Gurgling: air in the system

What it is. Weil-McLain’s troubleshooting table says radiators or baseboard that are noisy because of air in the system are fixed by bleeding the air through their vents. Viessmann says gurgling is caused by air in the radiators, and Lochinvar lists air in the piping as a cause of noisy operation.

The fix. Bleed the radiators or baseboard the way the makers describe: how to bleed a radiator. Viessmann warns the escaping air may be hot, so keep your hand and face clear. Then check the pressure gauge, because bleeding lets some water out. Never bleed a steam radiator: Castrads says its vent lets the air out by itself.

A noisy pump. Grundfos says air in its ALPHA2 pump may make a noise that stops after a few minutes of running, and that the system cannot be vented through the pump. Taco says loud water noise from a 007e with a flashing white light means air in the system, and the system should be vented.

Check 2A technician to de-lime it

Popping or rumbling inside the boiler

What it is. Weil-McLain’s tables call it a popping or percolating noise in the boiler. The first cause they give is mineral deposits from constant use of fresh make up water. People call this kettling, because it sounds like a kettle coming to a boil.

Why it happens. A leak lets water out, the fill valve tops it up with fresh water, and that water brings in minerals. Weil-McLain says those minerals build up in the boiler, overheat the metal and can cause section failure.

Weil-McLain’s other causes. The wrong pH in the boiler water, and too little water flowing through the boiler. Lochinvar’s chart for a noisy Knight also lists low water flow through the heat exchanger, and its fix is to check the boiler and system pumps are running on a call for heat.

What you can do. Look for drips along the pipes and radiators, and watch the pressure gauge for a slow fall, though a fill valve that tops the system up by itself can keep the gauge steady and hide a leak: why boiler pressure drops. For too little flow, Weil-McLain says to check that all the valves to and from the boiler are back at their proper setting.

What a technician does. Weil-McLain says a qualified technician de-limes the boiler if necessary, repairs the leaks and checks the pH, which should be between 7.0 and 8.5. It warns that in some cases the deposits are too heavy to remove.

Check 3Free to check the gauge, a technician for the rest

Rushing water, whistling or humming

Water moving too fast. Honeywell says water noise at its zone valves can come from excessive water velocity. Grundfos’s fix for noise in the system when the flow is too high is to reduce the pump speed.

Pressure too low. Lochinvar lists low system water pressure among the causes of noisy operation, and says to verify the system is at a minimum of 12 psi. Grundfos says noise in the pump can come from too little inlet pressure, and says to check the air volume in the expansion tank, a technician’s job. Taco’s remedy for a 007e that is noisy from too little suction pressure is to raise the system pressure within its limits.

A pump humming through the house. Taco says to add vibration dampeners to the piping when a circulator is mounted to a wall or floor joists, to reduce noise traveling through them.

The burner itself. Lochinvar’s chart for a noisy Knight also lists a gas supply problem, a wrong gas and air mixture, and a dirty or damaged burner. Those are all technician jobs.

Check 4A technician fits the fix

A bang when a zone valve closes

What it is. Water hammer: the moving water stops suddenly as a valve shuts. Weil-McLain recommends a pressure bypass valve on zone valve systems, to prevent too much flow through a single zone and water hammer when the valves close.

What you can do. Note which zone bangs and when, so the technician can find it quickly.

Check 5Free, a screwdriver

Ticking or creaking as the pipes warm

What it is. Pipes growing as they heat and rubbing on whatever holds them. Grundfos lists thermal expansion of system parts as a cause of noise in the system, and its fix is to check the pipe brackets and secure any loose ones.

What you can do. With the heat off and the pipes cool, look where the pipes pass through joists and brackets, and tighten anything loose.

Steam boilers

WHERE STEAM PIPES START TO BANG A sag, or too little pitch, holds water in the main Valve left half open open it all the way Must lean back toward its valve At the boiler: wet steam from wrong piping, or sludge inside
The places steam pipes start to bang, from the Peerless, Burnham, Castrads and Danfoss instructions.
Check 6Free to check the valves, a technician for the piping

Banging or clanking pipes and radiators

At the radiator. Castrads says a one-pipe steam radiator’s valve must be fully open or fully closed, because leaving it halfway open can cause very noisy steam hammer. Turn it with the boiler off and the radiator cold, and do not force one that will not move. Danfoss’s one-pipe steam instructions say free standing radiators must be properly pitched, so the water can drain back: the radiator should lean slightly down toward its valve, never toward the vent.

A big radiator that bangs halfway through a cycle. Peerless says a large radiator vented too quickly can hammer, and the fix is a smaller air vent, or two small vents with one higher than the other.

