Home / Air conditioning / Leaky Ductwork: How to Find and Fix Duct Problems

Leaky Ductwork: How to Find and Fix Duct Problems

Ray BennettBy Ray Bennett · Updated 2 October 2026 · 5 min read · Checked against the sources at the end
Leaky Ductwork: How to Find and Fix Duct Problems
Short answer

ENERGY STAR says a typical house loses about 20 to 30 percent of the air moving through its ducts to leaks, holes and poor connections. The usual spots are the joints, the registers where they meet the floor or ceiling, the furnace and its filter slot, and crushed flexible duct. Seal them with mastic or metal tape, never duct tape, then insulate the ducts you can reach.

Most ductwork is out of sight, in an attic, a crawlspace, a basement or inside the walls, so a leak can run for years. ENERGY STAR puts the loss in a typical house at about 20 to 30 percent of the air that moves through the ducts, lost to leaks, holes and poorly connected ducts.

That air has been heated or cooled and paid for, then dumped where nobody lives. This page brings together what ENERGY STAR and the Department of Energy say: the signs, where ducts leak, how to seal them, and what to leave to a contractor.

Before you start

What to carry: a torch, gloves, a stiff brush for the mastic, and a roll of fiberglass mesh tape. Half an hour to look, longer to seal.

Gas or electric? Either. The same ducts carry the air for a gas furnace, a heat pump or an air conditioner.

Water, not air? Ducts that drip in summer are usually sweating, not leaking: why ducts sweat.

Two things before you seal anything. Gas appliances nearby. ENERGY STAR says leaky ductwork can cause backdrafting, where combustion gases like carbon monoxide are drawn back into the house instead of going outdoors. It says a contractor should make sure there is no backdrafting, and run a combustion safety test after the ducts are sealed.

Never duct tape. ENERGY STAR says never to use it on ducts, because it is not long-lasting. Use mastic or metal tape.

The signs your ducts leak

Check 1

Read the signs

High bills in summer and winter. ENERGY STAR says leaky ducts can cut the efficiency of the heating and cooling by as much as 20 percent.

Rooms that are hard to heat or cool. Or stuffy rooms that never feel comfortable, whatever the thermostat says: one room hotter or colder than the rest.

Ducts in an attic, a crawlspace, an unfinished basement or the garage. ENERGY STAR counts that as a sign on its own.

Tangled or kinked flexible duct. Another of ENERGY STAR’s signs.

A dusty house. ENERGY STAR says fumes from household chemicals, insulation particles and dust can get into the ducts and circulate through the home.

Where ducts leak

WHERE DUCTS LEAK 1 Joints and seams leaky, torn or disconnected ducts 2 Registers and grilles where the boot meets the floor, wall or ceiling 3 The furnace and filter slot a slot with no cover, holes in the cabinet 4 Flexible duct kinks and crushed runs restricting the airflow
ENERGY STAR's four common duct problems. It names the connections at the registers as common places to find leaks.
Check 2Free, half an hour with a torch

Look in the four usual places

Joints and seams. ENERGY STAR’s first common problem is leaky, torn and disconnected ducts. Look where sections join and where the ducts meet the furnace. A room with no air at all may have a duct off completely: nothing from one room.

Registers and grilles. ENERGY STAR says the connections at vents and registers, where they meet the floors, walls and ceiling, are common places to find leaks and disconnected ductwork. The Department of Energy says holes for duct boots are often cut too large.

The furnace and the filter slot. ENERGY STAR lists leaks at the furnace and the filter slot. The Department of Energy’s job aid has a cover fitted where one is missing, one that seals the opening and still comes off easily to change the filter.

Flexible duct. Kinks and crushed runs restrict the airflow. ENERGY STAR’s answer is to straighten them.

How to seal them

SEAL BY THE SIZE OF THE GAP Under 1/4 inch mesh tape over the gap, then mastic over the tape 1/4 to 3/4 inch tape as a backer, mastic, mesh pressed in, then more mastic Over 3/4 inch a patch held with fasteners, then mastic and mesh Never duct tape ENERGY STAR says it is not long-lasting. Use mastic or metal tape.
The Department of Energy's methods, by the size of the gap. Mastic does the sealing; the mesh holds it.
Check 3Free to look, then the materials

Mastic and mesh, by the size of the gap

What to use. ENERGY STAR says mastic sealant or metal tape. Its list for contractors adds an aerosol based sealant.

Clean first. The Department of Energy’s checklist says the duct surfaces that take the sealant must be clean.

Gaps under 1/4 inch. Fiberglass mesh tape over the gap, seam or joint, then mastic over the tape.

Gaps of 1/4 to 3/4 inch. Tape as a backer to hold the mastic, mastic over it, mesh pressed into the mastic, then more mastic at least 1 inch past the edges of the tape.

Holes over 3/4 inch. A patch cut to cover the hole and held with mechanical fasteners, then mastic over its edges and the fasteners, with mesh pressed in.

Round a register. Clean round the boot, bridge the gap from the inside of the boot to the floor or ceiling with mesh tape, keeping it within what the register will cover, and cover it with mastic. Let it dry completely before the register goes back.

Insulate what you can reach

Check 4Free to plan

Seal first, then insulate

Which ducts. ENERGY STAR says to insulate all the ducts you can access, such as those in attics, crawlspaces, unfinished basements and garages.

How much. Its contractor list asks for duct insulation with an R-value of 6 or higher in unconditioned areas.

The order. ENERGY STAR starts with sealing the leaks, then insulating.

It also stops sweating. Insulation with an unbroken vapor barrier keeps damp air off cold metal: why ducts drip in summer.

What a contractor should do

Check 5A quote

Know what to ask for

The whole system. ENERGY STAR says a contractor should inspect all of it, including the attic, crawlspace, garage and basement.

Supply and return balance. ENERGY STAR says many systems have return ducts that are too small.

The repairs. Damaged and disconnected ducts repaired, tangled or crushed flexible ducts straightened, and every leak and connection sealed with mastic, metal tape or an aerosol sealant.

After the work. A new filter, the airflow checked again, and a combustion safety test for gas or oil appliances.

Replacing the equipment anyway. ENERGY STAR says a well sealed duct system may let you choose a smaller, less costly system.

Questions people ask

How much air do leaky ducts lose?

ENERGY STAR says about 20 to 30 percent of the air moving through the ducts in a typical house is lost to leaks, holes and poorly connected ducts.

Can I use duct tape on ducts?

No. ENERGY STAR says never to use duct tape, because it is not long-lasting. Use mastic or metal tape.

Where do ducts usually leak?

At the joints and seams, at the registers where they meet the floor, wall or ceiling, at the furnace and its filter slot, and in flexible duct that is kinked or crushed.

Is sealing ducts worth it?

ENERGY STAR says leaky ducts can cut heating and cooling efficiency by as much as 20 percent, and that sealing and insulating them can often pay for itself in energy savings.

Why is water dripping from my ductwork?

In summer that is usually condensation on cold metal, not a leak. Insulation with an unbroken vapor barrier stops it.

Can I seal my own ducts?

ENERGY STAR says some homeowners do the ducts they can reach themselves, and many hire a contractor. With a gas furnace or water heater, have a combustion safety test done after the sealing.

Sources: ENERGY STAR "Duct Sealing" and its Duct Sealing brochure (EPA 430-F-09-050), and the U.S. Department of Energy job aid "Seal Ducts With Mastic" (19-1, June 2024)