When it bangs tells the technician where to look. Peerless’s troubleshooting table lists these causes:

When it bangs What Peerless lists
As the heat comes on Sags in the steam piping or not enough pitch, a drip trap failed closed, or a new boiler’s water line higher than the old one
Halfway through Wet steam from wrong piping at the boiler, a trap failed open, a long nipple at the Hartford loop, or bare steam pipes
As it shuts off The close nipple on the Hartford loop set too high, or bare steam pipes in the boiler room while the system piping is insulated
Inside the boiler Poor circulation from sludge: clean and blow down the boiler

Wet steam. Burnham says wrong piping at the boiler sends wet steam into the system, and hammering is one of the problems that may follow.

The water level. Weil-McLain says normal is halfway up the gauge glass. Burnham says a steam boiler is surging when the water in the glass bounces or disappears while it makes steam, and Hydrolevel says foaming comes from oils, minerals and other dirt in the water. Peerless says an erratic water level with dirt in the glass means the boiler needs skimming. Those are jobs for a steam technician. If the glass shows no water at all, turn the boiler off and let it cool before any water goes in, because of the thermal shock Weil-McLain warns about.

Check 7The price of a vent

Hissing or whistling radiator vents

A soft hiss as the radiator heats is normal. Castrads says the steam pushes the air out through the vent, which closes by itself when the radiator is full of steam.

A loud whistle as the radiator fills. DOE’s Building America steam report says a vent that whistles loudly as the radiator fills may have too small an opening, and should be replaced. It says a whistle can also mean dirt clogging the opening, or the boiler running at a higher pressure than it needs.

A vent that hisses steam or spits water. DOE says to replace any one-pipe steam vents that are clogged or stuck open. Danfoss’s list for a spitting vent is to check the radiator’s pitch, open the supply valve fully, check the riser air vent for the main system, and check for too much pressure.

Replace a vent with the boiler off and the radiator cold.

Oil burners

A rumble or thump at start up. Turn the boiler off and do not keep resetting it, as in the warning at the top. Burnham says late ignition is the cause of start-up noise, and the technician rechecks the electrode settings, the flame shape, and for air or water in the fuel lines.

A puff or rumble at shut down. Burnham says this after burn happens when the flame runs out of air before it runs out of fuel. It lists a faulty cut off valve in the fuel pump, air trapped in the nozzle line, water in the fuel or a poor flame shape. Burnham says air trapped in the nozzle line can take several firing cycles to clear. All of these are for an oil burner technician.

If it locked out after a bang or a puff, leave it off for the technician rather than resetting it. For other lockouts: Beckett GeniSys reset.

What each one costs

The noise Cost
Gurgling, bled out of the radiators Nothing, a radiator key
Ticking pipes, brackets tightened Nothing
Steam radiator valve opened fully Nothing
A steam radiator vent replaced The price of the vent
Kettling, zone valve hammer, pump or burner noise A service visit
Steam piping or a Hartford loop repiped A steam technician’s quote

Questions people ask

Is it normal for a boiler to make noise?

Some. Navien says its boilers make some operating noise while they run. Gurgling, popping, banging or whistling are not normal, and each points at something the makers name.

What is boiler kettling?

A popping or rumbling inside the boiler as it heats. Weil-McLain’s first cause is mineral deposits from constant fresh make up water, usually because of a leak, and a qualified technician de-limes the boiler if necessary and fixes the leak.

Why is my boiler gurgling?

On hot water, air in the system. Weil-McLain’s fix is to bleed it through the vents on the radiators or baseboard. Then check the pressure, because bleeding lets some water out. Never bleed a steam radiator.

Why do my pipes bang when the heat comes on?

On steam, Peerless lists sags in the piping or too little pitch first, and Castrads says a radiator valve left halfway open can cause steam hammer. On hot water, Grundfos lists pipes expanding against loose brackets as they warm, and a bang when a zone valve closes is water hammer, which Weil-McLain recommends a bypass valve to prevent.

Why does my boiler bang when it lights?

Late or delayed ignition. Burnham names late ignition as the cause of start-up noise, and Triangle Tube says its recalled Prestige boilers can release carbon monoxide due to delayed ignitions. Turn it off, do not keep resetting it, and call a technician.

Can I fix a banging steam radiator myself?

Partly. Open its valve fully, check it leans back toward the valve, and replace a vent that whistles loudly, is stuck open or is painted over, all with the radiator cold. Piping changes are a technician’s job.

Sources: Weil-McLain gas boilers user manual 550-100-226 and WGO Series 4 oil boiler manual, Lochinvar Knight service manual, U.S. Boiler Company (Burnham) MPO-IQ and Independence instructions, Peerless Series 63/64 manual, Navien NCB-E installation manual, Taco 007e circulator instructions, Grundfos ALPHA2 manual, Honeywell V8043 zone valve instructions, Hydrolevel CycleGard CG450 manual, Castrads one-pipe steam guide, Danfoss RA2000 One Pipe Steam instructions, Viessmann "Bleeding the heating system", DOE Building America steam balancing report, DOE "Heat Distribution Systems", Watts 174A relief valve tag, Triangle Tube 2025 recall notice and CPSC "Carbon Monoxide Questions and Answers"